5
3.2.3
Electrical data Topvex FC
Model
Fans (W tot.) 230V 1~ and
400 V 3N~
El Heating battery (kW tot.)
Fuse (mains) (A) for
230 V 1~ and 400 V
3~
Topvex FC02
EL
1040
5
3x13
Topvex FC02
None, HWL, HWH
1040
-
10
Topvex FC04
EL
1536
10
3x25
Topvex FC04
None, HWL, HWH
1536
-
10
Topvex FC06
EL
5134
16
3x35
Topvex FC06
None, HWL, HWH
5134
-
3x10
3.3
Transport and storage
Topvex FC is delivered in one piece standing on a pallet for easy transportation using a forklift. The unit should be stored
and transported in such a way that it is protected against physical damage that can harm panels, handles, display etc. It
should be covered so that dust, rain and snow cannot enter and damage the unit and its components. The appliance is
delivered complete with all necessary components, wrapped in plastic on a pallet for easy transportation.
At delivery the unit is fastened to the pallet with mounting brackets. Unscrew the brackets from the pallet and fastened
them on the units upper side for roof installation. Do not lift the unit in the mounting brackets, they are only intended
for mounting the unit in the roof.
When transporting the Topvex FC units use a forklift placed on the gable of the unit.