Taco X Pump Block Скачать руководство пользователя страница 9

9 of 16

STEP TWO - INSTALLING THE SENSORS

Outdoor Sensor

Note:

 The temperature sensor is built into the plastic enclosure.

If the X – Pump Block is to be used in the outdoor reset mode, the Outdoor Sensor must be
installed. If the X – Pump Block is to be used in either the setpoint or a delta T mode, the
Outdoor sensor is not required and does not need to be installed. (See pages 5 to 7 for a
complete description of the available modes.)
• Remove the screw from the center of the sensor and pull the front cover off of the sensor.
• The outdoor sensor can either be mounted directly to an outside wall or onto a standard
electrical box. Wiring can enter the sensor either through the bottom or the back of the plastic
enclosure.
• The sensor should be mounted on a wall which best represents the heat load on the building
(i.e. a north facing wall for most buildings and a south facing wall for buildings with a large south
facing glass area). The sensor should not be installed near heat sources such as exhaust
vents or window openings.
• The sensor should be installed at an elevation above the ground that will prevent accidental
damage or tampering and above snow line.
• Ensure that the sensor is installed in a sheltered location out of direct sunlight and rain.
• Connect a two conductor wire to the terminal block in the Outdoor Sensor and run the wires
from the Outdoor Sensor back to the Radiant Mixing Control’s location.

Installing the System and Heat Source Sensors

Note:

 These sensors are designed to be mounted on a pipe or in a temperature well.

• These sensors can be strapped directly to the pipe using the cable tie provided with the
sensors. Insulation should be installed around the sensors to reduce the effect of air currents
on the temperature measurement. Care should be taken not to over-tighten the cable tie as
this can cause damage to the sensor.
• The System Supply Sensor is to be installed on the System Supply pipe. This sensor is
required at all times.
• If a Heat Source Sensor is used, install the heat source sensor on either the heat source
supply or the heat source return. E

nsure that the DIP switch on the back of the circuit

board of the VSMC is set to ON if the sensor is installed on the heat source supply and
set to OFF if the sensor is installed on the heat source return.

 If heat source control and

heat source protection are not required in the application, the heat source sensor does not
need to be installed.
• If a System Return Sensor is to be used, install the sensor on the system return pipe. This
sensor is only required if the VSMC is operating in the Delta T mode.

STEP THREE - WIRING THE VSMC

• Before wiring the control, ensure that power to all circuits is off.
• Ensure that all wires are stripped to a minimum of 

3

8

" (9 mm) in order to ensure proper connection to the low voltage terminals.

• Provide a separate circuit with a minimum 15 A capacity in order to insure proper operation.

Wiring Power to the VSMC

Using the supplied line cord, connect the white wire with the 

1

4

 inch female

spade connector to the 

1

4

 inch male spade connector labelled “N” on the

back of the VSMC circuit board. Connect the black wire with the 

1

4

 inch

female spade connector to the 

1

4

 inch male spade connector labelled “H” on

the back of the VSMC circuit board. Connect the green wire to the ground
screw located on the casting of the X – Pump Block.

Wiring to the X – Pump Block

Wiring to the Variable Speed Pump

Connect the variable speed pump’s three pin molex connector from the
X – Pump Block to the matching three pin molex connector labelled “Var”
on the back of the VSMC circuit board.

Wiring the X – Pump Block System Pump

Connect the system pump’s four pin molex connector from the X – Pump
Block to the matching four pin molex connector labelled “Sys” on the back
of the VSMC circuit board.

Com Sup Sys

Ret

Com Boil Out Com Heat

Dem

Var

T1A 250V

Sys

Man

N

H

Pmp

Use copper

conductors only

Power: 120 V +/- 10%

50/60 Hz, 750 VA

Var. Speed: 120 V

(ac) 1A

Pmp Relay: 120 V

(ac) 5 A, 1/6 hp

Injection Mixing 

967-01

Meets Class B Canadian ICES FCC Part 15

ON

OFF

1

2

3

4

5

C

US

158033

BOILER

R

Содержание X Pump Block

Страница 1: ...diant tubing glycol based snowmelt baseboard etc Extremely versatile the X Pump Block can be set up to operate in outdoor reset setpoint or delta T limiting mode Instruction Sheet X Pump Block XPB 102...

Страница 2: ...r Pressure Relief X Pump Block XPB Multiple Temperature System Circulators Exp Tank Output to System Supply Sensor Return Sensor Outdoor Sensor Pressure Relief X Pump Block XPB Multiple Temperature Sy...

Страница 3: ...pm 0 2 4 6 8 10 12 HEAD ft 0 2 4 6 8 10 12 14 16 18 20 SYSTEM SIDE HEAT SOURCE SIDE 1 2 1 2 Contents should include the following One X Pump Block preassembled unit consists of the following parts One...

Страница 4: ...OUNTING 1 Mounting position The X Pump Block must be mounted in the vertical position with the Variable Speed Mixing Control VSMC located at the top of the X Pump Block 2 Mount the X Pump Block using...

Страница 5: ...urce Operation section The VSMC also provides heat source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC...

Страница 6: ...at source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC can use either a powered or an unpowered demand...

Страница 7: ...T SOURCE CONTROL When the VSMC controls the heat source the VSMC opens and closes the heat source contact in order to control the temperature of the heat source supply water temperature When the VSMC...

Страница 8: ...stances is required When a heat source sensor is connected to the control the VSMC is capable of providing heat source protection When providing heat source protection the VSMC limits the output of th...

Страница 9: ...required at all times If a Heat Source Sensor is used install the heat source sensor on either the heat source supply or the heat source return Ensure that the DIP switch on the back of the circuit b...

Страница 10: ...a powered demand is being used connect the switched side of the 24 V ac demand circuit to the Heat Dem terminal of the terminal block Connect the second side of the 24 V ac demand circuit to the Com...

Страница 11: ...n the MIX RET elements are turned on This is the current temperature at the mixing return sensor The mixing return temperature is only displayed if the Outdoor Design temperature is turned OFF and a m...

Страница 12: ...his item is only available if the outdoor design set ting is not set to OFF Mixing Minimum Temperature The mixing minimum temperature is the lowest temperature that the control is allowed to use as a...

Страница 13: ...he rooms are cold increase the MIX DSGN setting by 5 F 3 C per day TESTING THE SENSORS Do not apply voltage to the sensor or to the sensor input of the control as this will result in damage to either...

Страница 14: ...plastic housing to pump castings 5 Remove the body bolts and swing motor assembly away from the body 6 Pull cartridge out of the motor housing 7 Install replacement cartridge making sure that the cov...

Страница 15: ...e Difference Between Mixing Supply and Return 10 to 70 F Off Design Outdoor Air Temperature 60 to 32 F Off Design Heating System Supply Water Temperature 70 to 185 F Maximum Mixing Target Supply 80 to...

Страница 16: ...service under this warranty it is the responsibility of the purchaser to promptly notify the local Taco stocking distributor or Taco in writing and promptly deliver the subject product or part deliver...

Отзывы: