Set the weekly schedule by choosing
Week
program
and edit the values. For more
information, see section 4.3.
5 Setting Type of Function
The unit is preset for
Not Active
.
Change the function by choosing
Functions
and
then some of the menu alternatives. For more
information, see section 4.3.
4.3 Software Description
Menu Item
Sub-menu
Item
Sub-sub-
menu Item
Explanation
Man / Auto
:
Show if the unit is running in
Manual
or
Automatic
mode.
Fanspeed
:
Show if the fans are running on
Low
,
Medium
or
High
speed or if the unit is stopped
Extended
/ Forced
running
Activate extended/forced running.
Extended/Forced running is the time the unit goes
from shut down mode, Low or Medium fan-speed
to the fan speed of your choice. OFF and ON
times and fan-speeds are set at the submenu
Week program
.
Control
temp.
Set the desired control temperature value,
16-30°C.
Running mode
Set the running mode of the unit. Choose
between:
Auto
,
Manual high
,
Manual
medium
,
Manual low
, or
Manual shut off
.
Service
Login with 1111 to service level. Log’s out after 5
minutes of inactivity, with main supply on.
Time / Date
Set the present time, date and weekday.
Week
program
Set the units ON time for each week day, 2
periods/ day
Preset time is Period 1. 07:00-16:00
Monday-Sunday and Period 2. 00:00-00:00
Monday-Sunday, 00:00-00:00 inactivates the
period.
For continuous run 00.00–23.59 must be set
Set the fan-speed when the unit is on to
Low
,
Medium
or
High
and the fan-speed when the unit
is off to shut off,
Low
,
Medium
or
High
.
Preset is: ON =
Medium
(75%) and OFF =
Low
(35%).