Taco LeakBreaker LBW Series Скачать руководство пользователя страница 6

Multi-Function LED and Troubleshooting (Red Status Lights):

This troubleshooting table is intended as a helpful guide and is not all inclusive. There could be other causes and solutions for a non-functioning product.

Only the most prominent error displays. Once addressed, the next error code will show. 

LED STATUS POWER

LED STATUS 

BATTERY ONLY

INDICATES

POSSIBLE CAUSE

POSSIBLE SOLUTION

AUDIBLE ALARM

Solid Green

-----------

Normal

-----------

1 Green Blink every

15 Seconds

(Approximately)

Normal

-----------

-----------

-----------

Solid Green with one red

blink

-----------

Low Batteries

Low Batteries

Replace batteries

Chirp every 60 seconds

Batteries installed incorrectly

Install batteries correctly

Chirp every 60 seconds

Not illuminated

-----------

Power off

Power supply not plugged in

Plug in power supply

-----------

------------

Not illuminated

Power off

Batteries installed incorrectly

or not at all

Install batteries correctly/

install batteries

-----------

In between cycles

Normal

Wait 15 seconds for indication

blinks

Solid Red with 2 red

blinks

Solid dim Red with

2 red blinks

Sensor error

Bad wire connection

Make sure wiring connections

are solid and tight and the

quick connect is all the way in 

Chirp every 60 seconds

Make sure sensors wired per

instructions

Chirp every 60 seconds

Solid Red with 3 red

blinks

Solid Dim Red with

3 red blinks

Valve error

Valve is not connected to the

control

Connect the valve to the con-

trol

Chirp every 60 seconds

Bad wire connection

Make sure wiring connections

are solid and tight and the

quick connect is all the way in 

Chirp every 60 seconds

Solid Red with 4 red

blinks

-----------

AC power error

Wrong power supply

Use power supply provided

Chirp every 60 seconds

Continuous Red blinks

Continuous Red

blinks

LeakBreaker has

Triggered

Sensor has detected water

Determine the water source

and correct. Dry the sensor

and reset the LeakBreaker.

Press the open button to

reset.

Constant alarm.

Press the mute button to

silence the alarm.

Solid Red

Solid Red

LeakBreaker has

triggered and the

water on the sensor

has dried up

Sensor has detected water

Determine the water source

and correct. Press the open to

reset.

Constant alarm.

Press the mute button to

silence the alarm.

LED STATUS POWER

LED STATUS

BATTERY ONLY

INDICATES

POSSIBLE CAUSE

POSSIBLE SOLUTION

AUDIBLE 

ALARM

Solid Green w/ 1 Orange Flash

every 3 seconds

1 Orange Flash

every 3 seconds

eLink Wi-Fi 

Setup Waiting

----------------

Refer to Wi-Fi set up section.

----------------

Solid Green w/ 1 Orange Blink

 

every 

10

 seconds

1 Orange Blink

every 30 seconds

Unconfigured

Refer to Wi-Fi set up section.

----------------

Solid Green w/ 2 Orange Blinks

 

every 

10

 seconds

2 Orange Blinks

every 

15

 seconds

Router Error

1. Can’t find router.

2. Incorrect Password

3. Incorrect SSID

Check Router.

Verify Networks Available.

Repeat Setup.

----------------

Solid Green w/ 3 Orange Blinks

 

every 

10

 seconds

3 Orange Blinks

every 

15

 seconds

Internet/Cloud

Error

1. Router not connected to Internet

2. No Gateway

3. Server Unavailable

Verify Internet Access is

Available.

Unplug router, plug back in.

----------------

eLink Multi-Function LED and Troubleshooting (Orange Status Lights): 

6

Содержание LeakBreaker LBW Series

Страница 1: ...rce try to take the actuator off of the valve body without using the release clip Both locking posts should be firmly attached to the actuator If the actuator slides up the stem repeat the assembly process Instruction Sheet LeakBreaker 102 506 SUPERSEDES July 27 2017 EFFECTIVE January 31 2018 Plant ID No 001 4237 Warning Never place any body parts or objects into the valve opening doing so may res...

Страница 2: ...e back of the controller plug the actuator wiring into the control panel port marked valve Two 2 sets of dry contacts are provided Each set includes normally open and normally closed connections They can be used to send a signal to any device requiring an open or closed signal such as a security system If using batteries install them into the battery holder Be sure to insert each battery in the co...

Страница 3: ...r device and connect to the eLink server through your wireless net work It will no longer be visible in your available Wi Fi networks 5 Setting Up eLink Notifications email text Registering your device will set up the email and or cell phone number that will be alerted when the LeakBreaker operates or for status updates a Using an internet connected device go to the following web page in your devi...

Страница 4: ...e valve should close the LED should flash red and the audible alarm should sound Once the valve closes press the mute button to silence the alarm a To reset the LeakBreaker completely dry off the sensor and then press the open button 1 2 3 4 Press Close Congratulations on the successful installation of your LeakBreaker 4 Installing Additional Sensors Up to ten 10 sensors may be daisy chained to th...

Страница 5: ...220 F 1 to 105 C Service Potable water Seat Leakage Drop Tight Close Off Electrical Input 120VAC 60 HZ Output 6VDC 600mA Power Supply or 4 AA Batteries Auxiliary Switch Rating Class 2 1Amp 24Volts MATERIALS OF CONSTRUCTION Control Panel Body High Performance Engineered Polymer Actuator Body High Performance Engineered Polymer Gears High Performance Internally Lubricated Engineered Polymer Valve Bo...

Страница 6: ...re wiring connections are solid and tight and the quick connect is all the way in Chirp every 60 seconds Solid Red with 4 red blinks AC power error Wrong power supply Use power supply provided Chirp every 60 seconds Continuous Red blinks Continuous Red blinks LeakBreaker has Triggered Sensor has detected water Determine the water source and correct Dry the sensor and reset the LeakBreaker Press th...

Страница 7: ...7 This page intentionally left blank ...

Страница 8: ...designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment...

Отзывы: