6.   Programming your 0034e circulator:

 Modify the performance of the circulator as needed by rotating the dial    

  using a flat screwdriver. When the circulator is powered on, the LED will illuminate and change color based on the  

  operating mode selected. The LED will flash each time a setting is changed. See diagram below to set pump for    

  desired operating mode. The selection of the right operating curve depends on the characteristics of the system    

  and  the actual flow / head requirements. See Pump Curves on pages 7, 8 & 10 to determine the best operating    

  mode for the system. See cross-reference replacement chart on back page. 

The 0034e has 5 Operating Settings:
•   activeADAPT — Automatic, self-adjusting, proportional pressure, variable speed.  

 

  (Violet LED)
•   LOW — 13 feet of head constant pressure, variable speed.    

 

 

 

 

  (Orange LED)
•   MEDIUM — 26 feet of head constant pressure, variable speed.  

 

 

 

 

  (Orange LED)
•   HIGH — 34 feet of head max, full fixed speed.  

 

 

 

 

 

 

  (Blue LED)
•   0-10V DC — Analog external input or PWM pulse width modulation  

 

 

 

  input from building control system, variable speed.  

 

 

 

 

 

  (Yellow LED)

Violet LED

Orange LED

Yellow LED

MEDIUM 

– 26 ft. Head

Constant Pressure 

Variable Speed

Orange LED

HIGH 

– 34 ft. Head

Fixed Speed 

White LED

SureStart

®

Automatic unblocking 

& air purging

0-10V Analog Input

Variable Speed

LOW

 

– 13 ft. Head

Constant Pressure

Variable Speed

activeADAPT™

Self-adjusting Proportional

Pressure Variable Speed

Blue LED

Figure 7 - Dial Settings & Operating Modes 

Содержание 0034e

Страница 1: ...re on flanges for easier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Double insulated Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking and air purging mode Rotatable control cover to allow any pump body orientation INSTALLATION WARNING Do not use in swimming pool or spa areas Pump has not b...

Страница 2: ...NE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC FC FC FC FC FC FC FC ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC Figure 2 PREFERRED PIPING FOR CIRCULATORS ON BOILER SUPPLY PREFERRED PIPING FOR CIRCULATORS ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR CIRCULATORS ON BOILER SUPPLY ...

Страница 3: ...RIMARY SECONDARY PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN igure 3 MOD CON BOILER ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 Figure 3 PREFERRED PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR ZONE VALVES ON BOILER SUPPLY ...

Страница 4: ...he system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To reduce the risk of electric shock be certain that it is connected only to a properly grounded grounding type receptacle Follow all local electrical and plumbing codes AVERTISSEMENT Risque de choc électriqu...

Страница 5: ...ualifié Les pièces de rechange pour un appareil à double isolation doivent être identiques aux pièces remplacées 4 Wiringthecirculator Disconnect AC power supply Remove terminal box cover Attach a wiring connector into knockout hole Use flexible conduit only The green terminal plug may be removed to simplify wiring then snapped back in place Connect Line Hot power to the L terminal Neutral to the ...

Страница 6: ... on back page The 0034e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 13 feet of head constant pressure variable speed Orange LED MEDIUM 26 feet of head constant pressure variable speed Orange LED HIGH 34 feet of head max full fixed speed Blue LED 0 10V DC Analog external input or PWM pulse width modulation input from building con...

Страница 7: ...te Q GPM 0 5 10 15 20 25 30 35 Head ft 0034e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT activeADAPT Mode activeADAPT is an operating mode designed for constant circulation systems On this setting the circulator will sense changes in system flow and head conditions and adjust the operating curve automatically See activeADAPT operating range in the chart to the right Constan...

Страница 8: ...High Efficiency Circulator Maximum Curve Fixed Speed Blue LED HIGH 5 0 10 15 20 25 30 35 40 45 50 55 Flow Rate Q GPM 0 5 10 15 20 25 30 35 Head ft HIGH Head 34 ft 0034e High Efficiency Circulator Maximum Curve Fixed Speed Blue LED Fixed Speed Mode At High setting the circulator always operates at full speed ...

Страница 9: ...plug Figure 8 Ref 4 from the electronic board Figure 8 Ref 5 4 Insert the cable Figure 8 Ref 6 in the cable strain relief gland M12x1 5 Figure 8 Ref 7 provided in carton and screw it to the cover 5 Strip Minimum 25 the ends of the wires insert them into the connector as shown Figure 8 Ref 4 and fix them with screws Figure 8 Ref 8 6 Re connect the terminal plug to the electronic board replace the c...

Страница 10: ...s state hysteresis See diagram below IMPORTANT If the input remains disconnected the circulator goes into Standby Mode Head ft PWM Pulse Width Modulation 2 4 6 8 0 0 6 8 2 4 10 16 12 14 20 22 18 26 28 30 32 24 34 36 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 54 52 Flow Rate Q GPM 0034e High Efficiency Circulator 0 10V DC Performance Curves 100 75 50 25 0 0 10V 4V 2V 8V 6V 10V P...

Страница 11: ...rculator still doesn t run it will need to be replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED on Presence of foreign bodies in the impeller Disassemble the motor and clean the impeller Loud noises of water circulation Flashing white LED Air in the s...

Страница 12: ...14 PL 50 PL 45 PL 36 PL 30 E90 1AAB Series 60 601 Series HV Series PR Series HV Series 100 NRF 45 NRF 36 ECOCirc XL 36 45 E 11 E 10 E 8 E 7 S 25 H 63 H 52 H 51 Astro 290 Astro 280 Astro 210 1050 1B 1050 1 1 4B Compass ECM TP E 32 40 UP 50 75 UPS 43 100 UPS 50 44 UP 43 75 UP S 43 44 UP 26 116 UP S 26 99 UP 26 96 UP 26 64 UPS 32 40 UPS 32 80 Magna 32 100 Magna 32 60 Alpha2 26 99 Stratos 1 25 x 3 35 ...

Страница 13: ...duct or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials ...

Отзывы: