SystemAir SAVE-P VSR 150/B Скачать руководство пользователя страница 13

Maintenance |

9

3.2.8.1 To schedule airflow settings

Touch settings icon to go to

SCHEDULE AIRFLOW SETTINGS

menu. In this

menu set airflow level for scheduled and unscheduled periods. Available lev-
els:

Off

,

Low

,

Normal

,

High

or

Demand

.

Set temperature setpoint offset for both periods (-10°C – 0°C).

Demand

level is available only if

Demand Control

or

External

fan function is active.

4

Maintenance

Danger

• Make sure that the mains supply to the unit is disconnected before performing any maintenance or

electrical work!

Warranty claims can only be made if maintenance work is carried out correctly and written evidence thereof is
provided.

4.1

Maintenance Schedule

Task

6 months

1 year

3 years

When necessary

General inspection

X

Filter change

X

X

Fan cleaning

X

Heat exchanger cleaning

X

X

Belt replacement

X

Checking and cleaning louvres/
diffusers

X

Checking and cleaning outdoor air
intake

X

Checking and cleaning roof cowl (if
fitted)

X

Cleaning of duct system

X

1

1. It is recommended to do this every 5 years and is normally carried out by authorized companies specialized in this area.

• Use original spare parts from Systemair only.

• Scan the code on the type label to find a spare part list.

4.2

To access internal components

Danger

• Make sure that the mains supply to the unit is disconnected before performing any maintenance or

electrical work!

• If the unit is ceiling mounted with the side cover facing downwards, be careful when opening the side

cover.

271400 | v1.0

Содержание SAVE-P VSR 150/B

Страница 1: ...Document in original language 271400 v1 0 SAVE P VSR 150 B User Manual GB...

Страница 2: ...stemair UAB All rights reserved E OE Systemair UAB reserves the rights to change their products without notice This also applies to products already ordered as long as it does not affect the previousl...

Страница 3: ...To change the temperature 7 3 2 7 To change the airflow 7 3 2 8 To set a week schedule 8 4 Maintenance 9 4 1 Maintenance Schedule 9 4 2 To access internal components 9 4 3 To change filters 10 4 3 1...

Страница 4: ......

Страница 5: ...temair will require these in the case of a warranty claim 1 3 Type label Before calling your service representative make a note of the specification and production number from the type label which can...

Страница 6: ...AVE LIGHT control panel Fig 2 Explanation of symbols SAVE LIGHT is a basic control panel for SAVE series resi dential air handling units SAVE LIGHT allows to change airflow levels and indicates when a...

Страница 7: ...nsation when the unit has been stopped 3 1 3 To cancel sleep mode Press any button to cancel the sleep mode SAVE LIGHT returns to the sleep mode after 3 minutes of inactivity All control panel lights...

Страница 8: ...e number and the second number indicates a total number of pages available Many options show up in a form of the pop up window Select the option from the displayed list in the pop up window and press...

Страница 9: ...ick information screen shows the following information 1 Time 2 Outdoor temperature 3 Current User mode Alarm 4 Fan speed off Minimum Low Normal High Maximum 5 Supply air temperature 6 Relative humidi...

Страница 10: ...irflow setting in Week Schedule Manual Manual selection of airflow levels The unit can be set run at one out of four available airflow speeds Off Low Normal High Note The fan can be set to OFF by acti...

Страница 11: ...ttings of all modes can be modified in Service menu 3 2 6 To change the temperature Touch the thermometer symbol on the home screen to open the temperature settings window Use up and down arrows to in...

Страница 12: ...Use arrow buttons and to increase or decrease value Confirm with OK button Note Scheduled time can start but never end at midnight 00 00 The latest END TIME period is 23 59 Scheduled time cannot go to...

Страница 13: ...1 Maintenance Schedule Task 6 months 1 year 3 years When necessary General inspection X Filter change X X Fan cleaning X Heat exchanger cleaning X X Belt replacement X Checking and cleaning louvres d...

Страница 14: ...e new filters Make sure that the correct filter types are inserted 5 Remount and fasten the filter cover plates and connect the unit to mains 6 Reset the filter time See chapter 4 3 1 4 3 1 To reset t...

Страница 15: ...if not secured Make sure that small children are not beneath the unit when the heat exchanger is removed Caution Beware of sharp edges during mounting and maintenance Use protective gloves Even if the...

Страница 16: ...eeded 4 Clean the fans with a cloth or a soft brush Do not use water White spirit can be used to remove obstinate deposits Allow the fans to dry properly before remounting 5 Remount the fans Don t for...

Страница 17: ...ouvres can be done as necessary 4 7 2 Checking the outdoor air intake Leaves and pollution could plug up the air intake grille and reduce the capacity Check the air intake grille and clean as necessar...

Страница 18: ...11 Check visible duct runs for damage and or build up of dust pollution 12 Check diffuser louvre openings The unit cannot be controlled control functions are stuck 1 Reset control functions by discon...

Страница 19: ...230V 1 50Hz 7 Disposal and recycling This product is compliant with the European WEEE Directive and related national waste legislation When disposing the unit follow your local rules and regulations...

Страница 20: ...SAVE P VSR 150 B User Manual 271400 en_GB 2021 04 30 v1 0 Systemair UAB Lin st 101 LT 20174 Ukmerg LITHUANIA Phone 370 340 60165 Fax 370 340 60166 www systemair com...

Отзывы: