SETTING THE CONTROLLER (SEE FIG.1).

1.

Set Td to required 'Day' temperature during occupancy.

2.

Set Tn to minimum 'Night' temperature during unoccupied periods.

3.

Set dph to design preheat time. This is the maximum time required 
for recovery to required day temperature after an unoccupied 
period during which the inside temperature has fallen to 12°C.

a.

Select the approximate time in whole hours on the rotary 
switch (1 to 5 hours).

b.

Fine trim ±1/2 hour on the associated setting potentiometer.

4.

Note: ALL 'ON' times must be set earlier than the start of 
occupancy by the selected pre-heat time (dph) set at (3) above.

Example:

DPH = 2 hours

 

Occupancy time = 8:00 am

 

Set clock 'ON' time to 6:00 am

ANALOGUE CLOCK OPERATION - SVT 4201

Cautions
DO NOT rotate the outer dial in any direction.

DO NOT rotate the minute hand anti-clockwise as this will damage 
the mechanism.

Each day can be set independently.

Day 1 is Monday and Day 7 is Sunday.

The clock manual override switch has the following functions:

I

-

OFF

-

Automatic control

II

-

ON

Overrides are usually set from the SVT and the clock override is left in 
the Automatic position.

SETTING THE ANALOGUE SWITCHING TIMES

1.

Set the required weekly programme by pushing in the blue 
segments around the clock dial for all 'ON' periods and pulling 
them out for all 'OFF' periods.

2.

For omitted days such as Sunday all the segments must be pulled 
out.

SETTING THE ANALOGUE CLOCK

1.

Set the time by turning the minute hand clockwise until the correct 
time and day is set.

2.

Make sure the SVT manual override switch is set to AUTO mode.

SETTING THE DIGITAL CLOCK

1.

SETTING THE TIME AND DATE

Time 
indicator

Menu selection, back in menu,
actuation > 1 s = back to status display

Select menu items or set parameters.

Confirm menu selection or adopt parameters

Reset

Press at the same time

1

3

2

4

5

TIME

  

OFF

6

7

WI

NEXT

AUTO

Prog

Memo free

Time

0:00

Date

01.01.2004

Su/Wi

EU

TIME/DATE SU WI

PROG

MODE

SET

TIME/DATE

SU WI

SET

TIME

SET

TIME

SET

TIME

SET

TIME

SET

SET

DAY

DATE

SET

DATE

DAY

SET

DATE

MONTH

SET

DATE

MONTH

SET

DATE

YEAR

SET

YEAR

DATE

TIME/DATE

SU WI

SET

Содержание Satchwell SVT

Страница 1: ...regain the required temperature at occupancy time In very mild weather this delay can be as much as five hours later than in cold weather and fuel savings of between 10 and 25 are possible By relating the start time to the inside temperature rather than the outside temperature the insulation and thermal mass of the building are taken into account The SVT makes the benefits of optimum start control...

Страница 2: ...hort power interruption to the electronics during the preheat period Ambient Temperature Limits Operating 0 to 40 C SVT 4201 Storage Transit 0 to 55 C 0 to 50 C SVT 4251 Max Ambient Humidity 95 rh non condensing CONSTRUCTION DIN Standard 144 x 144mm square for wall or flush panel mounting cut out size 138 x 138mm Case 2 piece polycarbonate or ABS moulding Fire Resistant Protection Class IP 41 Wind...

Страница 3: ... upper terminals b Check all wires are in accordance with scheme diagram or diagrams on this leaflet c Ensure all necessary links and resistors have been connected or removed as instructed 4 Check slide switch S is in correct position for application 5 Temporarily remove sensor wires and substitute a simulator If not available connect a variable resistor or switchable fixed resistors of values app...

Страница 4: ...l override switch has the following functions I OFF Automatic control II ON Overrides are usually set from the SVT and the clock override is left in the Automatic position SETTING THE ANALOGUE SWITCHING TIMES 1 Set the required weekly programme by pushing in the blue segments around the clock dial for all ON periods and pulling them out for all OFF periods 2 For omitted days such as Sunday all the...

Страница 5: ...WI SET WI MONTH SET WI MONTH SET WI YEAR TIME DATE SU WI SET SU WI SET SU WI SET DAY SU SET SU DAY SET SU MONTH SET SU MONTH SET SU YEAR SET SU YEAR SU TEST MODIFY NEW PROG MODE SET TIME DATE SU WI PROG MODE SET Programming One program switch on time switch off time switch on and switch off days Programs with predefined switch on switch off days DAY 1 7 MO SU DAY 1 5 MO FR DAY 6 7 SA and SU ...

Страница 6: ...1 3 2 4 5 NEW ON OFF PROG 6 7 TEST MODIFY NEW PROG NEW PROG 1 3 2 4 5 NEW PROG 6 7 1 3 2 4 5 NEW PROG 6 7 DAY 1 7 1 5 6 7 ANY DAY NEW PROG 1 3 2 4 5 NEW ON OFF PROG 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 Select switch on day Tuesday Select switch off day Tuesday 5x ...

Страница 7: ...t program Change switching times Change switching days MODIFY PROG MODIFY PROG MODIFY PROG Prog 1 Prog 2 Prog 3 NEW PROG 1 3 2 4 5 MODIFY ON OFF PROG 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 1 3 2 4 5 ON OFF 6 7 5x DEL ONE Delete a single program DEL ALL Delete the programs for the channel TEST MODIFY NEW PROG MODIFY PROG MODIFY PROG MODIFY PROG 1 3 2...

Страница 8: ...parate loom or trunk from any mains wiring and spaced as far as possible away from it 230Vac 45cm Min 415Vac 58cm Min both voltages are with respect to earth and a maximum current of 15A For other voltages currents refer to the IEE report titled Electro magnetic interference September 1987 ISBN85296353X TEST MODIFY NEW PROG TEST PROG PROG C1 TEST prog Programs in the order entered SERIAL Switching...

Страница 9: ...4 at switch off time after inside temperature cools to below Td R2 makes 5 3 if inside temperature Td R2 makes 5 4 if inside temperature Td nominal differential 1 C 1 2 PLANT Boiler Pump 3 DAY 4 BOOST 5 COMMON Fig 1 Voltage free outputs WIRING PRECAUTIONS Fig 2 The switch takes effect at the next switch on time HOLIDAY Open AUTO Closed Remove link 6 7 Fig 3 RECORDER 0 to 10Vdc RECORDER 0 to 100mV ...

Страница 10: ...mmissioning procedures have been completed If any equipment covers have to be removed during the installation of this equipment ensure that they are refitted after installation to comply with UL and CE safety requirements This is a mains operated device Local wiring regulations and usual safety precautions must be observed Note Earthing requirements Do not switch on mains power until commissioning...

Отзывы: