1 (6)
0-003-2060-1 (EN)
We reserve the right to make minor changes.
M400 is an electro-mechanical actuator for the control of
two-way and three-way plug valves in:
•
heating systems
•
air handling systems
M400 is primarily designed for applications where the
demands on actuator speed and thrust are small.
The actuator can not be equipped with Self Testing
Device STS.
M400 is either controlled by an increase/decrease signal
or by a modulating 2–10 V control signal.
The electronic circuitry of the actuator ensures that the
running time is the same, regardless of the stroke of the
valve in question.
It is easy to mount and connect the actuator. It can be
mounted directly onto TAC’s control valves, without any
mounting kit.
The working range of the actuator is adjusted
automatically depending on the stroke of the valve. The
electronic circuitry of the actuator then takes care of the
adjustment of the valve end positions.
The actuator is supplied by 24 V AC. It can provide
16 V DC voltage supply for older TAC controllers.
Actuator for Valves
G-40-22
11 Jun 2003
TECHNICAL DATA, M400
Part numbers ....................... see the table on the next page
Supply voltage ............................ 24 V AC ±10%, 50–60 Hz
Power consumption ........................................ average 6 VA
Transformer sizing ...................................................... 30 VA
Running time:
Modulating .................................................................. 60 s
Increase/decrease ............................................ 300 s/60 s
Stroke ........................................ 10–32 mm (0.39 - 1.26 in.)
Factory set stroke ................................... 20 mm (0.79 in.)
Thrust ............................................................. 400 N (90 lbf)
Duty cycle .......................................... max. 20%/60 minutes
Analog input:
Voltage .................................................................. 0–10 V
Impedance ..................................................... min 100 k
Ω
Digital inputs VH–VC:
Voltage across open input .................................. 24 V AC
Current through closed input .................................... 5 mA
Pulse time ....................................................... min. 20 ms
Output G1:
Voltage ..................................................... 16 V DC ±0,3 V
Load ......................................... 25 mA, short-circuit proof
Output Y:
Voltage ................................................... 2-10 V (0-100%)
Load ......................................................................... 2 mA
Ambient temperature:
Operation ............................ –10 – +50 °C (14°F - 122°F)
Storage ................................ –10 – +50 °C (14°F - 122°F)
Ambient humidity ............................................ max. 90% RH
Enclosure rating ........................................................... IP 54
Standards:
Emission ............................................... EN 50081-1:1992
Immunity ............................................... EN 50082-1:1992
Heat ................................................................. IEC-68-2-2
Humidity .......................................................... IEC-68-2-3
Cold ................................................................. IEC-68-2-1
Salt mist ........................................................ IEC-68-2-11
Vibration .......................................................... IEC-68-2-6
Material:
Housing ............................................................ aluminium
Cover ........................................................ ABS/PC plastic
Color ........................................................... aluminium/black
Weight .......................................................... 1.8 kg (3.96 lb)
Dimensions .................... refer to the table on the next page
TAC Forta