4.7.1.2 Condensation and Heat Insulation
Outdoor air duct and exhaust ducts must always be well insulated against condensation. Correct insulation
installation on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas
must be well insulated. Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion
barrier. In areas with extremely low outdoor temperatures during the winter, additional insulation must be
installed. Total insulation thickness must be at least 150 mm.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
4.7.1.3 Silencers
To avoid fan noise being transferred via the duct system, silencers should be installed both on supply and
extract air.
To avoid noise being transferred between rooms via the duct system and also to reduce noise from the
duct system itself, installation of silencers before every inlet diffuser is recommended.