Table-4 Troubleshooting

.

Components within TAC I/A Series MicroNet Sensors can not be field repaired. If there is a 
problem with a sensor, follow the steps below before contacting your local TAC office.

1. Make sure sensors are connected and communicating to desired devices.

2. Record precise hardware setup indicating the following:

Version numbers of applications software.

Controller firmware version number.

Information regarding the WorkPlace Tech Tool application program.

A complete description of difficulties encountered.

Sensor Condition

Corrective Action

LCD remains blank.

• Check sensor and controller wiring and correct, if necessary.
• If wiring is okay, check to see if power is being applied to the 

sensor by pushing the Override Key for less than four seconds. 
If the Override LED lights up, the sensor is powered. If the 
Override LED does not light up, the sensor may not be 
receiving power. Check controller power to verify presence.

• If the above measures do not address the problem, download 

a new application to the controller.

Sensor displays “Abn” 

indefinitely.

• Check the documentation to make sure the sensor model is 

compatible with the controller application and then choose one 
of the following options.

• If the sensor and application are compatible, download a new 

application to the controller. 

• If the sensor and application are incompatible, download an 

application that is compatible with the sensor. Or, install a 
sensor that is compatible with the controller application.

All LCD icons light up and 

remain lit.

• Check to see if the controller is constantly resetting and 

correct, if necessary.

• Check sensor and controller wiring and correct, if necessary.
• If reset and wiring are okay, download a new application to the 

controller.

• If the above measures do not address the problem, the 

controller may need to be configured. For configuration 
instructions, consult documentation associated with the 
network management tool.

Содержание I/A MicroNet MN-S Series

Страница 1: ...l interference between sensor and controller An optional wiring connection allows access to the TAC MicroNet LONWORKS network LON via a LONWORKS network jack on the left side of each sensor This jack...

Страница 2: ...Indication a LCD displays value and setpoint MN S4b b Allows viewing of alarms and diagnostics MN S4HTb Sensor with setpoint override and controller mode functions Six button Digital LCDc and LED Over...

Страница 3: ...A Series MicroNet MNL 11RF2 and MNL 13RF2 Controllers Includes instructions for network wiring installation on a LONWORKS network checkout and LED indication F 26580 TAC I A Series WorkPlace Tech Tool...

Страница 4: ...plate AT 1155 Clear plastic guard with solid and ring base tumbler type key lock AT 1163 Wire guard with steel base plate MNA STAT 1 Replacement covers qty 12 MNA STAT 2 Designer inserts for MN S1 mo...

Страница 5: ...ealer or an experienced radio television technician for help Canadian Department of Communications DOC This class B digital apparatus meets all requirements of the Canadian Interference Causing Equipm...

Страница 6: ...ure 1 and Figure 2 for appropriate mounting dimensions Figure 1 Mounting Dimensions for Direct wall 2 x 4 Electrical Box and Surface Box Mounting Figure 2 Mounting Dimensions for 1 4 DIN Electrical Bo...

Страница 7: ...e screws use drywall anchors as necessary mount base plate to wall Figure 3 Figure 3 Direct wall Mounting 2 x 4 Electrical Box Mount 1 Use mounting dimensions shown in Figure 1 2 Feed S Link wires fro...

Страница 8: ...ause a short of the LONWORKS network 4 Using two appropriate screws not provided mount base plate to electrical box using vertical mounting holes indicated in Figure 5 Figure 5 1 4 DIN Electrical Box...

Страница 9: ...n 32 pF per foot 0 3 m If shielded cable is used the capacitance between any one conductor and the others connected to the shield cannot be more than 60 pF per foot 0 3m Maximum wire length is 200 ft...

Страница 10: ...nt TAC I A Series MicroNet Controllers use LONWORKS Free Topology Transceivers and support polarity insensitive bus daisy chain and free all combinations of star tee and loop wiring topologies See TAC...

Страница 11: ...erved 11 Figure 8 Electronic Assembly Installation 3 Insert bottom tabs of cover and then snap top into place Note To remove sensor cover place thumb in middle of sensor grasp top edge of cover with f...

Страница 12: ...and allows controller setpoint adjustment The MN S3 offers one setpoint and one default display screen X X X X X MN S3HT MN S3HT adds humidity sensing functionality to the MN S3 X X X X X X MN S4 The...

Страница 13: ...e appears 2 Press Up Down Key to scroll through Node Address frame Errors frame and Alarms frame To access adjustable diagnostic data Access Temperature Offset frame and Relative Humidity Offset frame...

Страница 14: ...ey to change from the first display screen slot to the second display screen slot Before the second display screen slot appears 2 will appear to indicate you are about to view the second slot 2 Press...

Страница 15: ...mode corresponding icon Table 3 and 1 Note There are two mode slots The mode assigned to each slot depends on the controller application and sensor configuration If the sensor displays three dashes w...

Страница 16: ...sensor s configuration If sensor does not respond when you press the Setpoint Key all setpoints slots are unassigned or not active 2 Continue to press Setpoint Key to scroll through the setpoint slots...

Страница 17: ...mode is active or unoccupied setpoints are displayed This icon is not displayed in the occupied mode Fan Speed 2 Speed Fan The Fan Speed Icons indicate the speed of the fan If the fan has a two speed...

Страница 18: ...ide LED does not light up the sensor may not be receiving power Check controller power to verify presence If the above measures do not address the problem download a new application to the controller...

Страница 19: ...F 26277 7 Copyright 2006 TAC All Rights Reserved 19...

Страница 20: ...7 7 www tac com TAC 1354 Clifford Avenue P O Box 2940 Loves Park IL 61132 2940 Distributed manufactured and sold by TAC I A SERIES trademarks are owned by Invensys Systems Inc and are used on this pro...

Отзывы: