t.a.c. DuraDrive MS40-717 Series Скачать руководство пользователя страница 10

10

© 

Copyright 2007 TAC All Rights Reserved.

F-26748-4

Mounting the Actuator for Clockwise or Counterclockwise Dampers

The zero (0) position on the position indicator is the normal or spring return position. When 
the actuator is mounted with the “R” side facing the installer and the control signal increases 
the actuator will rotate in the counterclockwise direction. When the actuator is mounted with 
the “L” side facing the installer and the control signal increases the actuator will rotate in the 
clockwise direction.

Long Damper Shafts

1. Move the damper to its normal position. Verify the controller action is set to match the 

damper application (normally closed or normally open). See TYPICAL APPLICATIONS 
(wiring diagrams).

– For normally closed damper, when damper is closed the actuator position indicator 

should be at 0°. When damper is open the actuator position indicator should be at 
90°.

– For normally opened damper, when damper is open the actuator position indicator 

should be at 0°. When damper is closed the actuator position indicator should be at 
90°.

Note:

The actuator comes equipped with two AM-754 universal mounting clamps. For 

damper shafts larger than 1/2" (13 mm) in diameter, the AM-753 universal mounting 
clamps are required (order separately). The AM-753 clamps accommodate round shaft 
sizes ranging from 3/4" to 1" (19 to 25 mm) or 5/8" (16 mm) square shafts.

2. Slide the actuator over the shaft and into its desired final mounting position. 

– If the damper shaft rotates clockwise to the closed position, mount the actuator with 

the side marked “R” facing the installer. See Figure-10.

– If the damper shaft rotates counterclockwise to the closed position, mount the 

actuator with the side marked “L” facing the installer. See Figure-11.

3. Hand tighten the nuts on both of the actuator’s universal mounting clamps.

4. Align the actuator at 90° (perpendicular) to the damper shaft. See Figure-12.

5. Slide the anti-rotation bracket pin into the mounting slot on the actuator and drill 

mounting holes. See Figure-12. For narrow spaces the AM-752 anti-rotation bracket is 
recommended (order separately).

6. Attach one side of the anti-rotation bracket to the mounting surface with one of the 

screws provided. Leave the screw loose so that the bracket can be rotated. See 
Figure-10 for clockwise or Figure-11 for counterclockwise spring return.

7. Pivot the anti-rotation bracket away from the actuator. See Figure-10 or Figure-11.

8. Loosen the universal mounting clamps, making sure not to move the damper shaft. 

Rotate the actuator approximately 5° in the direction which would open the damper. See 
Figure-10 or Figure-11.

9. Tighten all of the universal mounting clamp nuts with a 1/2" socket wrench. Apply 

4 to 6 ft -lbs (5 to 8 N-m) of torque.

10. Manually rotate the actuator toward the full-closed position to apply pressure to the 

damper seals. See Figure-10 or Figure-11.

11. Pivot the anti-rotation bracket into place and secure the other side of the bracket onto 

the mounting surface using the other screw provided with the actuator. See Figure-10 
or Figure-11.

12. Verify that the damper is in its full-closed position and actuator at 90° (perpendicular) to 

the damper shaft. See Figure-10 or Figure-11.

Содержание DuraDrive MS40-717 Series

Страница 1: ...d reliability and repeatable timing Direct coupled to the damper shaft with dual industrial hardened universal mounting clamps Integral wiring for proportional control by 2 to 10 Vdc or 4 to 20 mAdc1 Clockwise or counterclockwise spring return is determined by actuator mounting position Accurate 92 travel digitally controlled Integral position indication scale Rugged die cast housing Oil immersed ...

Страница 2: ...to 25 mm round damper shafts two per package F Number Description Audience Purpose F 26750 MX40 6XXX 2XX MX40 7XXX 2XX Series Actuator Linkage Assemblies General Instructions Sales Personnel Application Engineers Installers Service Personnel Start up Technicians Describes the globe valve actuator linkage assembly s features specifications and possible applications Provides step by step mounting in...

Страница 3: ... OD for dual actuator mounting AM 703 Span adjustment AM 704 Modulation Interface converts a PWM to 2 to 10 Vdc AM 705 Positioner remote minimum positioning AM 706 Positioner flush mount digital position indicator AM 707 Digital Indication AM 708 Resistor for 500Ω modulating signal conversion AM 751 Standard anti rotation bracket 9 long x 13 16 wide 229 x 21 mm included with actuator AM 752 Option...

Страница 4: ...odes 3 Keep AI COM and AO wiring less than 30 meters length to meet CE requirements 2 3 Figure 1 Typical MS40 7170 2 to 10 Vdc Wiring Diagram MS40 7170 Black White L1 L2 120 Vac GRD Green Yellow Yellow Black Gray AI COM 4 to 20 mA 1 Position Feedback Signal 2 to 10 Vdc Blue AO 500 Ohm Control Signal 1 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to m...

Страница 5: ...lugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating 2 Color coding of wiring on older models MX40 717x 0 0 0 manufactured prior to December 2007 differs from current models See Table 4 on page 14 Consult label on product to confirm wiring codes 3 Keep AI COM and AO wiring less than 30 meters length to meet CE requirements 2 3 Figure 4 Typical MS40 717...

Страница 6: ...dc Control Signal GRD MS40 717X Power GRD 1 1 2 MS40 717X 1 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating 2 See table for power wire designations 3 Both actuators must be set to operate in the same direction 3 3 Yellow Black AI Gray COM Blue AO Yellow Black AI Gray COM Blue AO Position Feedback Signal 2 to 10 Vdc...

Страница 7: ...r tight conduit when using AM 756 metric conduit adaptor Two 8 1 2 13 mm sheet metal screws for mounting optional Training Installer must be a qualified experienced technician 4 to 20 mA DC Controller 4 to 20 mA DC Common DC Power GRD GRD 1 1 2 MS40 717X MS40 717X 1 Unused conduit port must remain plugged with a water tight pipe plug as shipped from factory to maintain NEMA Type 4 or IP56 rating 2...

Страница 8: ...ference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment to an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio television technician for help Canadian Department of Communications DOC Note This class B digital appa...

Страница 9: ... contact the damper manufacturer Damper Shaft Sizing Use the Long Damper Shaft mounting instructions if the damper shaft is at least 4 5 8 117 mm long Use the Short Damper Shaft mounting instructions if the damper shaft is shorter than 4 5 8 or the area around the damper shaft is too narrow to allow standard mounting as described in the Long Damper Shaft mounting section See Figure 9 for minimum s...

Страница 10: ...e closed position mount the actuator with the side marked R facing the installer See Figure 10 If the damper shaft rotates counterclockwise to the closed position mount the actuator with the side marked L facing the installer See Figure 11 3 Hand tighten the nuts on both of the actuator s universal mounting clamps 4 Align the actuator at 90 perpendicular to the damper shaft See Figure 12 5 Slide t...

Страница 11: ...e Spring Return for Normally Closed Damper R 1 1 5 CENTERLINE 1 Two AM 754 Universal Mounting Clamp Assemblies are provided with each actuator Each clamp assembly includes 1 universal mounting clamp and 1 retaining clip Two Universal Mounting Clamp Assemblies are required for all mounting configurations ...

Страница 12: ...TERLINE 1 Two AM 754 Universal Mounting Clamp Assemblies are provided with each actuator Each clamp assembly includes 1 universal mounting clamp and 1 retaining clip Two Universal Mounting Clamp Assemblies are required for all mounting configurations Figure 12 Mounting Anti rotation Bracket to Actuator AM 751 Anti rotation bracket 90 Actuator mounting slot 90 ...

Страница 13: ...ctuator is 90 perpendicular to the damper shaft Then hand tighten the nuts on both of the actuator s universal mounting clamps See Figure 12 Note If the universal shaft extension protrudes excessively above the damper actuator s top universal mounting clamp remove the damper actuator from the universal shaft extension remove the extension from the damper shaft shorten the universal shaft extension...

Страница 14: ...circuits Table 3 Control and Power Wiring Data Table 4 Wire Color Codes for Models Manufactured before December 2007 Figure 13 Installation of Universal Shaft Extension Actuator Anti rotation Bracket included with actuator AM 753 Universal Mounting Clamps Duct V clamp Mounting Surface Damper Shaft AM 676 Universal Shaft Extension 1 1 The AM 676 extends the damper shaft approximately 9 229 mm Actua...

Страница 15: ...ontroller output to minimum 5 Check to see that the actuator travels to the fully closed position Note If anticipated damper operation does not occur verify the Long Damper Shaft or Short Damper Shaft mounting procedures Also verify that the controller has the proper action direct or reverse to match the damper required operation THEORY OF OPERATION The actuator is by means of dual mounting clamps...

Страница 16: ...ctive owners Information contained within this document is subject to change without notice F 26748 4 www tac com TAC 1354 Clifford Avenue P O Box 2940 Loves Park IL 61132 2940 DIMENSIONAL DATA Figure 14 dimensions are in inches mm Figure 14 MS40 717X Damper Actuator 4 102 4 102 1 27 64 36 10 27 32 275 R ...

Отзывы: