Maintenance

5.1

Commissioning

Danger

• All electrical connections must be carried out by an authorized installer and in accordance with local rules

and regulations.

Before initial operation, check the following:

• Electrical connection has been properly completed.

• Protective earth has been connected.

• Safety devices in place (protection grid).

• Leftover installation materials and foreign materials have been removed from the casing.

Testing the installation:

• Adjustment may be required in the electrical compartment during test (i.e. changing of the potentiometer), however

during operation the lid must be closed.

When putting into operation, check the following:

• Connection data corresponds to the specifications on the nameplate: Maximum v6%, -10%, according to IEC

38. Rated current must not be exceeded with more than 5% at rated voltage.

• Smoothness of motor operation, (no abnormal noises).

Sound levels exceeding 70 dB(A) may occur depending on size (see www.systemair.com for detailed information).

6

Maintenance

6.1

Important

Danger

• Make sure that the mains supply to the unit is disconnected before performing any maintenance or

electrical work!

• Fan impeller has come to a complete standstill.

• Should the supply cable be damaged, it must be replaced by the manufacturer, its service agent or

similarly qualified persons in order to avoid a hazard

• The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use

protective clothing.

• Do not lift the fans by the connecting cable, connection box, motor bracket, impeller or inlet cone.

6.2

Cleaning the fan

Warning

• Make sure that the mains supply to the unit is disconnected before performing any maintenance or

electrical work!

• Fan impeller has come to a complete standstill.

Caution

• Beware of sharp edges during maintenance, use protective gloves. Risk of injury through pinching.

The fan should be cleaned when necessary, at least once a year to avoid imbalance and unnecessary damage to the
bearings. The fan bearings are maintenance free and should only be replaced if damaged. Do not use a high-pressure
cleaner (steam jet) when cleaning the fan. Ensure that the fan impeller's balance weights are not moved or the fan im-
peller distorted. Listen for abnormal operating noise.

145899 | A007

Содержание KVK Silent 200

Страница 1: ...Document in original language 145899 A007 KVK Slim 200 500 KVK Slim 200 500 EC KVK Silent 200 500 KVK Silent 200 500 EC Operation and Maintenance Instructions GB...

Страница 2: ...Systemair AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously...

Страница 3: ...ormation 3 4 1 General 3 4 2 Technical data 4 4 2 1 Dimensions 4 4 2 2 Performance 6 4 2 3 Wiring diagram 8 4 3 Transportation and storage 9 5 Installation 9 5 1 Commissioning 10 6 Maintenance 10 6 1...

Страница 4: ......

Страница 5: ...g reached by upper or lower limbs EN 60 335 1 Household and similar electrical appliances Safety Part 1 General requirements EN 60 335 2 80 Household and similar electrical appliances Safety Part 2 80...

Страница 6: ...ental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children sha...

Страница 7: ...ilent 200 500 KVK Silent 200 500 EC are intended for transporta tion of air in air handling systems The fans are meant for use in ducted systems and should always be duct connected on the inlet side N...

Страница 8: ...0 EC 773 657 548 450 300 250 KVK Slim 250 773 657 548 450 300 250 KVK Slim 315 945 825 694 590 451 315 KVK Slim 315 EC 866 746 694 590 414 315 KVK Slim 355 961 842 870 766 496 355 KVK Slim 355 EC 976...

Страница 9: ...250 836 720 630 533 382 250 872 KVK Silent 315 1022 906 768 672 536 315 1165 KVK Silent 315 EC 946 826 768 672 493 315 1125 KVK Silent 355 1041 922 952 848 578 355 1383 KVK Silent 355 EC 1041 922 852...

Страница 10: ...s Pa 19706 19705 4 6V 10V KVK Silent 200 EC 2 6V 6 6V 0 0 1 0 2 0 3 0 4 0 5 0 100 200 300 400 500 0 500 1000 1500 m h Q m s Ps Pa 19730 19729 4 6V 6 8V 10V KVK Slim 250 EC 2 4V 0 0 1 0 2 0 3 0 4 0 5 0...

Страница 11: ...Q m s Ps Pa 19037 19036 4 7V 6 9V 10V KVK Silent 400 EC 2 4V 0 0 5 1 1 5 2 0 200 400 600 0 2000 4000 6000 m h Q m s Ps Pa 19249 19244 19243 5V 7 2V 10 KVK Slim 500 EC 2 5V 0 0 5 1 1 5 2 0 200 400 600...

Страница 12: ...250 315 Slim Silent GY GY BN BU BK YE GN TK TK N L C Fig 4 KVK 355 500 Slim Silent RD YE BU WH BU BK YE GN 10V GND Tacho 0 10V N L Fig 5 KVK 200 250 Slim Silent EC RD YE BU WH BN WH WH BU BK YE GN 10...

Страница 13: ...rried out by an authorized installer and in accordance with local rules and regulations Warning The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with...

Страница 14: ...sure that the mains supply to the unit is disconnected before performing any maintenance or electrical work Fan impeller has come to a complete standstill Should the supply cable be damaged it must b...

Страница 15: ...e fan not start please contact your place of purchase 8 Deinstallation dismantling Deinstall and dismantle the fan in reverse order of installation and electrical connection 9 Disposal Ensure material...

Страница 16: ...KVK Silent 200 500 KVK Silent 200 500 EC Operation and Maintenance Instructions 145899 en_GB 2019 03 15 A007 Systemair Sverige AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00...

Отзывы: