TA CORA-HKT Скачать руководство пользователя страница 2

2

Installation

Suitable for installation on valves of radiators, floor heaters etc.
For correct measurement of room temperature, horizontal installation of the CORA-HKT is recom

-

mended.
In relation to power supply and data transmission, 3 options are available.

1.

Battery 

powered, 

wireless

 data transmission

2.

12V

 wired power supply, 

wireless

 data transmission

3.

12V

 wired power supply, 

wired

 data transmission via 

CORA-DL

The thermostat can only be operated using one of these options. It can also only be connected/cou

-

pled with a single controller at a time.
When programming on a controller using the CORA-HKT, it is necessary to enter whether wired or

wireless data transmission is in use.
When using wired 

12V

 power supply, values are updated every minute. When 

battery powered,

 val

-

ues are updated every 5 minutes.
If the CORA-HKT is powered using batteries, it cannot be used as a HOP node (see „Relaying wireless

signals“).

Wireless system

Principles

The wireless system comprises multiple CORA devices (e.g. CAN-MTx2 and CORA-HKT), which com

-

municate with one another, exchange data or transfer firmware.
The wireless range is around 1000 m outdoors, and typically 30 m in buildings (through approx.

2 walls/ceilings, depending on thickness and material). Up to 3 additional wireless devices can be

used as a bridge to enable data to be exchanged under deviating conditions.
RCV-DL, GBS-F and RAS-F devices 

cannot

 be used.

Pairing CORA devices

Two steps are carried out to pair two devices:

1. Allow

 pairing on the 

target device

2. Initiate

 pairing on the 

control device

To allow pairing on the EHS-R (= target device), double click on the button on the casing (= 2 click

within 2 seconds). Pairing is then allowed for 5 minutes (see chapter "Reset / Pairing").
On the control device, the CORA ID for the CORA-HKT is required for pairing.
The pairing process on other devices (control device) can be found in the corresponding operating

instructions.

Relaying wireless signals

Wireless-capable devices can relay signals of other devices. All required settings for this are carried

out at the device, which transmits the signal to be relayed. 
The CORA-HKT can also be used to relay wireless signals of other devices, but only when used with

wired power supply. Should it receive signals for relaying, it does so automatically. No additional set

-

tings for the CORA-HKT are necessary for relaying signals.

Содержание CORA-HKT

Страница 1: ...ying wireless signals 2 Wired connection 3 Battery powered operation 3 Initialisation run 3 Button 4 Opening the device 4 LED status indicator 4 Output variables 5 Error codes 5 Input variables 6 Prog...

Страница 2: ...nsfer firmware The wireless range is around 1000 m outdoors and typically 30 m in buildings through approx 2 walls ceilings depending on thickness and material Up to 3 additional wireless devices can...

Страница 3: ...pdated every 5 minutes Battery lifetime varies based on activity but typically lasts 3 years Initialisation run As soon as the HKT receives power it immediately carries out an initialisation run As su...

Страница 4: ...g for 5 minutes 10 sec long press Total reset While holding the button for a total reset the LED flashes red The button must be held until the LED turns green at which point the total rest is carried...

Страница 5: ...y opened position is defined by the initialisation run see page 3 Fully opened depends on the valve of the radiator Window contact Digital value Yes No Yes win dow closed Based on the room temperature...

Страница 6: ...ly opened 100 fully closed Set position 0 100 The desired position of the valve can be set manually Helpful in case several HKTs in the same room regulate different radiators See programming exam ple...

Страница 7: ...ad to the thermo stats attempting compensate for each other s temperatures by setting the valves into opposite po sitions one HKT might heat excessively while the other might not heat at all Several H...

Страница 8: ...to constant tech nical advancement and further development We therefore reserve the right to make changes without prior notice 2023 Batteries 2x AA not included Battery lifetime varies based on batter...

Страница 9: ...9...

Страница 10: ...10...

Страница 11: ...considered EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 General requirements EN 61000 6 3 2007 Electromagnetic compatibility EMC Part 6 3 Generic standards Emissi...

Страница 12: ...stallation instructions or incorrect maintenance 4 The guarantee will become void if repairs or actions are carried out by people who are not authorised to perform them or have not been so authorised...

Отзывы: