Maxi 1100-2000 

 

Operation- and maintenance instructions 

 

204414

 

 

Systemair AB

2

2

 

Warning 

In order to avoid electrical shock, fire or other damage that might occur in connection with faulty use and 
operation of the unit, it is important to consider the following: 

 

  The system must be installed according to the installation description. 

  Insulate mains supply before service or cleaning of the heat recovery unit. 

  Tumble dryer must not be connected directly to the ventilation system. 

  Make sure the filter is mounted in its place before running the system. 

  Maintenance must be performed according to the instructions. 

 

Maintenance 

Maintenance of the MAXI should normally be carried out 3 – 4 times a year. Apart from general cleaning 
the following should be observed: 
 

NOTE! For the Maxi 1100 both the inspection doors are fastened to the unit casing by 8 toggle 

locks. The two inspection doors are connected between themselves with hinges. When the unit 

is installed with the doors facing down make sure that the inspection doors are only opened one 

at the time (4 toggle locks), never open all of the 8 toggle locks at the same time unless you want 

to remove both the inspection doors. 

 

1.  Changing Supply/Extract air filter, indicates as “Filter guard” in the control panel (fig.3 and 4). 

The bag filter cannot be cleaned and must be changed as necessary. New filters can be ordered from 
Systemair. Pressure guards monitor Supply and Extract air filters. 
Initial pressure drop is approx.: Maxi 1100 90Pa and Maxi 2000 140Pa and the final pressure drop is 
approx. 200-220Pa for all sizes. 

 

2.  Checking the heat exchanger (Once a year), (fig.3 and 4). 

After long times use dust may build up in the exchanger and block the airflow. It is vital to clean the 
exchanger regularly to maintain high efficiency. The heat exchanger can easily be taken out of the unit. 
Wash in hot soapy water or use pressure air. Do not use detergent containing ammonia. 

 

3.  Checking the fans (once a year), (fig.3 and 4). 

Even if the required maintenance, such as changing of filters is carried out, dust and grease may slowly 
build up inside the fan (pos.1 and 2 in fig. 3 and 4). This will reduce the efficiency. 
The fans may be cleaned with a cloth or a soft brush. Do not use water. White spirit can be used to 
remove obstinate settlements. Allow drying properly before remounting. 

 

4.  Cleaning extract louvers and inlet diffusers (when necessary) 

The system supplies outdoor air to the building and extracts the used indoor air via the duct system and 
diffusers/louvers.  Diffusers and louvers are mounted in ceilings/walls in bedroom, living room, wet 
rooms, WC etc. Remove diffusers and louvers and wash in hot soapy water as required. 
(Diffusers/louvers must be put back with their original settings and positions in order not to unbalance 
the system). 

 

5.  Checking the outdoor air intake 

Leaves and pollution could plug up the air intake grille and reduce the capacity. Check the air intake 
grille at least twice a year, and clean if necessary. 

 

6.  Checking the duct system (when necessary) 

Dust and grease settlements may build up in the duct system even if filters are changed regularly. This 
will reduce the efficiency of the installation. The duct runs should therefore be cleaned/ changed when 
necessary. Steel ducts can be cleaned by pulling a brush soaked in hot soapy water, through the duct 
via diffuser/louver openings or special inspection hatches in the duct system (if fitted). 

 

NOTE!

 In addition roof cowl must be checked once a year and cleaned as necessary. 

Содержание MAXI 1100

Страница 1: ...Corrigo ver no 3 0 1 03 GB MAXI 1100 2000 Compact Air Handling Unit Operation and maintenance instructions...

Страница 2: ...rite enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button 7d Brown cable 6 Mounting holes 7e Black cable Description 1 Fan supply air 8 Damper Heat exchanger 2 Fan extract air 9 Water...

Страница 3: ...Locking brackets Exchanger block 21 By pass section 7 Motor for bypass damper 22 Transformer fan speed 8 Filter guard supply air filter 23 Transformer 24V AC control circuit 9 Fan guard supply fan 24...

Страница 4: ...E28 Controller 6 Locking brackets Exchanger block 20 Electronic temperature controller Pulser EL units 7 Motor exchanger shut off damper 21 Transformer fan speed 8 Filter guard supply air filter 22 Tr...

Страница 5: ...ng the design installation start up and operation to ensure a proper fail free operation of the unit The key to proper and safe operating of the unit is to read this manual thoroughly use the unit acc...

Страница 6: ...parameters Password As default MAXI comes with the following password for different levels Operator 1111 Service 2222 How to operate See fig 2 The menus in the Corrigo E are organized in a horizontal...

Страница 7: ...e LED for alarms pos 2 in fig 2 is blinking if there are non acknowledged alarms and shine steadily if the alarms are still active but have been acknowledged If there are multiple alarms use UP DOWN b...

Страница 8: ...W VHWWLQJ WUDFW DLU WHPS FWXDO 6HWS KHFN DQG PDNH VXUH WKDW FRUUHFW WLPH DQG GDWH LV GLVSOD HG LI QRW FKDQJH WKH VHWWLQJV 7LPH DWH HHNGD ULGD 6HW WKH ZHHN VFKHGXOH IRU KRZ LW V LQWHQGHG IRU WKH XQLW W...

Страница 9: ...SOD WKH DYDLODEOH PHQXV LQ WKH 2SHUDWRU OHYHO IROORZHG E WKH 6HUYLFH OHYHO PDQXDO 7R HQWHU 6HUYLFH OHYHO XVH FRGH LQ WKH FFHVV ULJKWV PHQX RU RSHUDWRU OHYHO XVH FRGH 1RWH 7R SHUIRUP PRUH DGYDQFHG VHWW...

Страница 10: ...RWRUV KDYH EHHQ RSHUDWLQJ 6 6XSSO DLU IDQ KDXVW DLU IDQ 6HOHFWHG IXQFWLRQV RQWURO IXQFWLRQ WUDFW DLU FRQWURO DQ FRQWURO ORZ FRQWURO 6KRZV W SH RI DLU WHPSHUDWXUH FRQWURO WKH XQLW LV FRQ JXUHG IRU 6KRZ...

Страница 11: ...H RXWSXWV 6KRZV WKH VWDWXV RI WKH QDORJXH RXWSXWV LJLWDO RXWSXWV 6KRZV WKH VWDWXV RI WKH LJLWDO RXWSXWV 7HPSHUDWXUH WUDFW DLU WHPS FW 6HWS 6KRZV WKH FRQ JXUHG WHPSHUDWXUH FRQWURO HIDXOW LV WUDFW DLU W...

Страница 12: ...ORZ FRQWURO RU 3UHVVXUH FRQWURO ORZ FRQWURO 6 FWXDO P K 6HWS P K 6KRZV DLU RZ IRU WKH VXSSO DLU IDQ FRQVWDQW DLU RZ FRQWURO 2QO YLVLEOH LI WKH XQLW LV FRQ JXUHG IRU ORZ FRQWURO ORZ FRQWURO 6 6HWS P K...

Страница 13: ...DLU IDQ 2QO YLVLEOH LI WKH XQLW LV FRQ JXUHG IRU 3UHVVXUH FRQWURO 9 9 3UHVVXUH FRQWURO 6 6HWS 3D 6HWS 3D 6HW WKH H WHUQDO SUHVVXUH VHW SRLQW IRU QRUPDO VSHHG DQG UHGXFHG VSHHG IRU WKH VXSSO DLU IDQ 2X...

