9. Troubleshooting the error codes: 

Listed below are potential diagnostic error codes which will appear on the LED display in case

of a malfunction.

FAULTS

CONTROL 
PANEL

CAUSES

REMEDIES

The circulator is 
noisy

LED on 

Suction pressure is 
insufficient - cavitation 

Increase the system suction 
pressure within the 
permissible range.

LED on

Presence of foreign bodies 
in the impeller

Disassemble the motor and 
clean the impeller.

Loud noises of 
water circulation

Flashing white 
LED

Air in the system 

Vent the system. Repeat 
fill and purge steps.

LED on 

The flow is too high

Reduce the pump speed. 

Circulator is not 
running although 
the electrical 
power supply is
switched on

LED off 

Lack of power supply

Verify voltage value of the 
electric plant.
Verify the connection of the 
motor.

One fuse in the installation 
is blown

Verify the fuses of the plant.

The circulator is defective

Replace the pump.

Overheating

Let the pump cool down for 
some minutes. Then try to re-
start it. Verify that the water 
and ambient temperature are 
within the indicated 
temperature ranges.

LED red 

The rotor is blocked

Disassemble the motor and 
clean the impeller. See 
unblocking procedure below.

Insufficient supply voltage

Verify that the power supply 
matches the data on the name 
plate.

Building does not 
get warm.

LED on

The circulator 
performance is too low

Increase the suction head. 
Increase speed. 

Unblocking Procedure:

A red light in the LED indicates the circulator rotor is blocked or sticking. Turn the selector to the position MAX, disconnect and

connect power supply to start the automatic release process. The circulator makes 100 attempts to restart (process lasts approx-

imately 15 minutes). Every restart is signalled by a short flash of white LED light. If the blocking is not removed through the auto-

matic release process after 100 attempts to restart,  the circulator goes into standby and the LED remains solid red. Perform the

manual unblocking steps described below.

1. Disconnect power supply - the warning light switches off.

2. Close both isolating valves and allow cooling. If there are no shut-off devices, drain the system so that the fluid level is

beneath that of the circulator.

3. Loosen 4 motor bolts. Remove motor from casing. Carefully pull the rotor/impeller from the motor.

4. Remove impurities and deposits from the impeller and casing.

5. Reinsert the rotor/impeller into the motor.

6. Set the dial to the MAX position.

7. Connect power supply. Check for impeller rotation.

8. If the circulator still doesn’t run it will need to be replaced.

6

Содержание 00e Series

Страница 1: ...SEMENT Ne pas utiliser dans une piscine ou un spa La pompe n a pas été étudiée pour ces applications CAUTION The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the warranty Consult factory for fluid compatibility ATTENTION L ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO annul...

Страница 2: ... point in system 2 Open all isolation valves 3 Once system is filled close the fixture at the highest point in the system 4 Close isolation valve on pump discharge 5 Open drain valve on pump discharge until all remaining air has been purged 6 Close drain valve 7 Operate pump until all remaining air is purged from bearing chamber 2 ...

Страница 3: ...CH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED KEY VI V2 V3 SHUT OFF ISOLATION VALVE P TACO CIRCULATOR FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE FC FLOW CHECK VALVE Figure 3 Typical Installation for Zoned Hydronic Heating Systems Boiler Supply Option No 1 Boiler Return Option No 2 3 ...

Страница 4: ...hock be certain that it is connected only to a properly grounded ground ing type receptacle Follow all local electrical and plumbing codes AVERTISSEMENT Risque de choc électrique Pour réduire le risque de choc électrique veillez à ce qu elle soit raccordée uniquement à un réceptacle de type mise à la terre proprement mis à la terre Respectez tous les codes de plomberie et électriques locaux WARNIN...

Страница 5: ...eed setting for the system CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter 006e3 Operating Modes 3 Fixed Speed Settings Low Medium High Pre marked 003 006 equivalent settings Min Max infinitely variable fixed speed settings for fine tuning 6 Wiring the circulator Disconnect AC p...

Страница 6: ...w Insufficient supply voltage Verify that the power supply matches the data on the name plate Building does not get warm LED on The circulator performance is too low Increase the suction head Increase speed Unblocking Procedure A red light in the LED indicates the circulator rotor is blocked or sticking Turn the selector to the position MAX disconnect and connect power supply to start the automati...

Страница 7: ... 2 4 01 2 2 5 6 77 A7 4 4 8 4 4 8 4 6 4 0B C 8 4 5 DE F 7 7 8 4 7 7 8 G H I 6750 5 4 B A 4 J K1 4 8 4 5 7 L 8 65 4 4 7 7 B MIN LOW MED HIGH MAX Flow 0 1 2 3 6 5 4 7 8 9 10 11 12 13 14 Head 0 2 4 6 8 10 12 14 16 Q l s 0 8 0 6 0 4 0 2 0 0 H m 0 1 2 3 4 5 Q m 3 hr 0 0 0 5 1 0 1 5 2 0 2 5 3 0 H f ft t Q gpm 006e3 PERFORMANCE CURVES 3 fixed speed settings Low Medium High allows the installer to choose ...

Страница 8: ... contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRAN...

Отзывы: