1. PRODUCT DESCRIPTION
IOM manual - SB series
11
1.8.
SB(…)
E technical data and function
No
Category
Set value
Actuation
time (s)
Recovery
time (s)
Recovery mode (s)
1
Phase loss
-
2
-
Manual recovery (Manually turn
off the power, then correct the
power and turn on the power)
2
Impeller jam
Double rated
current
0.1
-
Manual recovery (Manually turn
off the power, then solve the
problem and turn on the power)
3
Phase sequence
protection
With power line
input errors, the
pump won't
work
-
-
Manual recovery (Manually turn
off the power, then switch the
input wire and turn on the power)
4
Over-current
protection
≥
1.2 times
rated current
30
300
Automatic recovery
5
Low-voltage
protection
≤
323V
5
300
Automatic recovery
6
Overvoltage
protection
≥
460V
5
300
Automatic recovery
7
Temperature
protection
Winding
≥
125
± 5
o
C
0.1
-
Automatic recovery
(Winding
≤80 ±10
o
C)
8
Water level
control
As per below description
NOTICE:
SB(…)E
water level sensor probe is ON when touching the water, OFF when leaving water.
SB(…)E
automatic water-level control function
➢
Pump starts to work when the pump power is on, and water-level sensor is ON.
➢
During pump operation if water-level sensor is OFF, pump will continue to work for
60s and stop. But if water-level sensor is ON again during this 60s, the pump will
continue to operate without stop.
➢
When the pump is stopped due to low water-level, it will not start again within 60s
even if water-level sensor is ON, unless pump is powered off and on again.