4.2.7

To connect the ducts to the
product

To install the product with circular duct systems, Systemair
recommends to use CCM or CCMI flanged plate.

To install the product in rectangular duct systems, Systemair
recommends to use the flexible connection FGV.

To install the product in rectangular duct systems, obey the
steps below.

1

Put flexible connections on each side of the product and
use self drilling screws with sealing tape in between to
connect the product and the flexible connections. Sys-
temair recommends to use FGV flexible connections to
attach the duct to the product. The flexible connections
are available as an accessory. Refer to

13 Accessory

overview page 33

.

2

Put the ducts on each side of the product with the at-
tached flexible connections.

3

To connect the flexible connection, use self drilling
screws with sealing tape in between.

4

If you install the product near a duct bend, do these
steps to prevent vibrations, unwanted noise and de-
creased air pressure:

a.

Measure the distance (A) between the product and
the duct bend.

b.

Make sure that the distance (A) is a minimum of 2.5
x the diameter (B) of the duct system. For circular
ducts, (B) is the nominal diameter. For rectangular
ducts, (B) is the hydraulic diameter.

A

A

B

5

Electrical connection

Warning

The MUB/F fan switches off in case of
fire. The MUB/F fan has no motor
protection fitted as standard. Any kind of
motor protection and frequency
converter must be bypassed in case of
fire.

5.1

To do before the electrical
connection

• Make sure that the electrical connection agrees with the

product specification on the motor name plate.

• Make sure that the environment for electrical connection

is clean and dry.

• Make sure that the wiring diagram that is included with the

supply of the product agrees with the terminals in the con-
nection box.

5.2

To connect the product to the
power supply

• Complete the electrical connection for the motor. Refer to

the motor wiring diagram that is included with the product.

• Make sure that the cross section of the protective earthing

is equal to or larger than the cross section of the phase
conductor.

• Install a circuit breaker in the permanent electrical installa-

tion, with a contact opening of a minimum 3 mm at each
pole.

• If a residual current device (RCD) is installed, make sure

that it is an all-current sensitive RCD. Consider if the prod-
uct has a frequency converter, uninterruptible power sup-
ply (UPS), or an EC motor. EC motors have a leakage
current to earth that is <=3.5 mA.

5.3

Speed controller for AC
motors

Note:

The speed controller alternatives are different for different
motor types. Make sure that your motor is compatible with
the speed controller type before you use it.

The speed can be controlled by voltage reduction using a
transformer. It is also possible to control the fan speed with
frequency converter if the installed frequency converter has
built in all-pole sine filter and shielded cables are not needed.

10

Содержание MUB/F 042 400

Страница 1: ...ntenance instruction EN MUB Multibox fan AC EC MUB CAV VAV Multibox fan EC MUB T Thermo multibox fan AC EC MUB T ECO Thermo multibox fan AC EC MUB T S Thermo multibox fan AC EC MUB F Smoke extract fan...

Страница 2: ...duct with an AC motor 12 7 3 To stop the product 12 7 3 1 To stop the product in an emergency 12 8 Maintenance 13 8 1 Maintenance schedule 13 8 2 To clean the product 13 8 3 Spare parts 13 9 Troublesh...

Страница 3: ...20 UKCADeclaration of Conformity Thermo fans 41 21 UKCA Declaration of Conformity Smoke extract fans 42...

Страница 4: ......

Страница 5: ...al ventilation with air tempera tures up to 55 C and smoke extraction with temperatures up to 400 C for 2 hours The MUB Filter fan is a square multibox fan supplied with an AC or an EC motor and a bui...

Страница 6: ...8 3 5 6 1 Casing 2 Motor inside casing on MUB T fans and MUB T ECO fans 3 Motor connection box 4 Fan impeller 5 Name plate 6 Air flow direction arrow 7 Safety switch not applicable for MUB T ECO fans...

Страница 7: ...e standard ISO5801 1 Type designation Product name dimension and motor type Refer to 1 5 1 Type designation page 4 2 Current A 3 Input power W 4 Frequency Hz 5 Certifications 6 Scannable code 1 7 Volt...

