©Copyright Task Force Tips LLC 2021
9
LIX-750 March 11, 2021 Rev00
4.0 FLOW CHARACTERISTICS
The BLITZTAC portable monitor is designed for maximum flow of 500 GPM (2000 L/min) @ 175 PSI (12 BAR) and a maximum operating
pressure of 230 PSI (16 BAR) at lower flows. Do not exceed these limits.
4.1 AUTOMATIC, FIXED, AND SELECTABLE FLOW NOZZLES
A variety of water or foam nozzles may be used with the BLITZTAC portable monitor.
Automatic nozzles maintain a constant pressure by adjusting their opening to match the available flow. Consult the nozzle manufacturer
for maximum flow and pressure ratings. In all cases do not exceed 500 GPM (2000 LPM) @ 175 PSI (12 BAR) or 230 PSI (16 BAR).
4.2 STACKED TIPS OR SMOOTHBORE NOZZLES
Table 4.2
4.3 STREAM STRAIGHTENERS
Stream quality, especially with smooth bore nozzles, is generally improved with the use of a stream straightener. A stream straightener is
integrated into the exit of the monitor.
4.4 USE WITH FOAM
The monitor may be used with various foam nozzles and foam solutions. Refer to fire service training for the proper use of foam.
NOZZLE
DIAMETER
NOZZLE INLET PRESSURE
20 PSI
40 PSI
60 PSI
80 PSI
100 PSI
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
FLOW
(GPM)
REACTION
(LBS)
1-3/8”
251
59
355
119
435
178
500
236
---
---
1-1/2”
299
71
423
141
---
---
---
---
---
---
1-3/4”
407
96
---
---
---
---
---
---
---
---
NOZZLE
DIAMETER
NOZZLE INLET PRESSURE
1.3 BAR
2.6 BAR
3.8 BAR
5.1 BAR
6.4 BAR
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
FLOW
(L/min)
REACTION
(KG)
35 mm
951
27
1344
54
1646
81
1893
108
---
---
38 mm
1131
32
1600
64
---
---
---
---
---
---
44 mm
1540
44
---
---
---
---
---
---
---
---
---
FLOW EXCEEDS RATING OF BLITZTAC PORTABLE MONITOR
WARNING
For Class B fires, lack of foam or interruption in the foam stream can cause a break in the foam
blanket and greatly increase the risk of injury or death. Follow procedures established by the AHJ
for the specific fuel and conditions.
WARNING
Improper use of foam or using the wrong type of foam can result in illness, injury, or damage to the
environment. Follow foam manufacturer’s instructions and fire service training as directed by the
AHJ.
WARNING
Use of compressed air foam (CAF) with portable monitors can cause sudden surges in nozzle
reaction force resulting in risk of injury or death from hose whipping or an out of control monitor.
Be prepared for sudden changes in nozzle reaction caused by:
• Slug loading (Loss of foam concentrate sends slugs of air and water into the nozzle)
• Sudden release of built-up pressure in the hose when opening a nozzle