![Task Force Tips 350 Series Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/task-force-tips/350-series/350-series_manual_820853006.webp)
©Copyright Task Force Tips LLC 2010-2021
6
LIU-360 October 14, 2021 Rev05
4.0 INSTALLATION
The eductor body is equipped with four 3/8-16 x ¾” deep threaded mounting holes. To mount the unit, attach to the desired location
using bolts with enough length to provide at lease ½” engagement with the unit. See below for mounting hole spacing.
Figure 4.0
5.0 OPERATING INSTRUCTIONS
Refer to training approved by the AHJ for appropriate foam type, concentration, and hose length.
1. Choose the appropriate foam concentration.
2. Lay the appropriate hose line.
3. Connect the appropriate nozzle.
4. Charge the hose and open the nozzle fully to establish the water flow.
5. Adjust the pump pressure so the eductor inlet is set at pressure specified on body label.
6. Rotate the percentage knob to the desired concentration.
7. Place the concentrate intake hose in the foam supply.
5.1 CLEANING INSTRUCTIONS
The eductor must be cleaned after each use to prevent residual foam concentrate from clogging the passageways.
1. After use, take the concentrate intake hose out of the foam supply.
2. Turn down the pump pressure to below 75 psi (5.2 bar).
3. Shut off the nozzle.
4. Restrain the hose and expect a rapid discharge of water, especially at the 6% setting.
5. Push the red flush button to run fresh water through the hose and metering head on each setting until there is no visible foam in
the flush water.
6. Retract the lock ring to remove the metering head.
7. Turn off water supply and remove the eductor from the hose so that any remainingfoam residue can be washed from the wand,
metering head and eductor.
5.2 CONCENTRATE INTAKE HOSE OPTIONS
The eductor is shipped with a 1.25” x 8’ clear, flexible hose with a 1.0” camlock connection. A 1.25” x 8’ black, high UV resistant hose
with a lower temperature rating is available for purchase. To order, call 800-348-2686 and ask for part # UE940.
A camlock adaptor is available for those who wish to use a hose with a 1.5” female camlock connection. To order, call 800-348-2686 and
ask for part #UE960-KIT.
CAUTION
Rapid backflush discharge from the wand could cause injury.
The backflush push button is pressure activated and must not be forced at pressures over 75 psi (5
bar). Do not backflush above 75 psi.
2 3/4"
2 3/4"