Страница 8: ...le AC motor 3 phase 400 V EC K Elec tronically commutated 1 phase 230 V D4 4 pole AC motor 3 phase 400 V EC Elec tronically commutated 1 phase 230 V D4 6 4 6 pole AC mo tor 3 phase 400 V D4 L 4 pole A...

Страница 9: ...sories that are not original accessories from Systemair The product is used without motor protection 2 Safety 2 1 Safety definitions Warnings cautions and notes are used to point out specially importa...

Страница 10: ...size Visit www systemair com for more de tailed information about your product The product is not to be used by persons including chil dren with reduced physical sensory or mental capabil ities or la...

Страница 11: ...n where there is space for commissioning troubleshooting and maintenance Make sure that the installation location is clean and dry for full safety during electrical work Make sure that the installatio...

Страница 12: ...To set up the controller for CAV VAV page 9 6 If the product is installed outside install weather protec tion Systemair recommends installing weather protec tion roof WSD and weather protection grille...

Страница 13: ...nding on product size See table below Table 1 K factor Model K factor MUB CAV VAV 025 315 EC 143 MUB CAV VAV 025 355 EC 132 MUB CAV VAV 042 400 EC 159 MUB CAV VAV 042 450 EC 213 MUB CAV VAV 042 450 EC...

Страница 14: ...Any kind of motor protection and frequency converter must be bypassed in case of fire 5 1 To do before the electrical connection Make sure that the electrical connection agrees with the product speci...

Страница 15: ...is found at www systemair com 6 1 To do before the commissioning Make sure that the installation and electrical connection are correctly done Visually examine the product and accessories for damage Ma...

Страница 16: ...d with the 0 10 V signal speed con troller If an external speed controller is not installed ad just the fan speed directly with the integrated potentiometer 7 2 To start a product with an AC motor 1 S...

Страница 17: ...protective equipment and the me chanical protective equipment operates correctly X X Make sure that you can read the name plates of the product X X Examine all cable connections for damage Make sure t...

Страница 18: ...l the product operates smoothly Refer to 6 Commissioning page 11 The air output is not sufficient The fan impeller does not turn in the correct direction Make sure that the electrical connection is co...

Страница 19: ...al blockage Remove the blockage Phase loss occurs If the motor is a 3 phase motor make sure that no phase is missing The motor does not rotate A component in the power supply is defective Do a check o...

Страница 20: ...lectrical connection and installation 2 Recycle the product parts and the packaging at an appli cable disposal location 3 Obey the local and national requirements for disposal 11 Warranty For warranty...

Страница 21: ...uency enclosure class weight Refer to the name plate Refer to 1 5 Name plate page 3 for more information Motor data Refer to the motor name plate or the technical documentation from the motor manufact...

Страница 22: ...21 820 678 720 820 MUB 100 630 710 21 1020 878 920 1020 12 2 2 Product dimensions MUB CAV VAV fans Note If the unit of measure is not specified the dimensions are given in millimetres C B A F D E A B...

Страница 23: ...oduct dimensions MUB T fans Note If the unit of measure is not specified the dimensions are given in millimetres D C B F E A A B C D E F MUB T 025 355 520 378 420 520 1 inch 21 MUB T 045 400 450 500 6...

Страница 24: ...the dimensions are given in millimetres G E D C F A B A B C D E F G MUB F 042 400 783 670 400 410 548 590 670 MUB F 042 450 783 670 400 454 548 590 670 MUB F 062 500 915 800 560 520 676 720 800 MUB F...

Страница 25: ...MUB T S 025 315 EC L 520 378 420 520 684 1 inch 21 MUB T S 042 355 D4 690 548 590 690 790 1 inch 21 MUB T S 042 355 EV 690 548 590 690 805 1 inch 21 MUB T S 042 400 D4 520 378 420 520 684 1 inch 21 M...

Страница 26: ...C 820 678 720 820 1012 1 inch 21 MUB T S 062 560 EC 820 678 720 820 1050 1 inch 21 MUB T S 100 630 D4 1020 878 920 1020 1201 1 inch 21 12 2 6 Product dimensions MUB T ECO fans Note If the unit of meas...

