Task Force Tips Crossfire with Safe-Tak 1250 Base Скачать руководство пользователя страница 10

10

Monitor:

1) Handwheel must rotate freely.

2) Elevation stop pin must return to safe position.

3) Quick disconnect latch and safety catch must operate freely.

4) Rotation lock must operate freely and keep monitor from rotating when
engaged.

We recommend the following procedure to test the SAFE-TAK 1250 portable base safety valve.

a) Set up monitor for normal operation.

b) Put a seperate 2-1/2" or larger uncharged hose line or a rescue air bag under one leg. Attach at least 20 feet of air line if you are using
a rescue bag.

c) Point discharge straight ahead, at an elevation angle of approximately 60° with respect to the base. Set safety valve (section 4.6) and
flow water as desired, up to 500 GPM.

d) Charge the additional hoseline or inflate the rescue bag, from at least 20 feet away, until the safety valve trips. Valve trip is indicated
by the valve handle moving to the tripped position and reduction of flow. If valve does not trip, stop all flow at pump and inspect valve
and trip mechanism to determine the cause. If cause can not be determined, contact Task Force Tips at 1-800-348-2686 for additional
assistance.

e) Stay clear of the monitor during this test, as it will move when the valve trips.

The base must be anchored (See section 4.5).

Performance tests shall be conducted on the Crossfie Monitor after a repair, or anytime a problem is reported to verify operation in
accordance with Task Force Tips test procedures. Consult factory for the procedure that corresponds to the model and the serial
number of the Monitor. Any equipment which fails the related test criteria should be removed from service immediately.
Troubleshooting guides are available with each test procedure or equipment can be returned to the factory for service and testing.

5.1 GREASE WORM GEAR

Turn the handwheel to move the nozzle to its highest elevation and pump grease (medium viscosity automotive) into the fitting in the
worm gear housing until excess appears.

5.2 SAFETY VALVE TESTING

5.3 PERFORMANCE TESTS

6.0 SPECIFICATIONS

CROSSFIRE Monitor

SAFE-TAK 1250 Base

Weight

Storage Volume

L-W-H

Height Above Truck Flange

Height Above Truck Deck (min)

Height Above Ground on Base

Line of Reaction Force Above Ground

Flow Area (minimum)

Maximum Flow

Maximum Pressure

Materials Used

Inlets Available

17 lbs

4060 in

20 x 14-1/2 x 14

12-1/2 in

14 in

16-1/2 in

4 in

8.3 in

1250 GPM

175 PSI

Cast Aluminum, Aluminum,

Stainless Steel

One

3

2

24 lbs

1620 in

20 x 9 x 9

NA

NA

NA

NA

8.3 in

1250 GPM

175 PSI

Cast Aluminum, Aluminum,

Stainless Steel

Numerous Single & Double Inlets

2-1/2 in - 5 in

3

2

4

1

3

2

3

2

1

TFTX

-

X

XXXXX

SERIAL

#:

MODEL

#:

XFT

-
NJ

MODEL

#

:

XFT

-
NJ

0

psipsi

200

120

12

80

60

40

20

10

4

0

2

barbar

14

6

8

100

160

180

140

Содержание Crossfire with Safe-Tak 1250 Base

Страница 1: ...t responders to know and understand the following 1 Firefighting and Emergency Response are inherently dangerous activities requiring proper training in their hazards and the use of extreme caution at all times 2 It is your responsibility to read and understand any user s instructions including purpose and limitations provided with any piece of equipment you may be called upon to use 3 It is your ...

Страница 2: ...ase below the elevation safety stop An out of control monitor can cause injury or death To reduce risk of instability do not attempt to move the portable monitor with water flowing Injury can occur from an inadequately supported monitor When the monitor is used on a truck the mounting must be capable of supporting 900 lbs of nozzle reaction force Note the storage bracket is intended for storage of...

Страница 3: ...ety Plunger Pawls Figure 2 1 2 SAFE TAK 1250 BASE Inlet Anchor Strap Storage Cover Stainless Steel Leg Safety Valve Handle Carrying Handle Leg Lock Knob Anchor Attachment Point Figure 2 1 3 Truck Mount Adaptor Companion Flange 3 0 CROSSFIRE DEPLOYMENT 3 1 QUICK CONNECT SWIVEL JOINT The CROSSFIRE monitor can be used on either a truck mounted flange or portable base Installation on either base makes...

Страница 4: ...ise the nozzle and counter clockwise rotation of the wheel will lower the nozzle A spring loaded stop pin limits the nozzle elevation to 35 with respect to the base 3 5 ELEVATION CONTROL AND STOP PIN A sliding monitor can cause injury When used on a portable base keep the horizontal angle between the water stream and the anchor strap as small as possible At large angles the base can slide in an ar...

Страница 5: ...at the user purchase a Deck Mount Plate TFT part XF400 KIT from the manufacturer Please call 1 800 348 2686 for further information and advice concerning mounting alternatives Installation instructions are shipped with this accessory The storage bracket TFT part XF B for the base unit IS NOT STRONG ENOUGH to withstand the forces encountered with an operating monitor and is not intended for this pu...

Страница 6: ...as an attachment point for the anchor strap Set up the portable base with the anchor point between the portable base and desired target of the nozzle stream On ground such as sand mud or gravel wash out under the paddle may cause unwanted tripping of the safety valve on the SAFT TAK 1250 portable base In such case a thin flat object such as a clipboard may be placed under the paddle Object under p...

Страница 7: ...p on the end of the strap may be placed over the anchor point or the strap may be wrapped around an object such as a tree and the snap end of the strap passed through the loop and pulled tight Keep the entire length of the strap as close to the ground as possible Snap the hook into the hole in the front of the portable base below the carrying handle The length of the strap may be adjusted by the s...

Страница 8: ...on force is directed straight down and there is no sideways force that can cause the base to slide As the nozzle is angled downward at the same flow the reaction force remains the same but some of that force becomes a force acting sideways and some acts in a downward direction When the nozzle is at an angle of 45 with respect to the base the force acting sideways is equal to the force acting downw...

Страница 9: ... optional pressure relief valve on the single inlet portable base can be adjusted to open between 50 and 200 psi The pressure relief valve TFT part A1810 is set at the factory to open at 150 psi To change the relief pressure refer to the label on the bottom side of the pressure relief valve A pressure relief valve can be added to the single inlet portable base by removing the cover on the side of ...

Страница 10: ...ance tests shall be conducted on the Crossfie Monitor after a repair or anytime a problem is reported to verify operation in accordance with Task Force Tips test procedures Consult factory for the procedure that corresponds to the model and the serial number of the Monitor Any equipment which fails the related test criteria should be removed from service immediately Troubleshooting guides are avai...

Страница 11: ...X137 O RING 018 1 VO 018 PLUNGER WAVE SPRING 1 X165 SAFETY PLUNGER 1 X150 2 5 NH ELBOW PAINTED 1 X339NJ O RING 241 1 VO 241 DRAIN HOUSING 1 X375 DRAIN VALVE 1 X382 FLAT WASHER 1 VW687X281 50 1 4 28 X 1 2 BHCS 1 VT25 28BH500 O RING 130 1 VO 130 5 16 SS BALLS 76 VB 312 Read instruction manual before use Operation of this device without understanding the manual and receiving proper training is a misu...

Страница 12: ...X440 SHOT PIN SPRING 2 X445 5 32 x 7 8 SPIROL PIN 2 V1900 SHOT PIN 2 X435 BASE 1 X420 BELLEVILLE WASHER 12 D07590 INSTRUCTION LEG LABEL 1 3 1 XL010 FRONT LEG LEFT 1 X470L INSTRUCTION LEG LABEL 4 5 1 XL020 REAR LEG LEFT 1 X460L SPIKE 4 X480 BOTTOM PLATE 1 X450 3 8 16 X 3 4 FLAT HEAD SHCS 4 VT37 16FH750 REAR LEG RIGHT 1 X460R TFT LEG LABEL 1 XL050 FRONT LEG RIGHT 1 X470R SAFE TAK LEG LABEL 1 XL040 P...

Страница 13: ...OR NO VALVE BASE LABEL XL085 2 5 WYE 1 X712 2 5 CLAPPER 1 X772 2 5 CLAPPER GASKET 2 X762 WASHER 2 VW1 9x26 076 1 4 20 x 1 SHCS SS 1 VT25 20SH1 0 O RING 244 1 VO 244 1 4 20 STAINLESS NUT 1 VT25 20NT 1 4 28 X 3 4 BUTTON HEAD 1 VT25 28BH750 PIVOT BOLT 1 X784 O RING 013 1 VO 013 CLAPPER PIVOT 1 X732 REAR SPIKE 1 X482 2 5 NH COUPLING pictured 2 M307N 2 5 COUPLING GASKET pictured 2 V3190 ...

Страница 14: ... COUPLING HEAD STROZ 5 X 5 25 PSF HARDCOAT 1 A4135 28 PORT PLUG MOLDED 1 A1299 31 GASKET 5 PRESSURE MOLDED 9991000 1 A4220 32 BALL 7 16 STAINLESS 302 GRADE 100 1 VB 437 33 MATE PSM4 25 X PSF5 25 HARDCOAD 1 A4730 34 LABEL PORT COVER 1 A1298 35 PLASTIC STRIP 4 25 MOLDED 1 A1292 36 CUP SEAL 4 25 X 3 750 X 1 4 1 A1297 37 COUPLING RL 3 0NHF X PSF4 25 1 A4650N COUPLING RL 3 5NHF X PSF4 25 1 A4655N 38 GA...

Страница 15: ... return the equipment to TFT free and clear of any liens and encumbrances This is a limited warranty The original purchaser of the equipment any person to whom it is transferred and any person who is an intended or unintended beneficiary of the equipment shall not be entitled to recover from TFT any consequential or incidental damages for injury to person and or property resulting from any defecti...

Страница 16: ...2 10 11 Legs are fully opened and locked in place All leg spikes are in contact with the ground Monitor is securely tied down with no slack in anchor strap Safety valve operates freely Monitor is pointed in a safe direction PORTABLE BASE Rotation lock lever securely locks rotation Monitor top freely swivels on base when unlocked Elevation handwheel adjusts elevation freely Nozzle elevation is abov...

Отзывы: