6 - Pump Installation

The 1900e series pump is protected with a double box during shipping.  It 

can be lifted from the box by the heat sink.

Warning:

 Pump may be heavy. Provide yourself help if 

needed. 

Warning:

 The majority of mechanical seal failures are due 

to  poor  media  (fluid)  quality  in  the  system.  To  maximize 

seal life, media quality must  be maintained in the system, 

and TDS (Total Dissoled Solids)/TSS (Total Suspended 

Solids) should not exceed 500ppm with standard carbon/

Silicon-Carbide seals. The use of inhibitor based glycols is acceptable, 

but additional inhibitors should not be added. Always follow the  glycol 

manufacturer's  specification  for  system  preparation  and  water  quality. 

Treatment with silicates should not be used. Failure to maintain media 

quality will void the standard Taco warranty.

AVERTISSEMENT: 

La plupart des défaillances des garnitures mé-

caniques sont dues à une mauvaise qualité de caloporteur. Pour pro-

longer la durée des joints, on doit maintenir la qualité du fluide dans le 

système et les solides dissouts totaux (SDT)/matières en suspension to-

tales (MES) ne doivent pas dépasser 500 ppm avec des joints standard 

en carbone/carbure de silicium. L'utilisation de glycols/inhibiteurs com-

binés est acceptable, mais on ne doit y ajouter aucun inhibiteur supplé-

mentaire. Suivez toujours les spécifications du fabricant du glycol pour la 

préparation du système et la qualité du fluide. On ne doit pas utiliser de 

traitement aux silicates. Ne pas maintenir la qualité du fluide annulera la 

garantie standard de Taco.

AVERTISSEMENT:

 La pompe est lourde. Veillez à de-

mander de l’aide si nécessaire.

It is recommended that the1900e series pumps be installed with at least 5 to 

10 pipe diameters of straight pipe on the inlet and outlet of the pump. Use all 
nuts and bolts to attach companion flanges to the pump flanges.
The 1915e uses a mechanical seal.  To ensure reliability of the seal, a min-

imum continuous safe flow rate of 9 gpm at full load (15% of BEP flow) is 
recommended. Ensure flange bolts are adequately torqued.
The 1900e series model pumps can be installed with the motor shaft in the 

horizontal position or the vertical position with the control module facing up 

(see Figure 1).  The cover can be rotated independent of the pump to adjust 

orientation of the User Interface – the cable glands should never be pointed 

upward to mitigate water ingress.  The desired conduit box orientation can 

be achieved by rotating the motor housing on the pump casing.

Caution:

 When reassembling, care should be taken to avoid damaging the 

o-ring and insuring a good seal.

Figure 1.

Preferred Installation 

Positions

Acceptable Installation 

Positions

UNAUTHORIZED 

Installation Positions

Attention!

 Installing pumps in UNAUTHORIZED positions may result in voiding the warranty.

Flange Bolt 

Size

FLANGE DIMENSIONS

Model (Flange 

Size)

Bolt Hole 

Diameter

Flange 

Thickness

Minimum Bolt 

Size

Qty.

1915e (1 

1

/

2

”)

0.672

0.688

5/8” x 2 

1

/

4

2

PERMITTED AMBIENT AND MEDIA TEMPERATURE

Ambient       

Temperature [°F]

Fluid Temperature

Min. [°F]

Max. [°F]

Up to 75

36

230

85

36

212

95

36

203

105

36

175

Ambient       

Temperature [°C]

Fluid Temperature

Min. [°C]

Max. [°C]

Up to 25

2

110

30

2

100

35

2

90

40

2

80

Attention!

 Operation outside recommended conditions may shorten pump 

lifetime and void the warranty.

7 - Motor Rotation Procedure

Caution:

  If  system  is  filled  and  pressurized,  shut  off  valves  before  and 

after the 1900e series pump. Allow to cool if system fluid is hot.

Notice! 

It is recommended to always change the orientation of the motor 

before installing pump in piping.

5 - Pumped Fluids

In hot and chilled hydronic systems, use water or water/glycol mixtures only. 

Water/glycol mixtures must be HVAC-system compatible and should have 

no  more  than  50%  concentration  of  glycol. The  fluid  shall  not  consist  of 

aggressive or explosive additives, mixtures of mineral oils or solid or fibrous 

particles. The pump should not be used for pumping flammable, explosive 

fluids, or in an explosive environment.

Desired pump orientation can be achieved by rotating the pump casing. 

The pump is mounted to the volute with four screws. By removing those 

the head can be turned. See detailed Motor Rotation Procedure 7 below.

Cast Iron Flange Kit

1600-031RP

Stainless Steel Flange Kit

198-3084RP

Содержание 1900e Series

Страница 1: ...SUPERSEDES March 5 2019 Effective July 29 2019 302 388 Plant ID No 001 5016 Instruction Sheet 1915e ECM Circulator ...

Страница 2: ... Connections Setup and Operation Control UI Panel Layout Switching On Off Pump Functions Mode Descriptions Specifications Application Electrical Ratings Standards Protection Connections Materials of Construction 3 3 3 3 3 4 4 4 5 5 5 5 6 6 6 6 6 7 7 7 7 7 Section 2 Controller Operation 18 19 20 21 21 1 22 22 1 Features Specifications ControllerLayout Connection Considerations Connection Examples F...

Страница 3: ...mpératures qui peuvent entraîner des blessures Warning The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the warranty AVERTISSEMENT L ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO annule la garantie Warning Use supply wires suitable for 90 C Warning Misconnection or overload...

Страница 4: ...re adequately torqued The 1900e series model pumps can be installed with the motor shaft in the horizontal position or the vertical position with the control module facing up see Figure 1 The cover can be rotated independent of the pump to adjust orientation of the User Interface the cable glands should never be pointed upward to mitigate water ingress The desired conduit box orientation can be ac...

Страница 5: ...sing and Impeller Motor assembly Using the new gasket provided with the seal kit reassemble the Impeller Motor assembly to the casing and secure with the four body bolts Use caution not to pinch the body gasket or leaks may result Tighten the four bolts evenly in a crisscross pattern to 70 in lb of torque v Reinstall the pump into the system using the new flange gaskets sup plied with the seal kit...

Страница 6: ...ase differential head as flow increases In automatic mode the pump sets the operating pressure depending on the system resistance The parameters are preset and cannot be changed 0 10Vdc In this mode all automatic curves are deactivated for full control via an external signal A dry contact from the external source is used to acti vate or deactivate the pump Pump speed is controlled via a 0 10V DC s...

Страница 7: ... experienced radio TV technician for help Fluid Temperatures PSI bar 112 F 50 C 7 3 0 5 176 F 80 C 11 6 0 8 230 F 110 C 20 3 1 4 14 2 For indoor use only employer uniquement a l interieur 15 Electrical Ratings Pump Ratings 1 phase 200 240V 47 63Hz Power Consumption HP 0 027 0 75 HP Power Consumption W 20 650W Rated Current 1 phase 230V 0 25 3 8A Relay Output 30 VDC Max Load up to 2A 24VAC Max Load...

Страница 8: ...n 2 pump operation Used to provide analog feedback to an external controller MOTOR CONTROLLER RIBBON CABLE Connects High Voltage Power Module to UI If the cable becomes disconnected reconnect to MOTOR CONTROL RIBBON CABLE connector 21 Connection Considerations All cables connected must be heat resistant to at least 185 F All cables connected must be installed in accordance with The National Electr...

Страница 9: ...9 21 1 Connection Examples DEFAULT FACTORY Configuration REMOTE START Analog Control 1 REMOTE START Analog Control 2 REMOTE START Analog Control 3 ...

Страница 10: ...10 2 PUMP OPERATION Lag Pump 2 PUMP OPERATION Lead Pump ...

Страница 11: ...2 second intervals Description Probable Cause s 1 blink Locked Rotor Impeller is unable to turn debris in system 2 blinks Over Current High Motor Load 3 blinks Over Temperature Motor might be faulty or viscous medium is present High Motor Load Water Temperature too hot Pump running dry 4 blinks Over Voltage Line voltage is too high 5 blinks Under Voltage Line voltage is too low for proper operatio...

Страница 12: ...itable for use with a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construction...

Отзывы: