CALL TAMCO CUSTOMER SERVICE WITH ANY 
QUESTIONS CONCERNING TAMCO SMOKE DAMPERS.
DO NOT ADJUST LINKAGE MECHANISM. 
IF PROBLEM STILL EXISTS AFTER VERIFICATION AND 
CORRECT ACTION, CALL TAMCO CUSTOMER SERVICE.

Note that all technical information available on TAMCO’s website at 

www.tamcodampers.com supersedes and takes precedence over all 

information contained within the printed catalog.

READ ENTIRE INSTALLATION GUIDELINES MANUAL 

BEFORE INSTALLING DAMPERS. 
CHECK ALL DAMPER SIZES AND TAGS TO ENSURE 

THAT SMOKE DAMPERS ARE INSTALLED IN THEIR 

CORRESPONDING OPENINGS.

TAMCO UL/ULC APPROVED SMOKE DAMPER  |  

Installation Guidelines

For Series 1000 SM & 1000 SM-M 
Applies to all Options and Install Types

1

 

>

Any alteration to or deviation from TAMCO's UL Classified, Smoke 

Damper Installation Guidelines must be approved by the local AHJ 

(Authority Having Jurisdiction). 

 

>

Angle clips described in these installation guidelines are minimum 

16 ga 

(1.5 mm)

 zinc-plated or stainless steel or .125” 

(3 mm)

 extruded 

aluminum. Angle legs are to be a minimum 1” x 1” 

(25.4 mm x 

25.4 mm) 

and are to be a minimum ½” 

(12.7 mm)

 wide with 0.15" 

(4 mm)

 diameter screw holes. Continuous or full-length zinc-plated, 

extruded aluminum, or stainless steel angles are also acceptable.

 

>

Smoke dampers must be installed at, or adjacent to, but no more 

than 24" 

(609 mm)

 from the point where the duct or opening passes 

through the smoke barrier. This must be done in accordance with 

NFPA 90A. 

 

>

Duct air inlets, outlets or branches shall not be located between the 

smoke damper and the smoke barrier. 

 

>

Smoke dampers must not be installed in fiberglass-lined ducts in a 

manner that will damage the lining material, or interfere with damper 

blade operation.  

 

>

Provide a duct hanger at a smoke damper location, when the duct 

strength is inadequate for the damper and its operator. 

 

>

An access door must be provided, if the damper actuator is mounted 

inside the duct. 

GENERAL INSTALLATION NOTES:  

&

 

>

Smoke dampers must be installed square and free from racking, to 

ensure proper operation and performance. 

 

>

Dampers must be installed without stretching or compression, to 

allow them to maintain their original factory adjustment, thereby 

retaining their low leakage rating. 

 

>

TAMCO Smoke Dampers are approved to be installed either standing 

in the vertical plane, or lying in the horizontal plane. If smoke 

dampers are installed standing in the vertical plane, damper blades 

must be horizontal. 

 

>

Only lift dampers via sleeve or damper frame. Never lift damper by 

holding on to the damper blades or actuator.

 

>

All connections on the back or rear side of the smoke damper frame 

(opposite to sticker side), where the damper makes contact with the 

duct, sleeve, or substrate must be sealed using a ⅛" 

(3.2 mm) 

bead of 

silicone sealant. 

(See "Installation Procedures for Smoke Damper Install 

Types" for recommended silicone seal brands.)

 

 

>

When installing a multiple-section smoke damper assembly, all joints 

where damper frames meet must be sealed, using a bead of silicone 

sealant.

 

>

TAMCO Smoke Dampers must be kept in an environment that is free 

of dirt, dust, wall texture, paint over-spray, and other contaminants, 

prior to and after installation, to ensure proper damper operation and 

to guard against damage. 

MANUFACTURER'S RECOMMENDATIONS:  

&

 

>

When smoke dampers arrive at the job site, inspect all material for 

obvious and hidden damage. Report any damage or missing parts to 

TAMCO Customer Service.

 

>

Store dampers indoors to protect them from environmental 

conditions and to avoid damage.

 

>

All moving parts of the damper must be inspected and cycled at 

intervals not greater than every twelve (12) months or in accordance 

with the latest edition of NFPA 80, 90A, 92A, local codes and the 

actuator manufacturer.

 

>

Dry lubricants are recommended.

 

>

Smoke dampers do not typically require maintenance, if the 

environment they are installed in is kept dry and clean.

OPTIONS FOR SERIES 1000 SM & 1000 SM-M:  

&

 

>

MR  ̶  Moisture Resistance Option

 

>

SW  ̶  Salt Water Resistance Option

Содержание 1000 SM Series

Страница 1: ...e provided if the damper actuator is mounted inside the duct GENERAL INSTALLATION NOTES Smoke dampers must be installed square and free from racking to ensure proper operation and performance Dampers must be installed without stretching or compression to allow them to maintain their original factory adjustment thereby retaining their low leakage rating TAMCO Smoke Dampers are approved to be instal...

Страница 2: ...LL TYPE SHOWN JACKSHAFT MOUNTED top view ACTUATOR WIRING MUST BE CONNECTED IN ACCORDANCE WITH LOCAL CODES ORDINANCES AND NEC CSA REGULATIONS MULTIPLE ACTUATORS MOUNTED ON A SINGLE UNIT SHALL BE WIRED TO A SINGLE POINT TO ALLOW SIMULTANEOUS OPERATION OPTIONS FOR ACTUATOR MOUNTING 2 ACTUATOR WIRING GUIDE Wiring used to connect each actuator shall be as a minimum No 16 ga AWM The minimum temperature ...

Страница 3: ... dimensions are identical c Run a bead of silicone caulk around the perimeter of the damper flange face where it will come into contact with the substrate upon installation This is to prevent leakage between the damper and the wall Caulking may be applied at this step or following step e once the smoke damper has been fastened in place d Place the damper in the desired location on the wall so that...

Страница 4: ...ont label and back rear side of damper assemblies c Attach each joiner to the damper frame members using as a minimum four 8 sms screws or rivets as shown in Figures A B d Install the bridge bracket connecting the lower sections Place the bridge bracket so that it is centered over the joint where all four damper sections meet e Fasten the Bridge Bracket in place using 20 bolts making sure they are...

Отзывы: