background image

INSTALLING THE ON COMMAND STARTER BUTTON

The manual starter button is a unique feature to the On Command. The “on-command”
start to the circulating pump maximizes energy savings and controls operation only when
there is a request for hot water as compared to automatic timer controlled systems.

1. Drill  a 

5

8

"  hole  into  the  desired  location,  typically  the  side  or

front of a vanity cabinet.

2. Insert the gray wire from the controller through the back side of

the hole and connect it to the starter button.

3. Firmly insert the button into the drilled hole.

Note:  To  operate  the  On  Command  from  other  locations
throughout the house, additional starters can be installed and
spliced  into  the  gray  wire  provided.  Or  for  wireless  remote
operation, the Taco #554-1 transmitter/receiver kit can be eas-
ily installed. See “WIRELESS REMOTE KIT OPTION” below for
instructions.

4. If wireless remote kit is not installed, use electrical tape or wire nuts to isolate the 

three leads (black, white and green) on the black wire.

COMPLETING YOUR INSTALLATION

1. Turn on the water supply at the main. Check the system carefully for possible leaks.

If leaks occur, check all compression and threaded connections and tighten firmly.
Open hot and cold fixtures for one to two minutes to flush system completely.

2. Plug in the On Command to the 110V electrical outlet. The pump will start automatical-

ly the first time only and run for a short time until a rise in temperature is detected by
the thermal sensor. Pump will automatically shut off. 

Note: When the On Command

is  operating  a  green  LED  located  on  the  pump  motor  housing  will  illuminate.
The  Green  LED  will  only  be  “on”  when  the  pump  is  activated  and  circulating
water.

3. To  test  manual  starter  button,  wait  for  hot  water  temperature  to  cool  below  100°F

(approximately  20-30  minutes).  Press  starter  button  to  operate  the  pump.  The  On
Command should run for a short time and shut off automatically as in step 2 above.

4. Check hot water at the fixture for desired temperature. If hot water temperature is

not satisfactory, refer to Trouble Shooting checklist section.

WIRELESS REMOTE KIT OPTION – MODEL #554-1

Wiring the Receiver:

The optional remote receiver kit is the white rectangular box with
the three protruding wires (black, white and green). Batteries are
not required. Wire the receiver directly to the corresponding wires
on the controller by twisting each same colored wire together with
gray wirenuts provided. Receiver should be mounted toward front
of  cabinet.  (Range  of  transmitter  is  about  70'.)  If  transmitter  will
activate  pump  from  short  distance,  but  not  from  further  away,
receiver may need to be relocated for better reception. Strapping
receiver to front of drain trap facing outward will optimize reception.

Installing Batteries to the Transmitter:

Open  transmitter  by  inserting  a  small  flathead  screwdriver  into  slot  to  release  catch.
Load  battery  with  negative  side  of  battery  toward  spring.  Carefully  replace  cover.
Numbered jumper pins are inside the transmitter and receiver. The signal frequency can
be changed by removing the same numbered pins from both the receiver and transmit-
ter.  This  should  only  be  necessary  when  two  On  Command  pumps  are  in  the  same
home or neighboring homes.

For Additional Wireless Transmitter Buttons use Model #554-2.

Содержание ON COMMAND 006-CT-USK

Страница 1: ... parts available Patented Integral Flow Checks IFC are built into each On Command pump to prevent cold water from entering the hot water line State of the art electronics allow the On Command to accurately sense temperature and automatically shut off the pump to maximize comfort and energy savings On Command saves energy and water You can look forward to over 15 years of life expectancy with a Tac...

Страница 2: ...e prior to connecting the flex lines Note T s and flex lines supplied by Taco provide maximum flow and performance Alternative plumbing parts may restrict flow and delay hot water to fixtures WARNING In the event the retaining screws have been pulled out of the hous ing DO NOT replace them Use of any other screw may short out the stator windings creating a risk of electrical shock WARNING To avoid...

Страница 3: ...valve on hot water line For ease of installation leave the existing compression ring and nut from the angle stops on the hot and cold water lines 4 Remove the compression ring and nut from the adapter tees provided and slide on to opposite straight copper end Attach the existing nut and ring to the threaded end of the tee and tighten firmly 5 Connect the shut off valves to the new compression ring...

Страница 4: ... operating a green LED located on the pump motor housing will illuminate The Green LED will only be on when the pump is activated and circulating water 3 To test manual starter button wait for hot water temperature to cool below 100 F approximately 20 30 minutes Press starter button to operate the pump The On Command should run for a short time and shut off automatically as in step 2 above 4 Check...

Страница 5: ...he cold water tap A The water temperature sensor is loose or dislodged B The temperature sensitivity set ting now in place is too low so the pump is not shutting down soon enough Check the connection of the water temperature sensor to make sure it is firmly attached to the plug and casing Call 1 401 942 8000 for reset information 4 Water is not hot enough when pump shuts down A The temperature sen...

Страница 6: ...1 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY I...

Отзывы: