background image

0

25

50

75

100

125

150

175

200

225

250

275

300

0

25

50

75

100

125

150

175

200 FLOW (GPM)

PRESSURE

(PSI)

0

5

10

15

20

0

100

200

300

400

500

600

700 FLOW (LPM)

125 PSI SETTING

200 PSI SETTING

50 PSI SETTING

PRESSURE

(BAR)

4

To open the valve turn the hand wheel until the valve position says "OPEN". To close the
valve turn the hand wheel the opposite way until the valve position indicator says "CLOSED".

This valve is equipped with an Air Vent/Drain which will allow the air to escape from the valve when the hose is charged.
The Air Vent/Drain is opened by turning the knob counter clockwise and closed by turning it clockwise.

To drain the water out of the valve after use open the Air Vent/Drain. A 1/2” diameter plastic tube may be used to run the
drain behind the pump panel.

To set the relief valve pressure turn the adjusting screw on the relief valve housing until the surface of the screw is even
with the desired pressure. Do not cap or plug discharge opening.

5.0 USE
5.1 INTAKE ELBOW

5.2 VALVE POSITION INDICATOR

6.0 AIR VENT AND WATER DRAIN

7.0 PRESSURE RELIEF VALVE

7.1 RELIEF VALVE SETTING PRESSURE

7.2 RELIEF VALVE FLOW vs. PRESSURE CURVE

CL

OSED

OPEN

OPEN

3

4

1

2

1

4

1

4

1

2

3 4

CL

OSED

OPEN

OPEN

3

4

1

2

1

4

1

4

1

2

3 4

There is a pressure relief valve on the bottom side of the valve. It may be set to any pressure between 50 and 200 p.s.i.. Its
function is to protect the pump and the supply hose from excess pressure. The relief valve may be mounted with its
opening facing the front, back, right or left. A piece of hose or tubing may be mounted on the round spout to direct the
water coming out of the relief valve away from the pump panel. To change the orientation of the relief valve, remove the
four 7/16 bolts on the corners of the relief valve flange, orient the valve the way you want it, and replace the bolts. Use a
drop of thread locking compound on the threads of the bolt to prevent them from coming loose.

PRESSURE RELIEF VALVE PERFORMANCE

The intake elbow swivels 360 degrees to help prevent hose kinks, and make connection of suction lines easier. The intake
can be turned forward or backward to help make connections in tight places if the water supply is in front of or behind the
truck. To turn the elbow, pull the shot pin knob on top of the elbow. The elbow will lock into a detent every 45 degrees.
There is a hole on the side of the elbow that can be used to attach the lanyard or chain of a cap by use of

. The

elbow may be swivelled to any of eight positions by pulling the shot pin knob.

a key ring

Adjusting
Screw

Relief Valve
Discharge Opening

CAUTION

Loss of prime can interrupt water flow and cause injury or death. Always bleed
out air with air valve to prevent possible loss of prime.

LIA-200 March 17, 2004 Rev 5

©Copyright Task Force Tips, Inc. 2002-2004

If your application of this product requires drafting, you may need a suction gasket, please
call 1-800-348-2686 to receive a free suction gasket by mail.

Part Numbers: 4” STORZ - item # A4216, 5” STORZ - item # A4221

5.3

STORZ ‘SUCTION GASKET’ REQUEST

Содержание Ball Intake Valve

Страница 1: ...rsonnel MANUAL Ball Intake Valve WARNING Read instruction manual before use Operation of this device without understanding the manual and receiving proper training is a misuse of this equipment A person who has not read and understood all operating and safety instructions is not qualified to operate the Ball Intake Valve OPERATING RANGE Pressure Max 250 PSI Pressure Min Full Vac Hydrostatic Proof ...

Страница 2: ...duce water flow and cause injury or death to persons dependant on water flow When this valve is used on a hydrant or fire truck it is recommended that it be used with an elbow to minimize risk of hoseline kinks Maximum operating pressure 250 PSI 17 bar Do not exceed 250 PSI on either side of the valve Valve must be properly connected Mismatched or damaged connectors may cause leaking or uncoupling...

Страница 3: ...cts of corrosion can be minimized by good maintenance practice See section 9 0 for maintenance 3 1 CORROSION 4 2 CHANGING HAND WHEEL TO LEFT SIDE NUTS KEY SHAFT ASSEMBLY The handwheel is shipped from the factory on the right hand side of the valve The hand wheel can be switched to the left hand side for convenience or if it interferes with other equipment on the pump panel To move the hand wheel t...

Страница 4: ...xcess pressure The relief valve may be mounted with its opening facing the front back right or left A piece of hose or tubing may be mounted on the round spout to direct the water coming out of the relief valve away from the pump panel To change the orientation of the relief valve remove the four 7 16 bolts on the corners of the relief valve flange orient the valve the way you want it and replace ...

Страница 5: ... 15 8 16 17 18 59 20 22 23 25 24 58 27 30 32 29 33 69 68 36 37 38 61 62 63 42 43 45 46 47 50 56 57 21 14 44 49 48 51 9 54 53 52 14 15 60 28 62 64 65 66 67 31 5 8 0 DRAWINGS AND PARTS LISTS LIA 200 March 17 2004 Rev 5 Copyright Task Force Tips Inc 2002 2004 ...

Страница 6: ...UST WASHER 1 A1502 31 GEAR SPACER 1 A1511 32 3 8 16 X 5 16 SOCKET SET SCREW CUP POINT P 2 VT37 16SS312 33 1 4 BALL 302 STAINLESS STEEL 72 V2125 36 CUP SEAL 6 0 ID X 3 16 C S 1 A1545 37 HALF BALL STAINLESS STEEL 1 A1043S 38 ELBOW 4 4 STORZ ONLY 1 A1071 ELBOW 5 1 A1054 42 BARB X NPT FITTING 1 XX329 43 DETENT PIN 1 A1560 44 SPRING 1 X345 45 DETENT PIN HOUSING 1 A1570 46 DETENT PIN KNOB 1 A1575 47 SPI...

Страница 7: ...66NX MATE PSF5 25 X PSM7 0 NFS 1 A4745 PLASTIC STRIP 5 25 1 A1291 CUP SEAL 5 25 X 4 750 X 1 A1296 LABEL PORT COVER 1 A1298 BALL 7 16 STAINLESS 1 VB 437 GASKET 4 PRESSURE 4 STORZ ONLY 1 A4215 GASKET 4 PRESSURE 4 STORZ ONLY VACUUM 1 A4216 GASKET 5 PRESSURE 5 STORZ ONLY 1 A4220 GASKET 5 PRESSURE 5 STORZ ONLY VACUUM 1 A4221 51 GASKET 6 PRESSURE 6 STORZ ONLY VACUUM 1 A4226 GASKET 4 0 HOSE COUPLING 1 V3...

Страница 8: ...ipment is in part consideration for limiting TFT s liability Some states do not allow the exclusion or limitation of incidental or consequential damages so the above may not apply to you TFT shall have no obligation under this limited warranty if the equipment is or has been misused or neglected including failure to provide reasonable maintenance or if there have been accidents to the equipment or...

Отзывы: