background image

3 (6)

 0-003-2060-1 (EN)

The actuator may be mounted
horizontally, vertically and in any
position in between, but not upside
down, see figure 3.

N.B.! Do not use the actuator for the
DN15 valves V298, V282, V294, V384,
V386 and V394.

To mount the actuator on a valve, slide
the actuator onto the valve neck, thus
making the square nut on the valve
spindle fit into the groove on the cross
bar. Then slide the brace into the
groove on the valve neck and secure
the nuts.

MOUNTING

CONNECTIONS

N.B.!  When installed with 3
conductors, where the control signal
reference is connected to G0, the motor
current of the actuator will cause
varying voltage loss in the cable and
thus in the reference level.  Forta, which
has a highly sensitive control signal
input, will detect the varying signal and
follow it, which makes it difficult for the
actuator to find a stable position.

This variation may be accepted in
simplified installations on the following
conditions: the cables between the
controller and actuator

are shorter than 100 m (328 ft.), the
cross-sectional area is larger than
1,5 mm2 (AWG 16) and the cables are
only connected to one actuator.  Please
refer to the figures labelled “Simplified
installation” for wiring instructions.

Cable lengths
The cables to G, G0 and G1 should be
max. 100 m (328 ft.) and have a cross-
sectional area of min. 1,5 mm² (AWG
16).

Other cables should be max. 200 m
(656 ft.) and have a cross-sectional
area of min. 0,5 mm² (AWG 20).

Block Function

Description

G

24 V AC

Supply

G0

24 V AC rtrn

voltage

X1

Input

Control sign-

MX

Input, neutral

als (VH, VC

VH

Increase

short-circuited

VC

Decrease

to G0)

G1

16 V DC

Supply for RC

Y

0–100 %

Feedback
signal

}

}

2V

10V

NORM

VH

VC y

10V

2V

VH

VC y

10V

X1

10V

y

INV

NORM

X1

10V

0(2)V

10V

y

INV

2V

0(2)V

2V

Y X1 MX VH VC G1

1

2

3

4

5

6

7

8

G0 G

Terminal

block

Y X1 MX VH VC G1

G0 G

Forta P

24 V

0 V

K1 K2 KC1

CLOSING RELAY

OPENING RELAY

S2

Ej endläge Non ending position

Endläge Ending position

KC2

K3 K4

Ej endläge Non ending position

Endläge Ending position

Figure 3

Figure 4

Содержание Forta M400

Страница 1: ... by 24 V AC It can provide 16 V DC voltage supply for older TAC controllers Actuator for Valves G 40 22 11 Jun 2003 TECHNICAL DATA M400 Part numbers see the table on the next page Supply voltage 24 V AC 10 50 60 Hz Power consumption average 6 VA Transformer sizing 30 VA Running time Modulating 60 s Increase decrease 300 s 60 s Stroke 10 32 mm 0 39 1 26 in Factory set stroke 20 mm 0 79 in Thrust 40...

Страница 2: ...moves inwards on an increase signal and outwards on a decrease signal see Settings Manual operation There is a manual operation handle on the actuator see figure 2 When it is lowered the motor stops Then the actuator can be operated manually if the handle is turned Position feedback Forta actuators are equipped with a 2 10 V DC position feedback signal where 2 V always corresponds to the closed po...

Страница 3: ...allations on the following conditions the cables between the controller and actuator are shorter than 100 m 328 ft the cross sectional area is larger than 1 5 mm2 AWG 16 and the cables are only connected to one actuator Please refer to the figures labelled Simplified installation for wiring instructions Cable lengths The cables to G G0 and G1 should be max 100 m 328 ft and have a cross sectional a...

Страница 4: ...ta Controller Normal installation 4 wires to the actuator Short cable installation 3 wires to the actuator Forta Controller Forta Controller Normal installation 5 wires to the actuator Short cable installation 4 wires to the actuator Forta Controller Forta Controller Normal installation 5 wires to the actuator PU unit installation 4 wires to the actuator Control cabinet 0 V 24 V AC G0 G K1 K2 KC G...

Страница 5: ...age range to use the upper one 6 10 V 5 10 V or the lower one 2 6 V 0 5 V If the switch is in the NORM position the higher voltage corresponds to 0 and the lower one to 100 To achieve the opposite function the switch should be put in its INV position Running time 60 s 300 s During increase decrease control you can choose between 60 s or 300 s running time During modulating control the running time...

Страница 6: ...e valve and opens it fully The adjustment is finished by the actuator closing the valve again the electronic circuitry then adjusts the stroke and the running time to the valve The set values are stored in the EEPROM of the actuator so that they will remain after a loss of voltage When the end position adjustment is complete the actuator starts to control the valve according to the control signal ...

Отзывы: