26/31 |
S-RA1
Type of Activation B24-W
This type of activation has cable connectors for the supply and communication unit (the communication unit is not part
of the mechanism).
• The circuit switch between wires 2 and 3 is not part of the damper supply.
• When the power supply is connected to wires 1 and 3, the actuator moves to the OPEN position.
• When the power supply is connected to wires 1 and 2, the actuator moves to the CLOSED position.
Notes:
•
CAUTION:
Main power supply voltage!
• Parallel connection of more actuators possible when the power consumption and switching threshold is observed!
• Combination of power supply voltage and safety extra-low voltage not permitted at the both auxiliary switches.
Legend for Activation Type B24-W
The actuator has connection plugs.
Supply: With a 3-pole plug that is applicable, for example, for BKNE230-24
Auxiliary switch: With a 6-pole plug that is applicable, for example, for BKNE230-24