6.

 

Reset Control Setup & Wiring (Optional) 

Boiler Reset Types: 

The ZVC406-5 includes two types of boiler reset control logic:  

Indoor Reset Control (Load Reset) uses the thermostat cycling information to determine the 

supply water temperature. Thermostat short cycling usually indicates supply water 

temperature is too high and long on cycles usually is too low of water temperature.  
Outdoor Reset Control uses an outdoor sensor to compare it against the a reset ratio 

(configured by installer) to determine the appropriate supply water temperature. 

General Operation:

 When any thermostat calls for heat, the appropriate zone valve is 

energized, and the yellow light goes on. When the zone valve is fully open, the red light goes 

on and energizes the circulator relay(s). The boiler end switch relay and modulating output will 

be controlled by the reset algorithm.  either based on indoor thermostat operation or on 

outdoor temperature. 

Control Setup: 

The Taco eLink mobile app is required to set type of reset control and 

parameters to operate. See section 7 for more information on the Taco eLink mobile app. 
 

Wiring of Reset Control:

 

Remove the inner cover as shown in section 9 of this manual on page 

to have access to wire.  

Sensor Connections: 

 

Boiler Sensor: 

A boiler supply sensor is required for either indoor or outdoor reset.  

Mount the supplied strap-on sensor to the supply piping of boiler and 

wire the sensor to the Boiler Sensor terminal block on zone control. 

Outdoor Sensor: 

An outdoor sensor is required when utilizing the outdoor reset 

function. Mount the Taco outdoor sensor P# 9300-2052RP on north 

side of building and wire to Outdoor Sensor terminal block on zone 

control. 

Boiler Connections: 

Modulating Output: 

Most Mod-Con boilers have and input for an external modulating 

signal (0-10 vdc or 4-20 ma) to control boiler. Connect the 

modulating output to appropriate input terminals on boiler; noting 

that the polarity is correct. Some Mod-Con boilers also require a T T 

call for heat to activate boiler. In this case, wire the Main Boiler End 

Switch to T T input on boiler. 

Dry Contact End Switch:  ON/OFF boilers are controlled by the Main Boiler End Switch on 

zone control. Wire the Main Boiler End Switch to T T input on boiler. 

 

 

 

Содержание ZVC406-5

Страница 1: ...e zones 2 through 6 during a priority call this is ideal for when using an indirect water heater The ZVC406 5 includes timing options for Post Purge Pump Exercise and Priority Protection The ZVC406 5...

Страница 2: ...ceeding the FCC radio frequency exposure limits human proximity to the antenna shall not be less than 20 cm during normal operation and must not be co located or operating in conjunction with any othe...

Страница 3: ...al connectors for field wiring Low and live voltage wiring per code Location Do not mount to a surface that exceeds 104 F 40 C The unit must be only located in dry interior locations Use only copper c...

Страница 4: ...output will energize when any zone calls for heat except the priority zone When the dip switch is set to ON the AUX 2 circulating pump output will energize when any zone calls for heat Post Purge Oper...

Страница 5: ...one control s 3 Connect 3 on Master zone control to 3 on all Expansion zone control s Power Input 120 vac H Connect to 120 vac Hot side of power supply to zone control N Connect to 120 vac Neutral sid...

Страница 6: ...ical Diagram Electrical Diagram Dip Switch Settings 1 OFF Master 2 ON Priority 3 OFF Primary Pump 4 OFF or ON Post Purge 5 OFF or ON Pump Exercise 6 OFF Time Delay 2 Wire ZV Conceptual Sketches Only r...

Страница 7: ...FF or ON Pump Exercise 6 OFF Time Delay 2 Wire ZV PA02 V SR506 5 with 5 Zone Circulators Indirect DHW Primary Secondary Mechanical Diagram Electrical Diagram Conceptual Sketches Only refer to individu...

Страница 8: ...perature Zones Indirect DHW Primary Secondary Mechanical Diagram Electrical Diagram DipSwitchSettings Expansion 1 ON Expansion 2 OFF Priority 3 OFF PrimaryPump 4 OFForON PostPurge 5 OFForON PumpExerci...

Страница 9: ...Electrical Diagram DipSwitchSettings 1 OFF Master 2 OFF Priority 3 OFF PrimaryPump 4 OFForON PostPurge 5 OFForON PumpExercise 6 OFF TimeDelay2 Wire Conceptual Sketches Only refer to individual manufa...

Страница 10: ...meters to operate See section 7 for more information on the Taco eLink mobile app Wiring of Reset Control Remove the inner cover as shown in section 9 of this manual on page X to have access to wire S...

Страница 11: ...or Android mobile devices Follow the app menu to configure advanced features that the Taco new zone controls have to offer including Different levels of access Zone naming Programmable output naming...

Страница 12: ...The eLink APP...

Страница 13: ...The eLink APP...

Страница 14: ...or a 1000 ohm watt resistor has proven to work with most Problem No heat in a zone or room of building Solution LED diagnostic lights will help find a component that is not working properly The green...

Страница 15: ...perature Rating 58 F to 230 F 50 C to110 C DIP Switch Timing Settings Post Purge 30 seconds adjustable with mobile app Pump Exercise 30 seconds per 2 weeks of space heating inactivity adjustable with...

Страница 16: ...se with a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement product...

Отзывы: