![Taco 0034ePlus Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/taco/0034eplus/0034eplus_instruction-sheet_812808005.webp)
-5-
NEUTRAL
LINE
Removable Green
Terminal Plug
Terminal
Screws
GROUND
G
N
L
WARNING: SERVICING OF DOUBLE-INSULATED APPLIANCES. A double-insulated appliance is marked with one or more of the
following: The words “DOUBLE INSULATION” or “DOUBLE INSULATED” or the double insulation symbol (square within a square).
In a double-insulated appliance, two systems of insulation are provided instead of grounding. No grounding means is provided on
a double-insulated appliance, nor should a means for grounding be added. Servicing a double-insulated appliance requires extreme
care and knowledge of the system, and should be done by qualified service personnel. Replacement parts for a double-insulated
appliance must be identical to the parts they replace.
AVERTISSEMENT : ENTRETIEN DES APPAREILS À DOUBLE ISOLATION. Un appareil à double isolation est marqué avec un ou plusieurs
des éléments suivants : les mots « DOUBLE INSULATION » ou « DOUBLE INSULATED » ou le symbole de double isolation (carré dans
un carré). Dans un appareil à double isolation, deux systèmes d’isolation sont fournis plutôt que la mise à la terre ; aucun moyen
de mise à la terre n’est fourni ni ne doit être ajouté. L’entretien d’un appareil à double isolation exige de grandes précautions et
une connaissance approfondie du système, et doit être effectué par un technicien qualifié. Les pièces de rechange pour un
appareil à double isolation doivent être identiques aux pièces remplacées.
4. Wiring the circulator:
Disconnect AC power supply. Remove terminal box cover. Attach a wiring connector into knockout
hole. Use flexible conduit only. The green terminal plug may be removed to simplify wiring, then snapped back in place.
Connect Line/Hot power to the L terminal, Neutral to the N terminal and Ground to the G terminal. See wiring diagram
above. The 0034ePlus is a double insulated circulator; grounding wire is not necessary but recommended for safety.
Replace terminal box cover. Insert rubber cap plug provided to cover unused knockout hole.
4a. Wiring the circulator for 0-10V DC Operation:
(See Page 10)
5. Start the circulator:
When purging the system, it is recommended to run the circulator at full speed long
enough to remove all remaining air from the bearing chamber. This is especially important when installing
the circulator in the off-season. Set operating mode to Fixed Speed on 100% HIGH setting for maximum
fixed speed. A blue LED will illuminate when the 0034ePlus is powered on.
CAUTION: Never run the circulator dry or permanent damage may result.
ATTENTION: Ne laissez jamais le circulateur tourner à sec, des dommages permanents peuvent en résulter.
Full Speed Operation:
To run the pump at full speed during the fast fill, start-up and purge process, set operating mode to Fixed Speed on
100% HIGH setting. (See “Programming your 0034ePlus Circulator”). The LED will change to blue. To return to the normal
operating mode, reset operating mode to desired activeADAPT, Constant Pressure, Proportional Pressure, Fixed Speed
or 0-10V setting.
Wiring Diagram