14 - Specification
14.1 - Application
• Maximum Operating Pressure: 175 PSI (12 bar)
• Water Temperature Range: 36
°
– 230
°
F (2.2
°
– 110
°
C)
• Ambient Operation Temperature Range: 32
°
– 104
°
F (0
°
– 40
°
C)
• Relative Humidity: Max. 95%
• Central heating application is designed for closed loop heating and cool-
ing systems pumping water or a water/glycol mixture.
• DHW application is designed for open loop potable water systems.
Rated NSF/ANSI 61-G & 372 Commercial Hot (180 °F)
• NPSHr - Minimum static inlet pressure at pump suction to avoid cavita-
tion and mechanical seal damage:
Fluid Temperatures
PSI / bar
112°F (50°C)
7.3 / 0.5
176°F (80°C)
11.6 / 0.8
230°F (110°C)
20.3 / 1.4
14.2 - For indoor use only - employer uniquement a l’interieur.
15 - Electrical Ratings
Pump Ratings
1 phase, 200-240V, 47-63Hz
Power Consumption (HP)
0.027-0.75 HP
Power Consumption (W)
20-650W
Rated Current
(1 phase, 230V)
0.25-3.8A
Relay Output
30 VDC Max. Load up to 2A
24VAC Max. Load up to 3A
Analog Input
Input Voltage: 0-10V, 10mA
Output Voltage: 0-10V, 10mA
16 - Standards, Protection and Connection
• Insulation: Class H (180
°
C)
• Enclosure: Type 2
• Integrated Motor Protection (electronically protected)
• Continuous Duty
• UL778, 1004-1, 508C
• CAN/CSAC22.2#108, #100, #107.1, EMC (89/366EEC):EN61000
• Flange Connections: 2-bolt
17 - Materials of Construction
• Casing
• Impeller
• Shaft
• Bearing
Section 2. Controller Operation
18 - Features
This section describes the controller features for 1900e series of pumps.
The controller is used for various remote control applications, including:
• Remote on/off
• Analog 0 - 10 V voltage control
• Status relay feedback
There are several possible connection configurations. Not all functions can
be used simultaneously.
• on/off + 0 - 10 V + relay output
19 - Specifications
Tables to the right provide an overview of Controller specifications. For de-
tails, please refer to appropriate sections of this manual.
General Data
Ambient Humidity
< 95% relative,
non-condensing
Also see appropriate pump
data for other ambient spec-
ifications.
Analog Signals
Input Voltage Range
0 to 10V dc
When used as input. 10 mA
max. drive required.
Output Voltage Range
0 to 10V dc
When used as output. 10
mA max. load allowed.
Input Resistance
~3 kΩ
Relay Specifications
Connection Type
Terminal Block
Rating
24V AC, 3A
30V DC, 2A
HVAC application
: Ductile Iron, Cataphoresis Coated
DHW application
: Stainless Steel
PPS
Stainless Steel
Sealed for Life Ball Bearings, 6002 Series