background image

Other applicable NFPA standards, local codes and the requirements of the 
authority having jurisdiction.

Failure to follow these directions may result in failure of the device to report 
a waterflow condition. System Sensor is not responsible for devices that have 
been improperly installed, tested or maintained.

1.   Mount the detector where there is adequate clearance for installation and re-

moval and a clear view of it for inspection. See 

Figure 1

 for mounting dimen-

sions.

2.   Locate the detector 6 to 7 feet above the floor to protect from accidental 

damage.

3.   On horizontal runs, position the detector on top or side of the pipe. Do 

not mount it upside down.

4.   Mount detector at least 6 inches from a fitting which changes the direc-

tion of the waterflow, or no less than 24 inches from a valve or drain.

5.   BE SURE DIRECTION-OF-FLOW ARROW AND DIRECTIONAL COVER 

MATCHES ACTUAL DIRECTION OF FLOW IN THE PIPE. See 

Figure 3

.

MOUNTING INSTRUCTIONS

1.   This WFDTNRN waterflow detector is designed to fit only the appropri-

ate tee fitting.

  

NOTE:

 The outlet branch of tee must have a 1-inch NPT thread. Do not 

use a reducer to achieve the correct thread size. Failure to follow this 
instruction will result in failure of the detector to report a waterflow con-
dition.

2.   WFDT units are shipped without the paddles mounted to the actuator. Se-

lect the correct size paddle for the tee being used the appropriate nominal 
pipe diameter size is molded on the surface of the paddles. Align hole on 
stem of paddle with hole on actuator lever. Fasten together using a #4-40 

3

/

8

-inch fillister head screw supplied in bag assembly. See 

Figure 2

. Use 

only the screw provided with the WFDTNRN. Drive screw head through 
hole in paddle until it seats firmly to actuator lever surface. No washer is 
required. For paddle replacement refer to Maintenance section.

3.   Thread detector onto tee fitting and tighten with wrench. Use of thread 

sealant or tape is recommended. Use height gage (located at end of pad-
dle tree) to ensure proper depth of detector on tee fitting. See 

Figure 

1

. Height gage must fit between top of tee fitting and under side of hex 

tee adapter. A gap between gage and tee adapter is acceptable. When 
correctly installed, the detector must face in the proper direction of wa-
terflow and be aligned with the pipe, the provided directional cover il-
lustrates flow direction for device.

4.   Remove the plastic cover with the tamper proof wrench provided. Move 

the actuator lever back and forth to check for binding. If the vane binds, 
remove the detector and correct the problem before proceeding.

CAUTION

Be sure the direction-of-flow arrow and directional cover points in the correct 
direction, otherwise a waterflow condition will go unreported. See 

Figure 3

.

FIGURE 3. DIRECTIONAL COVER

OPERATIONAL TESTING

Always notify a central station monitoring waterflow alarms before repairing, 
maintaining, or testing waterflow alarm devices.

1.   Fill the fire sprinkler system and check for leaks around the WFDTNRN. 

If it leaks, check to see that the fittings are tight. If leak persists, drain the 
system and remove the detector (see removal instructions under Main-
tenance). Check for damaged threads or cracked fitting. Reinstall detec-
tor and check again for leaks. Do not proceed until all leaks have been 
stopped.

2.   With cover removed, connect an ohmmeter or continuity tester across 

(COM and B-NO) terminal switch contacts. The ohmmeter should show an 
open circuit, no continuity (when the red switch buttons are depressed).

3.   Deflect the actuator lever to release the switch buttons. The ohmmeter or 

continuity tester should show a short circuit when the switch buttons are 
released.

4.   Open the inspector’s test valve to allow the detector to indicate a flow 

condition. The detector should remain activated until the inspector’s test 
valve is closed. Air pockets in the sprinkler system may prevent the de-
tector from firing immediately.

5.   Replace the cover and tighten the security screws with the tamper proof 

wrench. Store wrench is a secure place.

FIELD WIRING

1.   The WFDTNRN has two SPDT switches. Switch contacts (COM and 

B-NO) are closed when water is flowing and open when water is not 
flowing. Connect the switches as shown in 

Figure 4

 depending on the 

application.

2.   When connected to a listed sprinkler/fire alarm control panel, the initiat-

ing circuit must be be unable to be silenced.

3.   A ground screw is provided with all WFDTNRN units. When grounding 

is required, clamp wire with screw in hole located between conduit en-
trance holes. See 

Figure 5

.

4.   Use proper waterproof conduit fittings where required.

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a de-
vice to which AC power is applied. Doing so may result in severe injury or death.

When utilizing switches at voltages greater than 74VDC 

 or 49VAC 

 

means to provide all–pole disconnection must be incorporated in the field wir-
ing, such as a circuit breaker.

NOTCHED COVER INDICATES FLOW DIRECTION AT A

DISTANCE FROM MULTIPLE VIEWING ANGLES

W0382-00

  

I56-4044-004 

 

 11-09

Содержание WFDTNRN

Страница 1: ...is supplied with 12 paddles One paddle is provided for each size of the threaded sweat or plastic tee See Figure 1 and approximate tee depth chart Each paddle has an indication that shows the pipe size and type of tee to be used with FIGURE 1 MOUNTING DIMENSIONS 3 1 2 2 5 8 4 TEE DEPTH DESIGNEDTO FITWITHIN 2 X 4 STUDWALL CONSTRUCTION PLASTICVANE TEE FITTING INSTALLATION GAUGE END OF PADDLETREE MUS...

Страница 2: ...f wrench provided Move the actuator lever back and forth to check for binding If the vane binds remove the detector and correct the problem before proceeding CAUTION Be sure the direction of flow arrow and directional cover points in the correct direction otherwise a waterflow condition will go unreported See Figure 3 FIGURE 3 DIRECTIONAL COVER OPERATIONAL TESTING Always notify a central station m...

Страница 3: ...ority having jurisdiction for leaks and replace if leaks occur Test detectors at least quarterly as described in Operational Testing to insure proper operation Test more often if required by the authority having jurisdic tion Under normal conditions System Sensor waterflow detectors should provide years of trouble free service However if the switch enclosure becomes faulty request Part No FS RT an...

Страница 4: ...ectors have a normal service life of 10 15 years Hard water systems however may substantially reduce waterflow detector service life 4 Waterflow detectors are not a substitute for insurance Building owners should always insure property and lives being protected by sprinkler systems 5 If valves controlling the water supply to a sprinkler system are closed vane type wa terflow detectors will not wor...

Отзывы: