3

Connect the other end of the tubes to the differential
pressure transmitter’s inlet ports.

Caution

Be careful when connecting the hoses to
the inlet ports, the thin inner connections
of the inlets are very sensitive. The lid
should be kept closed while performing
the connections, or the thin tubing might
detach from the sensor.

a.

Connect the red tube from the supply air duct to +
on one of the pressure transmitter.

b.

Connect the blue tube from the extract air duct to -
on the other pressure transmitter.

+

+

4

Connect the cables according to

5.1 Wiring diagrams

.

4.3

Description of the pressure
transmitter

1 2 3 4

A

B

C

D

1

2

3

4

5

6

E

Figure show dip-switches to the left, position OFF.

A.

DIP-switches

B.

Push button

C.

Status LED

D.

Sensor 1

E.

Terminals

4.3.1

To set the pressure range on
the pressure transmitter

Dip-switch setting

Pressure range (Pa)

2 = OFF, 3 = OFF, 4 = OFF

0...50

2 = ON, 3 = OFF, 4 = OFF

0...100

2 = OFF, 3 = ON, 4 = OFF

0...300

2 = ON, 3 = ON, 4 = OFF

0...500

2 = OFF, 3 = OFF, 4 = ON

0...700

2 = ON, 3 = OFF, 4 = ON

0...1000

2 = OFF, 3 = ON, 4 = ON

0...1250

4.3.2

To zero point calibrate the
pressure sensors

1.

Disconnect the pressure ports before zero setting.

2.

Let the product warm up for 10 minutes before attempt-
ing the procedure.

3.

Quick press the push button. Zero point calibration takes
about 5 seconds. The yellow LED will light up while the
zero point calibration is in progress.

4.

If the yellow LED starts blinking during the zero point cal-
ibration, the procedure has failed. Ensure that the pres-
sure ports are open and try again.

5.

If the procedure still fails, a sensor error is present and
the product must be replaced.

4.3.3

To reset to factory settings

• Long press (10 s) the push button

The red and yellow LED lights will flash alternating for the
duration of the operation. The product will then reset and
restart.

4.3.4

Status LED light

The red LED lights up when the power is on and goes out
when the built-in sensory circuit is ready for use.

Flashing red LED after power-up:

The product has lost important system settings and must be
taken back to the factory for reprogramming.

Steady red LED during normal operation:

The product is damaged and should be returned or
discarded.

3

Содержание 145946

Страница 1: ...Installation instruction EN VAV duct pressure control kit...

Страница 2: ...ure sensors 3 4 3 3 To reset to factory settings 3 4 3 4 Status LED light 3 5 Technical data 4 5 1 Wiring diagrams 4 5 2 Topvex SR TR SC TC 4 5 3 Topvex FR FC SF 5 6 To configure the pressure transmit...

Страница 3: ...ble 3 Tubes 4 Pressure measuring taps 2 Product liability Systemair is not liable for damages that the product causes in these conditions The product is incorrectly installed operated or maintained Th...

Страница 4: ...e the installation of the product Examine the packaging for transportation damage and re move the packaging from the product carefully Examine the product and all components for damage 4 2 To install...

Страница 5: ...4 ON 0 1000 2 OFF 3 ON 4 ON 0 1250 4 3 2 To zero point calibrate the pressure sensors 1 Disconnect the pressure ports before zero setting 2 Let the product warm up for 10 minutes before attempt ing t...

Страница 6: ...act air PTS Pressure transmitter supply air T15 T16 Terminals in Topvex SR TR SC TC control unit G0 G 42 40 Terminals in Topvex FR FC SF control unit 5 2 Topvex SR TR SC TC WH YE BN YE BN GN GN WH WH...

Страница 7: ...BN GB G G0 42 40 1 2 3 4 1 2 3 4 PTS PTE PTE PTS 6 To configure the pressure transmitter in the air handling unit controller 6 1 For SR TR SC TC FC FR 6 1 1 To log in 1 Open the log in window 2 Selec...

Страница 8: ...ressure range in the pressure transmitter 1 Select Configuration from navigation icons 2 Select Configuration wizard 3 Select Set up pressure control 4 Set sensor range 5 Select In Outputs 6 Select Co...

Страница 9: ...alog inputs use the navigation path Configuration I O allocation settings Analog inputs 10 Select Pressure extract air and repeat steps 7 and 8 6 1 5 To adjust the fan pressure set points Data setting...

Страница 10: ...Auto Settings Configuration Access rights Sensor settings Control function Fan control Extra sequence Y4 Fan control Pressure control 6 2 3 To set the adjusted working range Set the adjusted working...

Страница 11: ...tion Access rights Control temp Control pressure Alarm settings Alarm limits Alarm delays Restore alarm Control dev SAF 25 0 Pa Control dev EAF 25 0 Pa 6 2 6 To allocate in and outputs Menu level 1 Me...

Страница 12: ...air AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair Sverige AB...

Отзывы: