Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
Outdoor
comp.Setp.
–20°C = 0 m³/h
0°C = 0 m³/h
Act.
Comp:
0
m³/h
Set the SAF airflow
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive
or negative.
Shows the actual airflow
compensation.
Flow control
EAF
Actual:
xxx
m³/h
Setp.:xxx m³/h
Airflow for the extract air fan
(constant airflow control).
Only visible if the unit is
configured for “Flow control”
(CAV).
Flow control EAF
Setp 1/1:
1100
m³/h
Setp 1/2:
550
m³/h
↓
Set the normal (1/1) and
reduced (1/2) airflow for the
extract air fan.
Outdoor
comp.Setp.
–20°C = 0 m³/h
0°C = 0 m³/h
Act.
Comp:
0
m³/h
Set the EAF airflow
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive
or negative.
Shows the actual airflow
compensation.
Pressure
control SAF
Actual:
Pa
Setp.:
Pa
The actual external pressure
and set point for the supply air
fan.
Only visible if the unit is
configured for "Pressure
control" (VAV)
Pressure control
SAF
Setp 1/1:
200
Pa
Setp 1/2:
100
Pa
Set the external pressure set
point for normal speed (1/1)
and reduced speed (1/2) for the
supply air fan.
Topvex FC
Operation and Maintenance Instructions