Commissioning
4.1
Before starting the system
When the installation is finished, check that:
• The unit is installed in accordance with the installation instructions
• The unit is correctly wired
• Mufflers are installed and that the duct system is correctly connected to the unit
• Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vac-
uum system exhaust or similar)
• All external equipment are connected
• The following data is available:
• Intended configuration, for example temperature control functions, fan control, external control functions etc.
• How the unit is supposed to operate according to a weekly schedule (normal and reduced speed)
4.2
Initial setup of the unit
On the first start-up, the controller will start a special program for setting language, supply air temp set point, Time &
date and week schedule for normal speed. Use the “OK” button to move between changeable parameters and the UP/
DOWN arrows to see the displayed alternatives. Confirm by pressing “OK” once more. Move on down in the menu
structure by use of the UP/DOWN arrows.
The following will be displayed:
Choose Language
English
1 Select language by pressing “OK” and then move be-
tween the alternatives with the UP/DOWN buttons.
Confirm by pressing “OK”. Move to the next level by
pressing the “DOWN” button.
Supply air temp
Actual:.... ºC
Setp.: 18 ºC
2 Set the supply air set point. Default is 18°C (logon to
service level needed, code
2222
, to change default
setting)
Time: 12.46
Date: 2010–03–12
Weekday: Friday
3 Check and make sure that correct time and date is dis-
played, if not change the settings
Normal speed
Monday → Friday
Per 1: 07:00 – 16:00
Per 2: 00:00 – 00:00
4 Set the week schedule for how it’s intended for the
unit to operate at normal speed during Monday to Fri-
day. It’s possible to set 2 periods per day.
Normal speed
Saturday → Holiday
Per 1: 07:00 – 16:00
Per 2: 00:00 – 00:00
5 Set the week schedule for how it’s intended for the
unit to operate at normal speed during Saturdays and
holidays. It’s possible to set 2 periods per day.
Reduced speed
Monday → Friday
Per 1: 00:00 – 24:00
Per 2: 00:00 – 00:00
6 Set the week schedule for how it’s intended for the
unit to operate at reduced speed during Monday to
Friday. It’s possible to set 2 periods per day. Normal
speed inactivates reduced speed.
Reduced speed
Saturday → Holiday
Per 1: 00:00 – 24:00
Per 2: 00:00 – 00:00
7 Set the week schedule for how it’s intended for the
unit to operate at reduced speed during Saturdays
and holidays. It’s possible to set 2 periods per day.