| Configuration Guide: Fan control type – Pressure
5.3
Allocation
Setup differential pressure sensors.
Select I/O placement for the differential pressure sensors and set the sensors’ measuring range in the “Configuration >
I/O allocation settings > Analog inputs” menu.
Overview:
Configuration > I/O allocation settings > Analog inputs
06 Nov 8:25
Analogue inputs
Device
Signal
Pressure supply air
Controller
UAI2
Pressure extract air
Controller
UAI1
Configuration > ... > Analog inputs > Pressure supply air
06 Nov 8:25
Minimum
0.0
Maximum
500.0
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select UAI2 as signal for Pressure supply air
5. Select UAI1 as signal for Pressure extract air
6. Select Pressure supply air
7. Set “Minimum” the same as the start point of the sensor’s selected measuring range
8. Set “Maximum” the same as the end point of the sensor’s selected measuring range
9. Go back to Analog inputs (use the navigation path “Configuration > I/O allocation settings > Analog inputs”)
10.Select “Pressure extract air” and repeat steps 7 and 8.
151785 | A002