VR 250 ECH/B
Installation description
206609 (17-09-2010)
13
Systemair
AB
GB
Before starting the system
1. Choose required airflow at normal fan speed as follows:
Set the normal fan speed from a potentiometer on the print card in the unit (see
fig. 13
). The
potentiometer is set by using a screw driver. Each setting corresponds to a different fan speed based
on certain voltage output to the fans (see
table 1
). To get an idea of the airflow corresponding to each
setting see
fig. 14
showing a fan performance diagram displaying performance curves for supply air
and extract air.
DI1
Lo
Hi
GND
12V
AI2
GND
AI3
GND
AI4
GND
GND
AI1
R
N
Earth
R
N
R
N
DI2
220V Aux 2
220V Aux 1
COM
8
8
Table 1
Setting
Voltage output (V)
0 3,63
1 3,99
2 4,35
3 4,72
4 5,09
5 5,45
6 5,82
7 6,17
8 6,54
9 6,9
A 7,27
B 7,64
C 8,00
D 8,36
E 8,73
(Default)
F 10,17
Fig. 13
0
5
10
15
20
25
30
35
40
45
50
55
50
100
150
200
0
250
300
350
400
Q(l/s)
4.1V
6V
1
2
7.7V
10V
1
Fan performance curve extract air
2
Fan performance curve supply air
2. Adjust diffusers and louvers in accordance with commissioning or basic setting (see
"Diffusers/Louvers"). Make sure that the inlet diffusers are set so that the air stream is not lead
towards visible joist, wall etc. close to the diffuser.
Содержание VR 250 ECH/B
Страница 1: ...10 04 17 09 2010 VR 250 ECH B Air Handling Unit Installation description GB GB...
Страница 15: ...10 04 2010 09 17 VR 250 ECH B Luftbehandlingsaggregat Installationsbeskrivning GB SE...
Страница 29: ...10 04 17 09 2010 VR 250 ECH B Ventilasjonsaggregat Montasjeanvisning NO...
Страница 43: ...10 04 17 09 2010 VR 250 ECH B L ftungsger t Installationsanweisung DE...