Страница 27: ...ms 12 3 1 Wiring diagrams for AC fans Refer to the wiring diagram documents that are included in the supply of the product The wires in the motor cables have these colours Wire Colour 10 V Red 0 10 V...

Страница 28: ...N N L L N N N M M REE 4 Surface mounting Note Starting currents must be considered when you select the speed controller type Products that are used with this speed controller must have a built in ove...

Страница 29: ...ormer knob is in one of the positions 1 5 B Mains supply C Earth D Fan E Thermostat F Motor protection If the motor protection is not in use Tk must be looped together FRQ5S E 6A Frequency converter w...

Страница 30: ...fixed steps The steps are adjusted by using the control knob on the front of the unit RTRD2 7 N L1 L2 L3 L3 L2 L1 N PE U V W PE V W U TB TB TK TK RT L L N 230 V AC RT FS FS Y M 3 0 1 A A A B C D F E A...

Страница 31: ...0 1 5 4 2 3 C B D E G F RTRDU 0 1 A A A A If the function is not necessary the terminals must be bridged B Contact rating 230 V AC maximum 1 A C Time switch D OFF ON E OFF ON only by reset F Mains su...

Страница 32: ...asic EC Basic 230V AC 1 IN Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND MTV 1 10 MTV 1 010 1 IN Vac 2 IN Vac 4 Out 5 Out 10V 0 10V GND 230V AC S 5EC FRQ MTP 10 GND 10V A 10V 0 10V GND EC Vent EC Vent IN RPM...

Страница 33: ...y NO Relay NC 10V 0 10V GND Din1 12 3 6 Wiring diagrams for demand control for EC motors EC Basic EC Basic T for temperature control EC Basic 230V AC 1 IN Vac 2 IN Vac 4 Out 5 GND 10V 0 10V GND EC Bas...

Страница 34: ...stem has 2 units The control board CB and the room unit RU Connect the fan to the control board and remove the internal potentiometer EC Vent IN RPM PWM IN 10V OUT PWN GND TACH optional 10V 0 10V PWM...

Страница 35: ...GND A D PT1000 24V N out N in L out L in IN3 IN2 IN2 A Mains supply 230 V 1 AC 10 A B Analogue sensor for example pressure sensor C Analogue sensor for example pressure sensor type PT1000 D Digital s...

Страница 36: ...System neutral Mains supply 24 V AC Signal neutral Signal neutral Output minimum 0 10V Output maximum 0 10V PCA 1000D2 Pressure controller For constant air volume control CAV or variable air volume co...

Страница 37: ...to www systemair com or speak to Systemair technical support 1 3 2 3 4 4 5 6 1 7 8 9 1 FGV Flexible connection 2 WSG Weather protection grille 3 UGS Transition connections square to round 4 Tune AHU...

Страница 38: ...e For more information about accessories refer to www systemair com or speak to Systemair technical support 1 2 3 4 5 1 RSA Silencer 2 EVH Flexible connection 3 LRK Air operated damper 4 GFL Counter f...

Страница 39: ...C 2014 30 EU DIN EN IEC 61000 6 1 2019 11 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2020 0...

Страница 40: ...Part 6 1 Generic standards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2020 09 Electromagnetic compatibility EMC Part 6 4 Generic standards Emission stan...

Страница 41: ...y EMC 2014 30 EU DIN EN IEC 61000 6 1 2019 11 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 20...

Страница 42: ...ompatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2020 09 Electromagnetic compatibility EMC Part 6 4 Generic standa...

Страница 43: ...019 11 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2020 09 Electromagnetic compatibility EMC...

Страница 44: ...esidential commercial and light industrial environments DIN EN IEC 61000 6 4 2020 09 Electromagnetic compatibility EMC Part 6 4 Generic standards Emission standard for industrial environments The Rest...

Страница 45: ...1 2019 11 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2020 09 Electromagnetic compatibility...

Страница 46: ...andards Immunity for residential commercial and light industrial environments DIN EN IEC 61000 6 4 2020 09 Electromagnetic compatibility EMC Part 6 4 Generic standards Emission standard for industrial...

Страница 47: ...43...

Страница 48: ...rves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair GmbH Seeh fer Str 45 9...

Отзывы: