Taco Comfort Solutions FuelMizer SR501-OR-4 Скачать руководство пользователя страница 4

Taco,  Inc.  will  repair  or  replace  without  charge

(at  the  company’s  option)  any  product  or  part

which is proven defective under normal use with-

in  three  (3)  years  from  the  date  of  start-up  or

three (3) years and six (6) months from date of

shipment (whichever occurs first).
In order to obtain service under this warranty, it

is the responsibility of the purchaser to promptly

notify the local Taco stocking distributor or Taco

in writing and promptly deliver the subject prod-

uct or part, delivery prepaid, to the stocking dis-

tributor. For assistance on warranty returns, the

purchaser  may  either  contact  the  local  Taco

stocking distributor or Taco. If the subject prod-

uct or part contains no defect as covered in this

warranty,  the  purchaser  will  be  billed  for  parts

and  labor  charges  in  effect  at  time  of  factory

examination and repair.
Any Taco product or part not installed or operat-

ed in conformity with Taco instructions or which

has been subject to misuse, misapplication, the

addition  of  petroleum-based  fluids  or  certain

chemical  additives  to  the  systems,  or  other

abuse, will not be covered by this warranty.
If in doubt as to whether a particular substance

is suitable for use with a Taco product or part, or

for  any  application  restrictions,  consult  the

applicable  Taco  instruction  sheets  or  contact

Taco at [401-942-8000].
Taco reserves the right to provide replacement

products and parts which are substantially simi-

lar  in  design  and  functionally  equivalent  to  the

defective product or part. Taco reserves the right

to make changes in details of design, construc-

tion, or arrangement of materials of its products

without notification.
TACO OFFERS THIS WARRANTY IN LIEU OF

ALL  OTHER  EXPRESS  WARRANTIES.  ANY

WARRANTY  IMPLIED  BY  LAW  INCLUDING

WARRANTIES  OF  MERCHANTABILITY  OR

FITNESS  IS  IN  EFFECT  ONLY  FOR  THE

DURATION  OF  THE  EXPRESS  WARRANTY

SET  FORTH  IN  THE  FIRST  PARAGRAPH

ABOVE.
THE ABOVE  WARRANTIES ARE  IN  LIEU  OF

ALL  OTHER  WARRANTIES,  EXPRESS  OR

STATUTORY,  OR  ANY  OTHER  WARRANTY

OBLIGATION ON THE PART OF TACO.
TACO  WILL  NOT  BE  LIABLE  FOR ANY  SPE-

CIAL,  INCIDENTAL,  INDIRECT  OR  CONSE-

QUENTIAL  DAMAGES  RESULTING  FROM

THE USE OF ITS PRODUCTS OR ANY INCI-

DENTAL COSTS OF REMOVING OR REPLAC-

ING DEFECTIVE PRODUCTS.
This warranty gives the purchaser specific rights,

and the purchaser may have other rights which

vary  from  state  to  state.  Some  states  do  not

allow limitations on how long an implied warranty

lasts or on the exclusion of incidental or conse-

quential damages, so these limitations or exclu-

sions may not apply to you.

LIMITED WARRANTY STATEMENT

ond sensor can be placed alongside the one to be tested and the read-

ings compared. First measure the temperature using the thermometer

and then measure the resistance of the sensor at the control. The wires

from the sensor must not be connected to the control while the test is

performed. Using the chart below, estimate the temperature measured

by the sensor. The sensor and thermometer readings should be close.

If the test meter reads a very high resistance, there may be a broken

wire, a poor wiring connection or a defective sensor. If the resistance is

very low, the wiring may be shorted, there may be moisture in the sen-

sor or the sensor may be defective. To test for a defective sensor, mea-

sure the resistance directly at the sensor location.

The installer must ensure that this control and its wiring are isolated

and/or shielded from strong sources of electromagnetic noise. This

device complies with part 15 of the FCC Rules. Operation is subject to

the following two conditions: (1) This device may not cause harmful inter-

ference, and (2) this device must accept any interference received, includ-

ing interference that may cause undesired operation.

TECHNICAL DATA:
SR501-OR Boiler Reset Control Relay:

Control:

Microprocessor PI control. 

This is not a

safety (limit) control.

Enclosure:

TYPE 1

Dimensions:

4

1

4

" W x 5

1

4

" H x 2

3

4

" D

Approvals:

UL listed for US and Canada, Temperature

Indicating and Regulating Equipment.

Power Supply:

120/60/1 VAC, 12 amps maximum

Relays:                            Boiler Relay              1 amp  @ 24 VAC

                                        Circulator Relay        

1

3

HP (6 FLA, 36

LRA)

Thermostat:                     24 VAC Class 2 Output

Sensors:                          NTC thermistor, 10 k

Ω

@ 77°F

                                        (25°C ±0.2°C) ß=3892

Outdoor Design Temp.:   -30°F to 40°F (-35°C to 5°C)

Boiler Minimum:              70°F or 140°F (21°C or 60°C)

Differential:                      10°F or 20°F (6°C or 12°C)

WWSD:                            70°F (21°C), blinks TSTAT light when 

                                         >70°F

WARNING:

Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. 120 VAC wiring must have a min-

imum temperature rating of 75°C. Failure to follow this instruction can result in personal injury or death and/or property damage. 12-18 gauge wire rec-

ommended for 120 VAC connections, 14-22 gauge wire for thermostat connections, and 14-22 gauge wire for 24 VAC source connections.

TEMPERATURE RESISTANCE

°F

°C

Ω

-30

-34

234,196

-20

-29

165,180

-10

-23

118,018

0

-18

85,362

10

-12

62,465

20

-7

46,218

TEMPERATURE RESISTANCE

°F

°C

Ω

30

-1

34,558

40

4

26,099

50

10

19,900

60

16

15,311

70

21

11,883

80

27

9,299

TEMPERATURE RESISTANCE

°F

°C

Ω

90

32

7,334

100

38

5,828

110

43

4,665

120

49

3,760

130

54

3,050

140

60

2,490

TEMPERATURE RESISTANCE

°F

°C

Ω

150

66

2,045

160

71

1,689

170

77

1,403

180

82

1,172

190

88

983

200

93

829

Optional power stealing thermostat resistor part number: SRTR-001RP

(Value: 1000 Ohms, 1/2 watt or higher)

Replacement Switching Relay fuses part number: SR6A-001RP

(Manufacture: Littlefuse, Part Number: 229006)

A Taco Family Company

2016

Содержание FuelMizer SR501-OR-4

Страница 1: ...to the building The SR501 OR boiler reset control utilizes a reset ratio to set the relationship between outdoor tem perature and supply water temperature The reset ratio determines the amount the supply water temperature is raised for every 1 drop in out door air temperature and it is determined from the starting point and the system design conditions In order for the control to automatically det...

Страница 2: ...er Shut Down WWSD When the outdoor temperature rises above 70 F 21 C the control turns off the boiler and blinks the Thermostat LED light This function only applies for space heating and does not affect DHW operation Boiler Operation When the SR501 OR has a reset demand the system supply water temperature is controlled by turning the boiler on and off The control calculates the target supply water...

Страница 3: ... limit when there is a call for heat Boiler Minimum Supply Temperature Dip Switch 1 Most boilers require a minimum operating temperature to prevent cor rosion from flue gas condensation The minimum boiler dip switch should be set to ON 140 F supply water temperature so boiler can operate without causing the boiler flue gases to condense Consult the boiler manufacturer for recommended minimum boile...

Страница 4: ...d and the read ings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from the sensor must not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistanc...

Отзывы: