FIGURE 4. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS 

TO FLOOR

Degrees*

Percent of 

Rating

0

100

5-25

90

30-45

75

50

55

60

45

65

35

70

35

75

30

80

30

85

25

90

25

A0468-00

WIRING AND MOUNTING

All wiring must be installed in compliance with the National Electric Code 
and the local codes as well as the authority having jurisdiction. Wiring must 
not be of such length or wire size which would cause the notification appli-
ance to operate outside of its published specifications. Improper connections 
can prevent the system from alerting occupants in the event of an emergency. 

Wire sizes up to 12 AWG (2.5 mm²) may be used with the mounting plate. The 
mounting plate ships with the terminals set for 12 AWG wiring. 

Make wire connections by stripping about 

3

/

8

" of insulation from the end of 

the wire. Then slide the bare end of the wire under the appropriate clamping 
plate and tighten the clamping plate screw. 

See Figure 5 for wiring terminals and strip guide reference.

1. Connect the speaker. (See Figure 5.)
2. There are two rotary switches on the back of the product. The first switch 
is used to select either 25 or 70.7 volts input and the second switch is used to 
select the input power of ¼, ½, 1 or 2 watts. (See Figure 6.) 

FIGURE 5. WIRING DIAGRAM AND WIRING TERMINALS

 

(-)

(+)

(-)

(+)

(-)

(+)

(-)

(+)

From FACP

OUTPUT

To Next Device or EOL

From Amplifier

INPUT

To Next Device or EOL

  

 

 A0519-01

Wiring Terminals

1. Negative (-). Line in and out
2. Positive (+). Line in and out
3. Positive (+). Line in and out

NOTE: Do not loop electrical wiring un-
der terminal screws. Wires connecting 
the device to the control panel must be 
broken at the device terminal connec-
tion in order to maintain electrical su-
pervision.

FIGURE 6. SPEAKER WATTAGE AND VOLTAGE SETTINGS

 

  

A0419-01

FIGURE 1. CANDELA SELECTOR

 

 

  

A0486-00

CURRENT DRAW AND AUDIBILITY RATINGS

For the strobe, the current draw for each setting is listed in Tables 1 and 2.

TABLE 1. WALL-MOUNT STROBE CURRENT DRAW (mA) 

Candela

8-17.5 

Volts

16-33 Volts

DC

DC

FWR

15

88

43

60

NOTE:

 Products set at 15 and 30 

candela automatically work on ei-
ther 12V or 24V power supplies. 
The products are not listed for 
12V DC operation when set to any 
other candela settings.

30

143

63

83

75

-

107

136

95

-

121

155

110

-

148

179

135

-

172

209

185

-

222

257

 

TABLE 2. CEILING-MOUNT STROBE CURRENT DRAW (mA) 

Candela

8-17.5 

Volts

16-33 Volts

DC

DC

FWR

15

87

41

60

NOTE:

 Products set at 15 and 30 

candela automatically work on 
either 12V or 24V power supplies. 
The products are not listed for 12V 
DC operation when set to any other 
candela settings.

30

153

63

86

75

-

111

142

95

-

134

164

115

-

158

191

150

-

189

228

177

-

226

264

 

FIGURE 2. WALL LIGHT OUTPUT –  

FIGURE 3. VERTICAL 

HORIZONTAL DISPERSION 

DISPERSION, WALL TO FLOOR

Degrees*

Percent of 

Rating

Degrees*

Percent of 

Rating

0

100

0

100

5-25

90

5-30

90

30-45

75

35

65

50

55

40

46

55

45

45

34

60

40

50

27

65

35

55

22

70

35

60

18

75

30

65

16

80

30

70

15

85

25

75

13

90

25

80

12

Compound 45 

to the left

24

85

12

Compound 45 

to the right

24

90

12

A0467-00

    

A0469-00

*Tolerance of ±1 degree is permitted.