1 Introduction  

 

1.1 Overview  

TX7211  Addressable Sounder Circuit Module  unit is an addressable interface module, which will 
integrate conventional detectors or conventional manual call points to addressable system. When 
any of the connected devices alarms are active, the unit can send the alarm message to fire alarm 

controller, which generates alarm signal and displays its address. The unit can match with the 
conventional optical smoke detector, conventional rate of rise and fixed temperature detector and 
conventional manual call point etc. It has the function of checking short or open circuit of the 

output connection, by the End of Line Resistor (EOLR). The fault massage includes open circuit, short 
circuit or any removal of the detectors.  

The unit manufactured base on the requirement of EN 54 part 18, European Standard.  The unit is 
aesthetically pleasing with unobtrusive design that will complement modern building designs and its 

plug-in type assembles make installation and maintenance more convenient to the installer. The unit 
is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single 
manufacture Tand to avoid addressable  communication compatibility problem. 

1.2 Feature and Benefits  

 

EN54-18  Compliance 

 

Built-in MCU processor and digital addressing  

 

Intelligent self-diagnosis of open circuit 

 

Enhanced  capacity of interference  resistance by using multilevel wave filtering process 

 

LED status indicator  

 

Onsite Adjustable Parameter 

 

Loop and external power input  

 

Aesthetically  pleasing design 

 

Parallel connecting up to 10 fire alarm

(≤

500mA

 

 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Pending 

 

Compliance     

 

 

EN54-18:2005/AC2007 

 

Operating Voltage 

 

 

Loop: Loop 24V (16V~28V) 

Power:24VDC(20VDC~28VDC) 

 

Current Consumption   

 

Loop: Standby  1.5mA, Alarm: 10mA 

External PSU: Standby4mA, Alarm: 500mA 

 

Alarm Mode   

                          4 modes 

 

 

End of line Resistance   

 

5.1Kohms/ ¼ W  

 

Programming Method  

 

Electronically addressed  with 1~242, occupies  one or  

                    two addresses. 

 

Indicator Status   

 

 

Fault LED: red, flashes when polling, flashes twice  

when the circuit is short, broken or 24V power off. 

Output Activation LED: red, illuminates when start.  

 

Material  / Colour  

 

 

ABS  / White Glossy finishing  

 

Dimension / LWH 

 

 

108  mm x 86 mm x38  mm 

 

Weight  

 

 

 

154g  (with Base),  83g (without Base) 

 

Operating Temperature 

 

-10°C to +50°C 

 

Ingress Protection Rating 

 

IP30 

 

Humidity 

 

  

 

0 to 95%  Relative Humidity, Non condensing 

  

 

 

 

 

Содержание TX7211

Страница 1: ...TX7211 Addressable Sounder Circuit Module Installationand Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Страница 2: ...efore installing the module to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted muni...

Страница 3: ...Content 1 Introduction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Addressable Sounder Ci...

Страница 4: ...ore convenient to the installer The unit is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture Tand to avoid addressable communication compatibility...

Страница 5: ...al to consider the requirement of both sides of the Unit to avoid malfunction and typical fault scenario The main caution is to ensure that the voltage rating of the equipment and Unit are compatible...

Страница 6: ...device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Write Addressing 1 Connect the pro...