Area of Refuge Command Unit 

Installation Instructions 

Model AOR-24/AOR-32 

Page 

6

 of 

13

 

 

Rev. 10/15/2015 

 

 

Copyright 2014 Talk-A-Phone Co.

 

• 7530 North Natchez Avenue • Niles, Illinois 60714 • Phone 773.539.1100 • [email protected] • www.talkaphone.com.  

All prices and specifications are subject to change without notice. 

Talk-A-Phone, Scream Alert, WEBS and WEBS Contact are registered trademarks of Talk-A-Phone Co. All rights reserved.

 

your other device picks up (or, if sharing with a standard telephone, be sure to 
allow enough rings for the person answering the phone to pick up).  

 

WARNING:

 The other device sharing the line should never be emergency 

equipment of any kind 
 

 
 

22.

 

Once the correct configuration of for the 

AOR-24/AOR-32 

has been determined 

and appropriately wired. Connect incoming 115-230 VAC 50-60Hz power wiring 
to the power supply board located in the bottom compartment of the unit. The 
LINE,  NEUTRAL,  and  GROUND  terminals  are  located  on  the  left  side  of  the 
board. 

 

WARNING:

 

The  order  in  which  115-230  VAC  50-60Hz  or  backup 

batteries  is  connected  does  not  matter.  However,  once  either  the 
batteries  are  connected  OR  the  115-230  VAC  50-60Hz  line  is 
energized, THE UNIT WILL BECOME “HOT” ENERGIZED. 

 

23.

 

Connect the backup batteries. 
The  batteries  and  their  corresponding  connections  to  the  wiring  harness  are 
labeled.    Starting  with  the  battery  that  is  labeled  with  the  numbers  3  and  4, 
place  the  battery  on  the  lowest  battery  shelf  and  connect  the  matching  leads 
from the wiring harness. 
 

24.

 

Next  locate  the  battery  that  is  labeled  with  the  numbers  5  and  6.    Place  this 
battery  on  the  second  shelf  from  the  bottom  and  connect  the  matching  leads 
from the wiring harness. 
 

25.

 

Now  locate  the  battery  that  is  labeled  with  the  numbers  7  and  8.    Place  this 
battery on the third shelf from the bottom and connect the matching leads from 
the wiring harness. 
 

26.

 

Place  the final  battery,  labeled  with  the  numbers  9  and  10,  on  the  top  battery 
shelf and connect the matching leads from the wiring harness. 
 

27.

 

The  batteries  connect  to  the  power  supply  board  by  inserting  the  connector 
onto  the  header  pins  located  on  the  bottom  right  of  the  power  supply  board 
which  the  115-230 VAC  50-60Hz    power  supply  was  connected. Although  the 
pins  are  polarized,  ensure  correct  polarity  when  connecting  the  backup 
batteries. Red-positive & Black-negative. 

 

Содержание AOR-8

Страница 1: ......

Страница 2: ...through the installation of this product and provide comprehensive operating instructions Please read this instruction manual completely and thoroughly before installing this product II Contents Befor...

Страница 3: ...s must provide 1 At least 24 Volts at 20 mA off hook no current is drawn on hook 2 Either a disconnect pulse voltage drop at end of call or 30 seconds or silence after hang up no re order or howler f...

Страница 4: ...fore mounting the enclosure NOTE Whenever possible it is best to keep the maximum clearance possible between analog phone lines and alternating current Running phone lines too close to hot VAC lines w...

Страница 5: ...2 banks of eight 8 The emergency analog phones on the system can connect to either the incoming POTS PSTN line or the local phone built into the AOR 16 unit 13 Attach the incoming Emergency Phone line...

Страница 6: ...ing must be done for each of the consolidators one 1 consolidator for the AOR 8 or two 2 consolidators for the AOR 16 NOTE See Technical Requirements p 2 for outside phone line requirements 17 Sharing...

Страница 7: ...to ensure compliance with all national regional and local regulations Programming Instructions To program the AOR 8 or AOR 16 Command unit each bank of eight 8 Talkaphone Area of Rescue emergency ana...

Страница 8: ...olidator to be programmed listen for 3 beeps 2 Enter Guard Access Code 31 3 Program the consolidator for Day Night Mode 63 4 Program the consolidator to call either Local first then Remote 35 Remote f...

Страница 9: ...try to change Guard Access Code or Master Access Code Default Code is 30 12345678 30 14725836 Resets Consolidator programming to factory defaults 32 up to 8 digits Programs and stores a new Master Acc...

Страница 10: ...a call is already being answered any other calls which come in will cause the appropriate LED to blink to indicate they are awaiting an open line As soon as the initial call has been completed any cal...

Страница 11: ...ground only at the consolidator end The resistance on the line is not to exceed 25 ohms The following chart shows distances and recommended wire gauges Distance from AOR 8 16 to Emergency Information...

Страница 12: ...p battery 6 My consolidator is not at my desk where the calls come in Is there a way to make the LED s remote so I can see who is calling Although the LED s cannot be made remote Emergency Information...

Страница 13: ...line into the Local port If so contact Talk A Phone technical support I hear noise on the line 1 You are not using twisted shielded wire Fluorescent lights elevator machinery and many other devices ca...

Страница 14: ...u through the installation of this product and provide comprehensive operating instructions Please read this instruction manual completely and thoroughly before installing this product II Contents Bef...

Страница 15: ...olts at 20 mA off hook no current is drawn on hook 2 Either a disconnect pulse voltage drop at end of call or 30 seconds or silence after hang up no re order or howler feature If connected to a POTS l...

Страница 16: ...lug phone and power connections back into phone in the correct order 6 Remove the three 3 Phillips screws from the left side of the unit which secure the hinged front cover shut 7 Carefully open the h...

Страница 17: ...ly on a wall in an appropriate location per the instructions packaged with the strobe siren assembly 14 Three 3 outgoing low voltage power lines from the strobe siren assembly must be wired to the Bla...

Страница 18: ...hone Area of Refuge Emergency Phone calls and the AOR 24 AOR 32 is in Day Night mode it will ring the Command Unit s built in local handset phone first ring it a second time if no one answers the firs...

Страница 19: ...matter However once either the batteries are connected OR the 115 230 VAC 50 60Hz line is energized THE UNIT WILL BECOME HOT ENERGIZED 23 Connect the backup batteries The batteries and their correspon...

Страница 20: ...dator will respond with three beeps Each consolidator will respond to all programming requests in one of two ways 1 Beep Command completed successfully 2 Beeps Error s detected If you hear two beeps e...

Страница 21: ...ce each Consolidator has been programmed each Talkaphone Area of Refuge Emergency Phone must be programmed individually A call can be routed to the desired phone port by entering the following code 4X...

Страница 22: ...tions are subject to change without notice Talk A Phone Scream Alert WEBS and WEBS Contact are registered trademarks of Talk A Phone Co All rights reserved 37 Local Mode 63 Day Night Mode 35 In Day Ni...

Страница 23: ...ll is already being answered any other calls which come in will cause the appropriate LED to blink to indicate they are awaiting an open line As soon as the initial call has been completed any calls t...

Страница 24: ...h ground only at the consolidator end The resistance on the line is not to exceed 25 ohms The following chart shows distances and recommended wire gauges Distance from EC 8 to Emergency Information Te...

Страница 25: ...battery 6 My consolidator is not at my desk where the calls come in Is there a way to make the LED s remote so I can see who is calling Although the LED s cannot be made remote Emergency Information p...

Страница 26: ...line into the Local port If so contact Talk A Phone technical support I hear noise on the line 1 You are not using twisted shielded wire Fluorescent lights elevator machinery and many other devices ca...

Страница 27: ...u through the installation of this product and provide comprehensive operating instructions Please read this instruction manual completely and thoroughly before installing this product II Contents Bef...

Страница 28: ...olts at 20 mA off hook no current is drawn on hook 2 Either a disconnect pulse voltage drop at end of call or 30 seconds or silence after hang up no re order or howler feature If connected to a POTS l...

Страница 29: ...lug phone and power connections back into phone in the correct order 6 Remove the three 3 Phillips screws from the left side of the unit which secure the hinged front cover shut 7 Carefully open the h...

Страница 30: ...ly on a wall in an appropriate location per the instructions packaged with the strobe siren assembly 14 Three 3 outgoing low voltage power lines from the strobe siren assembly must be wired to the Bla...

Страница 31: ...hone Area of Refuge Emergency Phone calls and the AOR 24 AOR 32 is in Day Night mode it will ring the Command Unit s built in local handset phone first ring it a second time if no one answers the firs...

Страница 32: ...matter However once either the batteries are connected OR the 115 230 VAC 50 60Hz line is energized THE UNIT WILL BECOME HOT ENERGIZED 23 Connect the backup batteries The batteries and their correspon...

Страница 33: ...dator will respond with three beeps Each consolidator will respond to all programming requests in one of two ways 1 Beep Command completed successfully 2 Beeps Error s detected If you hear two beeps e...

Страница 34: ...ce each Consolidator has been programmed each Talkaphone Area of Refuge Emergency Phone must be programmed individually A call can be routed to the desired phone port by entering the following code 4X...

Страница 35: ...tions are subject to change without notice Talk A Phone Scream Alert WEBS and WEBS Contact are registered trademarks of Talk A Phone Co All rights reserved 37 Local Mode 63 Day Night Mode 35 In Day Ni...

Страница 36: ...ll is already being answered any other calls which come in will cause the appropriate LED to blink to indicate they are awaiting an open line As soon as the initial call has been completed any calls t...

Страница 37: ...h ground only at the consolidator end The resistance on the line is not to exceed 25 ohms The following chart shows distances and recommended wire gauges Distance from EC 8 to Emergency Information Te...

Страница 38: ...battery 6 My consolidator is not at my desk where the calls come in Is there a way to make the LED s remote so I can see who is calling Although the LED s cannot be made remote Emergency Information p...

Страница 39: ...line into the Local port If so contact Talk A Phone technical support I hear noise on the line 1 You are not using twisted shielded wire Fluorescent lights elevator machinery and many other devices ca...

Отзывы: