0-003-2063-2 (EN)
4 (8)
Figure 5
CONNECTIONS
Block Function
Description
G
24 V AC
Supply
G0
24 V AC rtrn
voltage
X1
Input
Control sign-
MX
Input, neutral
als (VH, VC
VH
Increase
short-circuited
VC
Decrease
to G0)
G1
16 V DC
Supply for RC
Y
0–100 %
Feedback
signal
}
}
N.B.!
When installed with three
conductors, where the control signal
reference is connected to G0, the motor
current of the actuator will cause
varying voltage loss in the cable and
thus in the reference level. Forta, which
has a highly sensitive control signal
input, will detect the varying signal and
follow it, which makes it difficult for the
actuator to find a stable position.
This variation may be accepted in
simplified installations on the following
conditions: the cables between the
controller and actuator are shorter than
100 m (328 ft.), the cross-sectional area
is larger than 1.5 mm2 (AWG 16) and
the cables are only connected to
one
actuator. Please refer to the figures
labelled “Simplified installation” for
wiring instructions.
Cable lengths
The cables to G, G0 and G1 should be
max. 100 m (328 ft.) and have a cross-
sectional area of min. 1.5 mm²
(AWG 16).
Other cables should be max. 200 m
(656 ft.) and have a cross-sectional
area of min. 0.5 mm² (AWG 20).
Y X1 MX VH VC G1 G0 G
1
2
3
4
5
6
7
8
9
Terminal
block
NORM
VH
VC
VH
VC
INV
X1
10V
0(2)V
INV
10V
X1
NORM
0(2)V
STS
G
MX VH VC G1 G0
X1
Y
0 V
24 V~
K1 K2 KC1
CLOSING RELAY
OPENING RELAY
S2
Ej ändläge Non ending position
Ändläge Ending position
KC2
K3 K4
Ej ändläge Non ending position
Ändläge Ending position