Taco Comfort Solutions FuelMizer SR501-OR-4 Скачать руководство пользователя страница 1

Instruction Sheet

FuelMizer

®

SR501-OR-4 Switching Relay with Outdoor Reset

A Taco Family Company

102-431

SUPERSEDES: March 1, 2013

EFFECTIVE: December 20, 2013

Plant ID# 9300-2871

MULTI-ZONE INSTALLATION WITH ZONE CONTROL

AND WITH INDIRECT DHW

ONE ZONE

SWITCHING RELAY

WITH OUTDOOR RESET

S

R

 5

0

1

O

R

-4

LED

INDICATORS

POWER

TSTAT

DHW
OVERRIDE

BOILER
RELAY

N H

INPUT

120 VAC

ZONE 1

120 VAC

N H

6

AMP

X

R

BOILER

TSTAT

W

C R

W

DHW

OUTDOOR

SENSOR

SUPPLY

SENSOR

X

DESIGN OUTDOOR

TEMPERATURE

FOR 180°F SUPPLY

TEMPERATURE

OFF

-30

-20

0

-10

10

20

40

30

ON

SW1

OFF

SYSTEM

CIRCULATOR

(OPTIONAL)

N

H

POWER

INPUT

(120 VAC)

BOILER

CONTROL

OUTDOOR

SENSOR

BOILER

SUPPLY

SENSOR

POT1

1 2 3 4

ZONE 1

1 2 3 4

ZONE 2

1 2 3 4

ZONE 3

EXISTING

ZONE VALVE CONTROL

P

O

W

E

R

 I

N

2

4

 V

A

C

 

N/O COM N/C

PUMP END

SWITCH

FU

S

E

5

 A

M

P

ZONE 3 PUMP

END SWITCH

THERMOSTATS

(24VAC)

T STAT 1

VALVE 1

T STAT 2

VALVE 2

T STAT 3

VALVE 3

POWER

LED

INDICATORS

ZONE 1  ZONE 2  ZONE 3

ISOLATED

X

X

R W

R W

R W

END SWITCH

THERMOSTATS

PRIORITY

24 VAC ZONE VALVES

PRIORITY

X

X

ZONE 3

PRIORITY

OFF

ON

C

C

C

2 WIRE ZONE VALVE

(NO END SWITCH)
MUST USE JUMPER

TACO 3 WIRE
ZONE VALVE 

1
2
3

JUMPER

3 & 4

TACO 3 WIRE
ZONE VALVE 

1
2
3

DHW

AQUASTAT

A

CONTROL STRATEGY:
Outdoor Reset:

In order to properly control a hot water heating system, the heat sup-

plied to the building must equal the heat lost by the building. 

•    The heat supplied to a building is proportional to the temperature of

the supply water and the surface area of the heating element. A

small surface area such as baseboard radiators requires a higher

water temperature than a larger surface area such as radiant floors. 

• The heat lost from a building is dependent on the outdoor tem-

perature, as well as other factors. As the outdoor temperature

drops, the building heat loss increases.

Reset Ratio:
Operation of a hot water heating system can generally be improved by

modulating the supply water temperature as the outdoor temperature

changes.  Using  this  approach,  the  heat  lost  from  the  building  is

matched by the heat input to the building. The SR501-OR boiler reset

control utilizes a reset ratio to set the relationship between outdoor tem-

perature and supply water temperature. The reset ratio determines the

amount the supply water temperature is raised for every 1° drop in out-

door air temperature, and it is determined from the starting point and

the system design conditions. In order for the control to automatically

determine  the  reset  ratio,  outdoor  design  conditions  must  be  estab-

lished.  This is usually the typical coldest outdoor temperature or it can

be set by using ASHARE standards for Design Outdoor Temperature

for specific geographic locations.

APPLICATION:

The SR501-OR is a microprocessor-based control designed to regulate

the supply water temperature of a single boiler, based on the outdoor

temperature. The SR501-OR is a boiler reset control and switching relay

in one unit. The SR501-OR is ideal for retrofit application, but may also

be used in new installations as well.
The SR501-OR includes functions such as automatic reset ratio calcu-

lation, warm weather shut down (WWSD), minimum boiler temperature

setting, and boiler differential setting. The control also has boiler sensor

and outdoor sensor error checking.

40

30

20

10

0

-10

-20

-30

70

-20

90

130

110

150

170

180

190

210

90

80

70

60

50

40

30

20

10

0

-10

OUTDOOR TEMPERATURE (°F)

BOILER SUPPLY TEMPERATURE vs. OUTDOOR TEMPERATURE (°F)

FOR OUTDOOR DESIGN TEMPERATURES

B

O

IL

E

R

 S

U

P

P

LY

 T

E

M

P

E

R

A

T

U

R

E

 (

°F

)

For  information  on  Taco’s

Switching  Relays  (SR)

including  catalog  sheet,

instruction sheets, Visio sten-

cils  and  our  highly  praised

Zone Controls Wiring Guide,

scan  the  QR  code  above  or

go to our website:
http://www.TacoComfort.com.

ONE ZONE INSTALLATION W/O INDIRECT DHW

ONE ZONE

SWITCHING RELAY

WITH OUTDOOR RESET

S

R

 5

0

1

O

R

-4

LED

INDICATORS

POWER

TSTAT

DHW
OVERRIDE

BOILER
RELAY

N H

INPUT

120 VAC

ZONE 1

120 VAC

N H

6

AMP

X

R

BOILER

TSTAT

W C R

DHW

OUTDOOR

SENSOR

SUPPLY

SENSOR

X

DESIGN OUTDOOR

TEMPERATURE

FOR 180°F SUPPLY

TEMPERATURE

OFF

-30

-20

0

-10

10

20

40

30

ON

SW1

OFF

SYSTEM

CIRCULATOR

(OPTIONAL)

N

H

POWER

INPUT

(120 VAC)

24 VAC

THERMOSTAT

BOILER

CONTROL

OUTDOOR

SENSOR

BOILER

SUPPLY

SENSOR

POT1

See

 NOTE

NOTE:

 Resistor

(1K

Ω

1

2

 W)

may be needed
between 

W

 and 

C

terminals.

W

Содержание FuelMizer SR501-OR-4

Страница 1: ...to the building The SR501 OR boiler reset control utilizes a reset ratio to set the relationship between outdoor tem perature and supply water temperature The reset ratio determines the amount the supply water temperature is raised for every 1 drop in out door air temperature and it is determined from the starting point and the system design conditions In order for the control to automatically det...

Страница 2: ...er Shut Down WWSD When the outdoor temperature rises above 70 F 21 C the control turns off the boiler and blinks the Thermostat LED light This function only applies for space heating and does not affect DHW operation Boiler Operation When the SR501 OR has a reset demand the system supply water temperature is controlled by turning the boiler on and off The control calculates the target supply water...

Страница 3: ... limit when there is a call for heat Boiler Minimum Supply Temperature Dip Switch 1 Most boilers require a minimum operating temperature to prevent cor rosion from flue gas condensation The minimum boiler dip switch should be set to ON 140 F supply water temperature so boiler can operate without causing the boiler flue gases to condense Consult the boiler manufacturer for recommended minimum boile...

Страница 4: ...d and the read ings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from the sensor must not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistanc...