1.5.2
Factors Affecting Maximum Output Current
The maximum output current obtainable from each tap of the loading unit output depends on
the following factors:
Lead impedance
Lead length
Load impedance
The lead impedance is often dominant in defining the maximum current that may be injected
into the load. The cross-sectional area of the leads and the lead layout have a large effect on
impedance.
Figure 1.5 shows the ideal lead layout for the maximum current obtainable from a CU-Ps and
PLU-6k with a 3m 5000AL output lead set.
Figure 1.5 Ideal lead routing for maximum output current