Through normal operation and during its defrost mode, the HRV may produce some condensation. This water should flow into a nearby drain, or be taken
away by a condensate pump. The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point.
A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the unit.
Drain line installation
1
2
3
3.
1.
Min ¼” (6mm)
2.
12” (305mm)
2” (50mm) min
1” (25mm) min
2” (50mm) min
or