2. Prepare the following assemblies on the site.
2-core shielded cable
86 Electrician box
Qty.(embeded
into wall)
Note to installation of
SYSCONTROL CWC
01:
No.
Name
Remarks
Specification
(only for reference)
Max 350m
1. One KNX module can only connect with one indoor unit;The KNX module should
connect to indoor XYE ports, can’t connect to outdoor XYE ports.
2. Circuit of
CWC
01 is low voltage circuit. Never connect it with a standard
220V/380V circuit or put it into a same Wiring Tube with the circuit.
3. Do not attempt to extend the shield cable by cutting, if it is necessary, use
Terminal Connection Block to connect.
4. After finishing connection, do not use Megger to have the insulation check to the
signal wire.
5. The default physical address of the
CWC
01 is 15.15.255,If there are two or
more KNX modules, then the physical addresses can not repeat.The physical
address can be changed by ETS software.