Страница 14: ...SHU GD IRU FRQWLQXRXV UXQQLQJ LQDFWLYDWHV WKH SHULRG 1RWH WKH VHWWLQJV LQ WKH FRPPLVVLRQLQJ UHFRUG 7LPHU UHGXFHG VSHHG 6HW ZHHN VFKHGXOH 0RQGD WR 6XQGD ROLGD IRU UHGXFHG VSHHG 3RVVLEOH WR VHW SHULRGV...

Страница 15: ...VLJQDOV ZLOO FKDQJH DFFRUGLQJO LI WKH DUH LQ XWR PRGH W LV DOVR SRVVLEOH WR PDQXDOO FRQWURO HDFK RI WKH WHPSHUDWXUH RXWSXW VLJQDOV LQGLYLGXDOO 6LQFH OHDYLQJ DQ RI WKH RXWSXWV LQ PDQXDO FRQWURO ZLOO G...

Страница 16: ...R 6HW WKH SXPS FRQWURO IRU WKH FRROLQJ FRLO WR XWR 2Q RU 2II LUH GDPSHU XWR 6HW WKH LUH GDPSHU WR XWR 2SHQ RU ORVH 1RWH 1HHGV WR EH DFWLYDWHG LQ RUGHU WR EH YLVLEOH KHUH RQ JXUDWLRQ RI UH GDPSHU IXQFW...

Страница 17: ...3 EDQG DFWLYH 3 EDQG DFWLYH PHDQV WKDW WKH IURVW SURWHFWLRQ FRQWUROOHU ZLOO VWDUW RYHUULGLQJ WKH KHDWLQJ RXWSXW ZKHQ WKH IURVW SURWHFWLRQ WHPSHUDWXUH LV OHVV WKDQ GHJUHHV DERYH WKH VHW IURVW DODUP GH...

Страница 18: ...QW FRQ JXUDWLRQ FDQ EH VDYHG LQ D VHSDUDWH PHPRU DUHD DQG FDQ ODWHU EH UHVWRUHG XVLQJ WKH SUHYLRXV PHQX 5HVWRUH XVHU VHWWLQJV 6HOHFW HV RU 1R RQILJXUDWLRQ RQWURO IXQFWLRQ RQWURO IXQFWLRQ 0RGH 5RRP FRQ...

Страница 19: ...EOH KHDWLQJ VHTXHQFH LV LQLWLDWHG L H KRZ ORQJ D FRROHU URRP WHPSHUDWXUH WKDQ VHW WHPSHUDWXUH FDQ EH DFFHSWHG DQ RXWSXW ZKHQ IUHH FRROLQJ 6 6HW WKH IDQ VSHHG LQ SHUFHQWDJH RI WKH QRUPDO VSHHG IRU HDFK...

Страница 20: ...6HW WKH FRROLQJ UHFRYHU WR HV RU 1R 6HW WKH FRROLQJ OLPLW WKH GLIIHUHQFH LQ WHPSHUDWXUH EHWZHHQ H WUDFW DLU DQG RXWGRRU DLU WKDW DFWLYDWHV WKH FRROLQJ UHFRYHU FFHVV ULJKWV RJ RQ RJ RQ QWHU SDVVZRUG F...

Страница 21: ...R WKDW WKH VHQVRUV FDQ SHUIRUP D WHPSHUDWXUH PHDVXUHPHQW I DERYH FRQGLWLRQV DUH PHW WKH IUHH FRROLQJ IXQFWLRQ LV VWDUWHG LI QRW WKH XQLW JRHV EDFN WR 2 SRVLWLRQ I WKH RXWGRRU VHQVRU LV QRW ORFDWHG LQ...

Страница 22: ...er Once a year fig 3 and 4 After long times use dust may build up in the exchanger and block the airflow It is vital to clean the exchanger regularly to maintain high efficiency The heat exchanger can...

Страница 23: ...quired D Cleaning of diffusers louvers required E Cleaning of fans exchanger block required F Is roof unit air intake clogged G Duct system Check visible duct runs for damage and or build up of dust p...

Страница 24: ...rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www s...

Отзывы: