Taco 00-VS Скачать руководство пользователя страница 5

5

WARNING: 

Wiring connections must be made in accordance with all applicable electrical codes.

CAUTION: 

To prevent electrical shock, disconnect electric power to system at main fuse or circuit breaker box until 
installation is complete. When a service switch is installed, more than one disconnect switch may be 
required to deenergize this device for servicing.

DIP switch 2 = Off DIP switch 2 = On

Minimum Variable Speed Output

DIP switch 5 = On

62%

18%

42%

  8%

DIP switch 5 = Off

Minimum Variable Speed Output

When the 00-VS is configured for 

T Target operation and 

reverse acting mode, a minimum variable speed output is incor-
porated during operation. In this case the variable speed output 
is adjusted between the selected minimum variable speed 
output percentage and full output. Select from the four different 
minimum variable speed output percentages in the table to the 
side. The 00-VS also provides full output for 30 seconds when 
the Heat Request appears, then resumes normal operation.
Note: Minimum variable speed output is not available when 
configured for 

T Target operation and Direct Acting Mode.

Exercising

During long periods of no operation, the 00-VS is designed to exercise for 10 seconds every 3 days of no operation in order to prevent 
precipitate build-up in the pump. The % OUT LED turns on during the exercising function.

Powering the control

Insert the line voltage wires through the knockout of the enclosure and connect the live wire to the H terminal and the neutral wire to 
the N terminal on the PC Board. Ensure that no power is present during this process.

Heat Request

The heat request signal may be provided by jumpering the heat request (HT Req) terminals or by applying 24 V (ac) to the HT Req ter-
minals. This signal may come from zone valve end switches, Taco ZVC/SR series zone controls, or thermostats. When a thermostat is 
connected directly to the heat request terminals, use dry contact style. (i.e. mechanical, digital hard wired or digital battery operated)

Sensors

Do not apply power to these terminals as this will damage the PC Board. The wiring terminals for the sensors may be removed for 
ease of installation. 
Do not run the wires parallel to telephone or power cables. If the sensor wires are located in an area with strong sources of electro-
magnetic interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using 
shielded cable, the shield wire should be connected to the Com terminal on the PC Board and not to earth ground.

System and Boiler Return Sensors

The sensors can be strapped directly to the pipe using a cable tie. Insulation should be placed around the sensor to reduce the effect 
of air currents on the sensor measurement. The sensors should be placed downstream of a pump or after an elbow or similar fitting. 
This is especially important if large diameter pipes are used because the thermal stratification within the pipe can result in erroneous 
sensor readings. Proper sensor location requires that the fluid is thoroughly mixed within the pipe before it reaches the sensor.
If the system sensor is used to measure duct (air) temperature, the sensor should be mounted in such a manner that it measures the 
average duct outlet temperature.

System Sensor (S1)

Connect the two wires from the system sensor (S1) directly into the Com and 

Wiring and Sensor Installation

S2 terminals on the PC Board.

System Sensor (S2)

Connect the two wires from the system sensor (S2) directly into the Com 
and S2 terminals on the PC Board.

Boiler Return Sensor (S3)

Connect the two wires from the boiler return sensor directly into the Com 
and S3 terminals on the PC Board.

Содержание 00-VS

Страница 1: ...ture the variable speed output is adjusted to ensure the boiler inlet temperature is above the boiler inlet minimum setpoint The 00 VS adjusts the variable speed output to the P1 pump to maintain a setpoint temperature at the supply sensor whenever a heat demand is present While the control is operating to maintain the setpoint temperature the variable speed output is also adjusted to ensure the b...

Страница 2: ...unwanted heat transfer primary secondary piping tech niques are used as shown in figure 1 This piping arrangement requires that the injection piping be at least one pipe diameter smaller than the piping of the boiler and system loops There must be no more than 4 pipe diameters between the tees in the boiler and system loops Note 1 in order to prevent ghost flow when the injection pump is off and t...

Страница 3: ...est signal is present at the Heat Request Ht Req terminals A heat request signal may be provided by external end switches from zone valves or ZVC SR series zone controls applying a dry contact closure or a powered 24 V ac signal across the Ht Req terminals If end switches or switching relays are not available a jumper must be installed to provide a heat request Once a heat request signal is presen...

Страница 4: ...al where the first and last temperatures from the selected temperature range corresponds to 1 and 10 respectively on the RANGE dial with the temperature increasing in 5ºF increments Note Only one of the sensors S1 or S2 can be connected in this mode of operation Boiler Protection When either system sensor S1 or system sensor S2 is installed for setpoint operation and the boiler return sensor S3 is...

Страница 5: ...his signal may come from zone valve end switches Taco ZVC SR series zone controls or thermostats When a thermostat is connected directly to the heat request terminals use dry contact style i e mechanical digital hard wired or digital battery operated Sensors Do not apply power to these terminals as this will damage the PC Board The wiring terminals for the sensors may be removed for ease of instal...

Страница 6: ...ce In addi tion to this the actual temperature must be measured with a good quality digital thermometer First measure the temperature using the thermometer and then measure the resistance of the sensor at the 00 VS The wires from the sensor must not be connected to the PC Board while this test is performed The wiring terminals are easily removed by pulling them from the PC Board Using the chart be...

Страница 7: ...s between the cartridge flange and motor 6 Make sure the replacement cartridge corresponds to the full circulator product number A complete parts list is available from your local plumbing supply wholesaler 7 Reassemble the circulator using the new gasket and bolts supplied 8 Follow the Installation procedure to start up the circulator Replacing Integral Flow Check IFC Assembly if applicable 1 Dis...

Страница 8: ...replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANT...

Отзывы: