SRC-131 Hotel Controller Manual
19
Value
40034
Read Only
Remote Sensor
Value
Value / 10 (e.g. 21.8°C = 218)
40035
Read Write
W relay status
0 = Off (under thermostat control)
1 = Energised (under thermostat control)
1000 = Held OFF by Modbus
1001 = Held ON by Modbus
1 = Energised
40036
Read Write
Y Relay Status
0 = Off (under thermostat control)
1 = Energised (under thermostat control)
1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40037
Read Write
High Fan Relay
Status
0 = Off (under thermostat control)
1 = Energised (under thermostat control)
1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40038
Read Write
Medium Fan
Relay Status
0 = Off (under thermostat control)
1 = Energised (under thermostat control)
1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40039
Read Write
Low Fan Relay
Status
0 = Off (under thermostat control)
1 = Energised (under thermostat control)
1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40040
Read Write
0-10V Heat Value Value / 10 (e.g. 7.3V = 73)
( To write add 10 e.g. - to write 7.3v send 1073
40041
Read Write
0-10V Cool Value Value / 10 (e.g. 7.3V = 73)
( To write add 10 e.g. - to write 7.3v send 1073
Values below only apply to version 2 hardware only, Firmware version 3+
40043
Read / Write
2 pipe mode
changeover
0 = Heat
1 = Cool
40044
Read / Write
Thermostat
Displaying
0 = Deg C
1 = Deg F
40045
Read / Write
Buttons shown on
display
0: Both mode and fan buttons show (default)
1: Show mode but hide fan button
2: Show fan but hide mode button
3: Hide both mode and fan buttons
40046
Read / Write
Permitted Modes
0: Off / Auto
1: Off / Heat / Cool / Auto
2: Off / Heat / Cool
3: Off / Heat
4: Off / Cool
5: Off / Auto – (display current mode in LCD)
40047
Read / Write
Swap C/F display
shown on display
0: C/F Button hidden
1: C/F button shown
40048
Read / Write
Fan Span for 3
speed relays
0.5C-10 C 0.5C step 1.0F-20 F 1F steps
Data format : Fan span * 10
40049
Read / Write
0-10 Fan Interval
10-300 seconds in 10 second steps (60 seconds
default.
40050
Read / Write
0-10 Fan Direction 0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40051
Read / Write
0-10 Fan Minimum
Voltage.
0-10v (Fan value x 10)
40052
Read / Write
0-10 Heat Interval 10-300 seconds in 10 second steps (60 seconds default.
40053
Read / Write
0-10
Heat
Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open n(reverse acting)