background image

N770-05-00 

I56-0480-013R

Failure to follow these directions may result in failure of the device to report 
a waterflow condition. System Sensor is not responsible for devices that have 
been improperly installed, tested or maintained.

1.   Mount the detector where there is adequate clearance for installation and 

removal and a clear view of it for inspection. See 

Figure 1

 for mounting 

dimensions.

2.  Locate to protect from damage, 6-7 feet above the floor.
3.   On horizontal runs, position the detector on top of the pipe or on the side 

of it. Do not mount it upside down because condensation may collect in 
the housing and impair the operation of the detector.

 

 For vertical flow applications, mount detector on pipe where upflow con-
ditions exist. Failure to do so may prevent unit from operating properly.

4.   Mount detector at least 6 inches from a fitting which changes the direc-

tion of the water flow, or no closer than 24 inches from a valve or drain.

5.   BE  SURE  DIRECTION-OF-FLOW  ARROW  MATCHES  ACTUAL  DIREC-

TION OF FLOW IN THE PIPE.

figUre 2. assembLY Diagram:

TAMPER 

PROOF 

WRENCH 

(P/N WFDW)

COVER

DELAY 

MECHANISM 

(P/N A3008-00)

GASKET 

(WFDT ONLY)

WATERFLOW

FLOW

TERMINAL BLOCK 

(REPLACEMENT P/N 

A77-01-02)

GROUND SCREW 

(GREEN)

MOUNTING 

PLATE

PADDLE 

(P/N PRK9)

FILLISTER 

HEAD SCREW

1˝ NPT 

THREAD

ACTUATOR 

LEVER

COVER TAMPER 

SWITCH

(P/N 546-7000)

W0127-00

moUnTing insTrUcTions

1.   The WFDT and WFDTH waterflow detectors are designed to fit only the 

appropriate tee fitting.

 

 

NOTE:

 Leg of tee perpendicular to flow of water must have a 1-inch NPT 

thread. Do not use a reducer to achieve the correct thread size. Failure 
to follow this instruction will result in failure of the detector to report a 
waterflow condition.

2.   WFDT and WFDTH units are shipped without paddles mounted to the 

actuator.  Select  the  correct  size  paddle  for  the  type  of  tee  being  used. 
Align hole on stem of paddle with hole on actuator lever. Fasten together 
using a #4-40×

1

4

-inch fillister head screw supplied in bag assembly. See 

Figure 2

. Use only the screw provided with the unit. Drive screw head 

through hole in paddle until it seats to actuator lever surface. No washer 
is required. For paddle replacement refer to Maintenance section.

3.   Carefully roll the vane opposite the direction of flow and insert through 

tee.  Thread  detector  onto  tee  fitting  and  tighten  with  wrench.  Use  of 
thread sealant or tape is recommended. Use height gage (located at end 
of paddle tree) to ensure proper depth of detector on tee fitting. See 

Fig-

ure 1

. Height gage must fit between top of tee fitting and under side of 

hex tee adapter. A gap between gage and tee adapter is acceptable. When 
correctly installed, the detector must face in the proper direction of wa-
terflow and be aligned with the pipe.

4.   Remove the metal cover. Move the actuator lever back and forth to check 

for binding. If the vane binds, remove the detector and correct the prob-
lem before proceeding.

CAUTION

Be sure the direction-of-flow arrow points in the right direction, otherwise a 
waterflow condition will go unreported. See 

Figure  2

.

preoperaTion TesTing

1.   Fill  the  sprinkler  system  with  water  and  check  for  leaks  around  the 

WFDT  or  WFDTH.  If  there  is  a  leak,  check  to  see  that  the  fittings  are 
tight. If leak persists, drain the system and remove the detector (see re-
moval instructions under Maintenance). Check for damaged threads or 
cracked fitting. Reinstall the detector and check again for leaks. Do not 
proceed until all leaks have been stopped.

2.   Connect an ohmmeter or continuity tester across (COM and B-NO) ter-

minal switch contacts. The ohmmeter should show an open circuit, no 
continuity.

3.   Deflect  the  actuator  lever  and  hold  it  until  the  pneumatic  delay  shaft 

releases the switch buttons. The ohmmeter or continuity tester should 
show  a  short  circuit  after  the  delay  has  elapsed.  If  there  is  no  delay, 
check the setting of the delay adjustment dial.

fieLD Wiring

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on 
a device to which AC power is applied. Doing so may result in severe injury 
or death.

When utilizing switches at voltages greater than 74VDC 

 or 49VAC 

 

means  to  provide  all–pole  disconnection  must  be  incorporated  in  the  fixed 
wiring, such as a circuit breaker.

1.   The WFDT and WFDTH have two SPDT switches. Switch contacts (COM 

and B-NO) are closed when water is flowing and open when water is not 
flowing. Connect the switches as shown in 

Figure 3

 depending on the 

application.

2.   When connected to a listed sprinkler/fire alarm control panel, the initiat-

ing circuit must be non-silenceable.

3.   A ground screw is provided with all units. When grounding is required, 

clamp wire with screw in hole located between conduit entrance holes. 
See 

Figure 2

.