DESCRIPTION:

The 0034e™ is a high-performance, variable speed, high-efficiency, wet-rotor circulator 

with an ECM permanent magnet motor. With 5 easy settings, its variable speed 

performance curves are equivalent to the Taco 009, 0010, 0011, 0012, 0012 3-Speed, 

0013, 0013 3-Speed & 0014. Ideal for large residential and light commercial hydronic 

heating, chilled water cooling and domestic hot water systems. The 0034e reduces 

power consumption by up to 85% compared to equivalent AC permanent split 

capacitor circulators. With a maximum of 34 feet of head and 50 gpm. It is available

in either Cast Iron or NSF certified Stainless Steel.

APPLICATION:

• Maximum operating pressure: 150 psi (10.3 bar)

• Minimum NPSHR: 18 psi at 203˚F (95˚C)

• Maximum fluid temperature: 230°F (110˚C)

• Minimum fluid temperature: 14°F (-10˚C)

• Electrical specifications:

Voltage: 115/208/230V, 50/60 Hz, single phase

Maximum operating power: 170W

Maximum amp rating: 1.48 (115V) / .70 (230V)

• Equipped with a Cast Iron or Stainless Steel casing

• SS Model suitable for open loop potable water systems

• Taco circulators are for indoor use only – employer uniquement a l’interieur

• Acceptable for use with water or maximum of 50% water/glycol solution

FEATURES:

• 5 easy dial settings to match system requirements - activeADAPT, LOW, MEDIUM, HIGH or 0-10V DC input

• Replaces all single speed and 3-speed circulators in its class

• ECM performance equivalent to Taco’s 009, 0010, 0011, 0012, 0013 & 0014 circulators

• Multi-color LED: power on, mode setting and error code diagnostics

• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation

• Nut-capture feature on flanges for easier fit up

• Dual electrical knockouts and removable quick-connect terminal strip for easy wiring

• Double insulated

• Whisper quiet operation

BIO Barrier®

 protects the pump from system contaminants

SureStart®

 automatic unblocking and air purging mode

• Rotatable control cover to allow any pump body orientation

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.

AVERTISSEMENT : Ne pas utiliser dans une piscine ou un spa. La pompe n’a pas été étudiée pour ces applications.

CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment

voids the warranty. Consult factory for fluid compatibility.

ATTENTION : L’ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un

équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.

CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent

pump cavitation and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. 

A larger size expansion tank may be required.
ATTENTION : Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée de 20 psi 

au minimum afin d’éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression 

du réservoir d’expansion de façon qu’elle soit égale à la pression de remplissage. Un réservoir d’expansion d’une taille supérieure 

peut être nécessaire.

Instruction Sheet

102-543

SUPERSEDES: 

February 2, 2021

EFFECTIVE: 

August 16

, 2021

Plant ID No. 001-5019

-1-

Figure 1

Standard flange model: 0034e-F2

Certified to

NSF/ANSI 61 & 372

Содержание 0034e

Страница 1: ...re on flanges for easier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Double insulated Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking and air purging mode Rotatable control cover to allow any pump body orientation INSTALLATION WARNING Do not use in swimming pool or spa areas Pump has not b...

Страница 2: ...NE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC FC FC FC FC FC FC FC ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC Figure 2 PREFERRED PIPING FOR CIRCULATORS ON BOILER SUPPLY PREFERRED PIPING FOR CIRCULATORS ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR CIRCULATORS ON BOILER SUPPLY ...

Страница 3: ...RIMARY SECONDARY PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN igure 3 MOD CON BOILER ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 Figure 3 PREFERRED PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR ZONE VALVES ON BOILER SUPPLY ...

Страница 4: ...he system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To reduce the risk of electric shock be certain that it is connected only to a properly grounded grounding type receptacle Follow all local electrical and plumbing codes AVERTISSEMENT Risque de choc électriqu...

Страница 5: ...ualifié Les pièces de rechange pour un appareil à double isolation doivent être identiques aux pièces remplacées 4 Wiringthecirculator Disconnect AC power supply Remove terminal box cover Attach a wiring connector into knockout hole Use flexible conduit only The green terminal plug may be removed to simplify wiring then snapped back in place Connect Line Hot power to the L terminal Neutral to the ...

Страница 6: ... on back page The 0034e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 13 feet of head constant pressure variable speed Orange LED MEDIUM 26 feet of head constant pressure variable speed Orange LED HIGH 34 feet of head max full fixed speed Blue LED 0 10V DC Analog external input or PWM pulse width modulation input from building con...

Страница 7: ...te Q GPM 0 5 10 15 20 25 30 35 Head ft 0034e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT activeADAPT Mode activeADAPT is an operating mode designed for constant circulation systems On this setting the circulator will sense changes in system flow and head conditions and adjust the operating curve automatically See activeADAPT operating range in the chart to the right Constan...

Страница 8: ...High Efficiency Circulator Maximum Curve Fixed Speed Blue LED HIGH 5 0 10 15 20 25 30 35 40 45 50 55 Flow Rate Q GPM 0 5 10 15 20 25 30 35 Head ft HIGH Head 34 ft 0034e High Efficiency Circulator Maximum Curve Fixed Speed Blue LED Fixed Speed Mode At High setting the circulator always operates at full speed ...

Страница 9: ...plug Figure 8 Ref 4 from the electronic board Figure 8 Ref 5 4 Insert the cable Figure 8 Ref 6 in the cable strain relief gland M12x1 5 Figure 8 Ref 7 provided in carton and screw it to the cover 5 Strip Minimum 25 the ends of the wires insert them into the connector as shown Figure 8 Ref 4 and fix them with screws Figure 8 Ref 8 6 Re connect the terminal plug to the electronic board replace the c...

Страница 10: ...s state hysteresis See diagram below IMPORTANT If the input remains disconnected the circulator goes into Standby Mode Head ft PWM Pulse Width Modulation 2 4 6 8 0 0 6 8 2 4 10 16 12 14 20 22 18 26 28 30 32 24 34 36 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 54 52 Flow Rate Q GPM 0034e High Efficiency Circulator 0 10V DC Performance Curves 100 75 50 25 0 0 10V 4V 2V 8V 6V 10V P...

Страница 11: ...rculator still doesn t run it will need to be replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED on Presence of foreign bodies in the impeller Disassemble the motor and clean the impeller Loud noises of water circulation Flashing white LED Air in the s...

Страница 12: ...14 PL 50 PL 45 PL 36 PL 30 E90 1AAB Series 60 601 Series HV Series PR Series HV Series 100 NRF 45 NRF 36 ECOCirc XL 36 45 E 11 E 10 E 8 E 7 S 25 H 63 H 52 H 51 Astro 290 Astro 280 Astro 210 1050 1B 1050 1 1 4B Compass ECM TP E 32 40 UP 50 75 UPS 43 100 UPS 50 44 UP 43 75 UP S 43 44 UP 26 116 UP S 26 99 UP 26 96 UP 26 64 UPS 32 40 UPS 32 80 Magna 32 100 Magna 32 60 Alpha2 26 99 Stratos 1 25 x 3 35 ...

Страница 13: ...duct or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials ...

Отзывы: