
7
__________________________________________________________________________________________________________________
TAGLab
Battery Tester |
BAT 100
Battery Test
•
Connect the red (+) terminal connector cable to the positive (+) terminal of the battery.
•
Connect the black (-) terminal connector cable to the negative (-) terminal of the battery.
•
With both the battery clamps connected, the tester’s display meter will show the battery’s current state of
charge.
•
Engine and al electrical accessories must be off when testing battery.
•
If it is less than 12V, disconnect the battery and recharge before re-testing.
•
If recharging will not bring the reading above 12V, the battery is defective.
•
Press and hold the load switch “ON” for 10 seconds to apply the load to the battery.
•
Keep the load switch “ON” till the needle is steady. However do not exceed 10 seconds.
•
Read meter with load switch “ON”.
•
Release the battery load switch and remove the battery clamps from the battery.
•
Refer to the battery analysis table on back of tester or in user manual
Cold Temperature Effects
•
A battery will test lower when cold than when warm. For more accurate results, please reduce the battery’s
nominal rating by 200 CCA (one step on meter scale) for each 10°C drop below +5°C. If display meter CCA
rating is 800 and battery temperature is -5°C, read the same as 600 CCA (i.e. 1 step down).
Temperature Compensation
Battery Temperature
-5°C
-15°C
-25°C
Decrease Rating by
1 Step
2 Step
3 Step
1 Step = 200 CCA