background image

5

2.3 HYDRAULIC INSTALLATION

2.5 PATTERN CONTROL

2.6 USE WITH FOAM

2.4 ELECTRIC INSTALLATION

On nozzles with hydraulic stream shaper actuation, the hydraulic system is connected to the nozzle with two 1/8"-27 NPT (1/4”-18 NPT
on Masterstream 4000) female ports on the filter block located on the nozzle's stream shaper. When the port on the left of the filter block
(as seen from behind the nozzle) is pressurized, the shaper moves back into the wide fog position. Pressurizing the right port moves
the shaper forward into straight stream. Hydraulic lines must be flexible to allow for movement of the stream shaper.

Use only clean fluid compatible with Buna N Compound (Nitrile). System must be free from all dirt, chips and contaminants.
Replacement filter elements are available from TFT (item #M160). Maximum hydraulic pressure is 1000 psi (70 bar, 7000 Kpa) for
Masterstream 1250 or Masterstream 2000 Nozzles. (1500 psi, 105 bar, 10500 Kpa for Masterstream 4000 Nozzle).

TFT's Masterstream Series nozzles have full pattern control from straight stream to wide fog. On models with manual shapers, turning
the stream shaper clockwise (as seen from the operating position behind the nozzle) moves the shaper to the straight stream position.
Turning the stream shaper counterclockwise will result in an increasingly wider pattern.

Since the stream trim point varies with flow, the nozzle should be "trimmed" after changing the flow to obtain the straightest and farthest
reaching stream. To properly trim a stream, first open the pattern to narrow fog. Then close the stream to parallel to give maximum
reach. Note: Turning the shaper further forward will cause stream crossover and reduce the effective reach of the nozzle.

The Masterstream Series nozzles may be used with foam solutions. Refer to fire service training for the proper use of foam.

Nozzles with electric stream shaper actuation are shipped with a wiring diagram (TFT item #LIM-040). Other documentation is
available on request. The actuator is not rated as ignition proof, explosion proof, or intrinsically safe. NOTE: Masterstream 1250 and
Masterstream 2000 nozzles are equipped with manual override in case of electrical power failure. Refer to figure 1D for manual
override instructions.

For Class B fires, lack of foam or interruption in the foam stream can cause a break in the foam
blanket and greatly increase the risk of injury or death.

Avoid using wrong type of foam on a fire, i.e. Class A foam on a Class B fire; Plunging foam into pools of burning liquid fuels; Causing
environmental damage; Directing stream at personnel.

There is a wide variety of foam concentrates. Each user is responsible for verifying that any foam
concentrate chosen to be used with this unit has been tested to assure that the foam obtained is
suitable for the purpose intended.

The electric motor and other components are ignition sources. The electric stream shaper should
be operated only in areas where there is adequate ventilation and no hazard of flammable vapor
buildup.

WARNING

WARNING

WARNING

WARNING

©Copyright Task Force Tips, Inc. 1999-2005

Assure that application rate is sufficient (see NFPA 11 or foam manufacturer's recommendations); Enough concentrate is on hand to
complete task (see NFPA for minimum duration time requirements); Foam logistics have been carefully planned.

Allow for such things as storage of foam in a location not exposed to the hazard it protects; Personnel, equipment and technique to
deliver foam at a rapid enough rate; Removal of empty foam containers; Clear path to deliver foam, as hoses and other equipment and
vehicles are deployed.

Improper use of foam can result in injury or damage to the environment. Follow foam
manufacturer's instructions and fire service training.

2.6.1 FOAMJET LX WITH MASTERSTREAM 1250 NOZZLE

3.0 AUTOMATIC NOZZLE OPERATION

To increase the expansion ratio, Task Force Tips "Foamjet LX" (model FJ-LX-M) may be used with the Masterstream 1250 nozzle. This
low expansion foam tube attaches and detaches quickly from the nozzle. Adjust nozzle spray pattern to give best foam quality. Note:
As expansion ratio is increased, the reach of the nozzle will be decreased due to the greater amount of bubbles in the stream and their
inability to penetrate the air. Generally the reach with foam is approximately 10% less than with water only. Actual results will vary based
on brand of foam, hardness of water, temperature, etc.

Automatic nozzles operate by sensing the pressure at the nozzle's inlet and adjusting the discharge opening to maintain a constant
pressure throughout the flow range of the nozzle. For example, when the pressure at the inlet increases, the exit area is automatically
increased until the inlet pressure returns to the nominal pressure of the nozzle.

Note: Inlet pressure of a Masterstream Series nozzle will stabilize at the nominal pressure (within 5%). This stabilization may take as
long as half a minute after a change in inlet pressure.

LIM-030 October 12, 2005 Rev 05

Содержание Masterstream Series

Страница 1: ...eries firefighting nozzles This manual should be kept available to all operating and maintenance personnel INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE MASTERSTREAM NOZZLE SERIES 150 1250 GPM 100 P...

Страница 2: ...TENANCE WARRANTY 1 0 MEANING OF SIGNAL WORDS A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a particular hazard Per ANSI...

Страница 3: ...the nozzle 2 0 GENERAL INFORMATION Do not couple aluminum to brass Dissimilar metals coupled together can cause galvanic corrosion that can result in inability to unscrew threads or complete loss of t...

Страница 4: ...igures 1A 1E See catalog for model numbers and details FIG 1 Methods for Moving Stream Shaper Fig 1A Stream Shaper moved manually by rotating halo ring Coupling Hydraulic Ports Manual Override Knob Ma...

Страница 5: ...h Avoid using wrong type of foam on a fire i e Class A foam on a Class B fire Plunging foam into pools of burning liquid fuels Causing environmental damage Directing stream at personnel There is a wid...

Страница 6: ...ure Performance WARNING Copyright Task Force Tips Inc 1999 2005 0 0 20 2 40 4 60 6 80 8 100 10 120 140 160 0 0 400 4000 800 6000 8000 1200 1600 2000 2000 2400 FLOW GPM FLOW L MIN PRESSURE PSI PRESSURE...

Страница 7: ...the pressure loss constant from step 2 and the following equation the flow with an automatic nozzle can be calculated for your particular installation Where automatic nozzle flow in GPM or LPM nomina...

Страница 8: ...0 10 20 30 40 50 60 70 80 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 HORIZONTAL DISTANCE FEET VER TICAL D ISTAN CE FEET 0 5 10 15 20 0 10 20 30 40 50 60 70 80 90 METERS METER S A B C D...

Страница 9: ...C D E LPM FLOW 2300 3800 7600 11000 15000 KGF REACTION 130 210 430 640 860 0 10 20 30 60 80 100 120 160 200 240 280 320 360 400 HORIZONTAL DISTANCE FEET METERS METERS B C D E 0 20 40 60 80 100 0 0 20...

Страница 10: ...clears shaft The cylinder and piston will come out as a unit Remove the small spring and stainless steel poppet from the center of the shaft Remove debris Reassemble the nozzle Figures 5A 5B 5C show...

Страница 11: ...rstream 4000 Nozzle Front End Parts RETURN SPRING CYLINDER SHAFT POPPET CONTROL SPRING LUBE LUBE LUBE LUBE PISTON RETURN SPRING CYLINDER SHAFT POPPET CONTROL SPRING LUBE LUBE LUBE LUBE PISTON Copyrigh...

Страница 12: ...ed by TFT It is agreed and understood that the price stated for the equipment is in part consideration for limiting TFT s liability Some states do not allow the exclusion or limitation of incidental o...

Отзывы: